Data Sheet

Maximal11FE Expandable Power System provide system designers and installers with
optimum power choices and the highest levels of versatility. They provide 12VDC,
24VDC, or 12VDC and 24VDC simultaneously via two (2) single output power sup-
ply/chargers. Includes AC fail, low battery and battery presence monitoring. Enclosure
facilitates up to four (4) 12VDC/12AH batteries. All interconnecting equipment must
be UL Listed.
Maximal11FE
Expandable Power System
Rev. DSMaximal11FE_05192015
Overview
Specifications
Optional Field Installable UL Listed Sub Assembly Modules
Maximal11FE
Location A - ACM4, ACM4CB, MOM5, PD4UL, PD4ULCB,
PD8UL, PD8ULCB, PD16W & PD16WCB.
A
Power Supply
Power Supply
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
B
C
Location B - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.
Input:
120VAC 60Hz, 7.0 amp input.
Output:
12VDC and/or 24VDC outputs.
Maximum output current:
Options P/S 1 P/S 2
A) 12VDC @ 4 amp 12VDC @ 4 amp
B) 24VDC @ 4 amp 24VDC @ 4 amp
C) 12VDC @ 4 amp 24VDC @ 4 amp
Power-limited outputs.
Aux. power-limited output rated @ 1 amp (unswitched).
Overvoltage protection.
Fuse Ratings:
Power Supply input fuse rated @ 5 amp/250V.
Fire Alarm Disconnect:
Supervised Fire Alarm disconnect (latching or
non-latching) 10K EOL resistor. Operates on a
normally open (NO) or normally closed (NC) trigger.
Supervision:
AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 2 hours.
Battery fail & presence supervision (form “C” contacts).
Supervision (cont’d):
Low power shutdown. Prevents deep battery discharge.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 1.54 amp.
Automatic switch over to stand-by battery when AC fails.
Battery fuse rated @ 7.5 amp/32V.
Visual Indicators:
Green AC Power LED indicates 120VAC present.
AC input and DC output LED indicators.
Electrical:
Operating temperature: 0º C to 49º C ambient.
• BTU/Hr.:
- 12VDC: 48.14 BTU/Hr.
- 24VDC: 73.70 BTU/Hr.
- 12VDC and 24VDC: 98.26 BTU/Hr.
System AC input VA requirement: 840VA.
Mechanical:
Enclosure Dimensions (H x W x D approx.):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
Enclosure accommodates up to four (4) 12AH batteries.
Product weight (approx.): 32.1 lbs. (14.6 kg).
Shipping weight (approx.): 39.25 lbs. (17.8 kg).
Location C - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.

Summary of content (2 pages)