Installation Guide

- 4 - NetWay8 / NetWay16
3. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1d, pg. 4).
4. Plug the grounded AC line cord (included) into the IEC 320 connector of the NetWay unit (Fig. 1e, pg. 4).
Plug unit into a reliable earth grounded socket. When using multiple units the sum of the individual name
plate ratings should not exceed the supply circuit rating. Do not connect to a receptacle controlled by a switch.
5. Connect structured cables from port marked [IN] on NetWay to the corresponding inputs of an ethernet
switch or video server (Fig. 1b, pg. 4, Fig. 5, pg. 6).
Note: All cabling and wire must be UL Listed and/or Recognized wire suitable for their application.
6. Connect structured cables from port marked [OUT] on NetWay to PoE compliant camera/edge devices
(Fig. 1a, pg. 4, Fig. 5, pg. 6).
Note: For UL294 applications, the products are to be tested as part of a complete Access Control System and
in accordance with UL Listed Access Control Devices.
Note: All interconnected devices must be UL Listed.
7. Upon completion of wiring set illuminated master power disconnect circuit breaker to the RESET (ON)
position (Fig. 1d, pg. 4).
8. Port status LEDs on the NetWay will initialize when PoE devices are connected as follows:
- LED will illuminate when devices are IEEE 802.3af compliant.
- LED will blink once and illuminate when devices are IEEE 802.3at compliant (PoE+).
Port Status and LED Flash Codes:
Port Status Flash Codes Description
All Ports Off Sequential LED Port Scan No devices connected
Port Off OFF LED OFF
Port On ON LED ON
Class 4 detection Port Blinks 2 times Enables power to PoE devices.
Non-compliant Device 2Hz Will prevent port from turning on.
Port Overload Fault 5Hz Will prevent port from turning on.
4 Port Overload Grouped 5Hz
4 LEDs
Will prevent ports from turning on.
8 Port Overload Grouped 5Hz
LED’s 1-8 Power Supply Overload for ports 1-8.
LED’s 9-16 Power Supply Overload for ports 9-16.
Fig. 1
AC POWER
NetWay8 & NetWay16 - Rear Panel
NetWay8 - Front Panel
NetWay16 - Front Panel
1a 1b
1c
1d 1e
1a OUT 1-8 (NetWay8), OUT 1-16 (NetWay16): Structured cable to PoE compliant cameras/edge devices.
1b IN 1-8 (NetWay8), IN 1-16 (NetWay16): Structured cable to ethernet switch or video server.
1c LED(s) 1-8 (NetWay8), 1-16 (NetWay16): Port status LEDs.
1d Illuminated master power disconnect circuit breaker (switch):
OFF position Circuit breaker tripped Switch not illuminated.
RESET (ON) position Switch illuminated.
1e IEC 320 Connector: 115VAC 60Hz (grounded line cord included).