Data Sheet

Maximal77F
Access Power Controller
Rev. DSMaximal77F_05192015
Maximal77F Access Power Controller distributes and switches power to access
control systems and accessories. It converts a 120VAC 60Hz input into sixteen
(16) independently controlled 24VDC fuse protected outputs. These Fail-Safe/
Fail-Secure power outputs may be converted to dry form “C” contacts. The out-
puts are activated by an open collector sink or normally open (NO) dry trigger
input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units
will route power to a variety of access control hardware devices including: Mag
Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables
Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary
devices. The fire alarm disconnect feature is individually selectable for any or all
of the sixteen (16) outputs. All interconnecting equipment must be UL Listed.
Overview
Specifications
Input:
120VAC 60Hz, 9 amp input.
Power supply input options:
a) Two (2) common power input for either ACM8
and lock power (factory installed).
b) Two (2) isolated power inputs (external power
supply is required), (current is determined by the
power supply connected, not to exceed a
maximum of 10 amp total).
Sixteen (16) Access Control System trigger inputs.
Input options:
a) Sixteen (16) normally open (NO) inputs.
b) Sixteen (16) open collector inputs.
c) Any combination of the above.
Output:
24VDC outputs.
Maximum output current:
Options P/S 1 P/S 2
A 24VDC @ 9.6 amp 24VDC @ 9.6 amp
Sixteen (16) independently controlled outputs.
Output options:
a) Sixteen (16) Fail-Safe and/or Fail-Secure
power outputs.
b) Sixteen (16) form “C” 5 amp rated relay outputs.
c) Any combination of the above.
Sixteen (16) auxiliary power outputs (unswitched)
(outputs are rated 2.5 amp).
Filtered and electronically regulated outputs (built-in
power supply).
Thermal and short circuit protection with auto reset.
Fuse Ratings:
Power Supply input fuse rated @ 6.3 amp/250V.
ACM8 boards main fuse is rated at 10 amp.
Fused outputs are rated @ 2.5 amp each.
Supervision:
AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 2 hours.
Supervision (cont’d):
Battery fail and presence supervision (form “C” contacts).
Low power shutdown. Shuts down DC output terminals
if battery voltage drops below 71-73% for 12V units
and 70-75% for 24V units (depending on the power
supply). Prevents deep battery discharge.
Features:
Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
sixteen (16) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry
contact input.
b) Polarity reversal input from FACP signaling circuit.
Alarm output relay indicates that FACP input is
triggered (form “C” contact rated @ 1 amp 28VDC).
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 3.6 amp per p/s board.
Automatic switch over to stand-by battery when AC fails.
Zero voltage drop when unit switches over to battery
backup (AC failure condition).
Visual Indicators:
Red LEDs indicate outputs are triggered
(relays energized).
Green LED indicates FACP disconnect is triggered.
AC input and DC output LED indicators.
Electrical:
Operating temperature: 0º C to 49º C ambient.
BTU/Hr.: 235.85 BTU/Hr.
System AC input VA requirement: 1080VA.
Mechanical:
Enclosure Dimensions (H x W x D approx.):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm).
Enclosure accommodates up to four (4) 12AH batteries.
Product weight (approx.): 33.9 lbs. (15.4 kg).
Shipping weight (approx.): 41.2 lbs. (18.7 kg).
Maximal77F