PT724A Series 365 Day 24 Hr. Timer/Controller Installation Guide Models Include: • PT724A - Timer Module • PT724AE - Timer Module and Enclosure. • DPT724A - Timer Module Equipped w/Snap Track for Din Rail Mount. Rev.
Overview: Models PT724A/DPT724A/PT724AE are extremely versatile 24 Hour 365 Day Event Timers designed to support a wide range of applications. Such applications include: Home and Building Automation, Security, Access Control, Lighting Control, Etc. PT724A/DPT724A/PT724AE are equipped with an independently controlled form “C” relay contact that provides many latching and/or momentary operations during a program schedule of your choice.
The four (4) output relay modes consist of: Relay OFF - De-energizes the relay until a relay ON event is detected Relay ON - Energizes the relay until a relay OFF event is detected. Disable - Used to cancel an existing programmed event. Pulse - Momentarily energizes the relay for a selectable time period of 1 sec. to 15 secs. Time is displayed in 24 hr. military format. Terminal Identification Table: Terminal Legend Function/Description NO, C, NC Dry Contact output used to switch controlled devices.
Programming Instructions: A. Setting Clock/Calendar: Upon initial power up Depress SET Depress ENTER RLY OFF SU 01:01 will appear in display. ENTER to SET TIME will appear in display. 01/01/01 SU/01:01 will appear in display. Enter the current date, day of week and time (military) by depressing UP and DWN to make the selection then depress ENTER to accept. Next select either DS (daylight savings mode) or ST (standard time mode) by depressing set until ENTER to appears in display.
C. Setting Block Events (weekly repeat): Depress SET until ENTER to SET BK appears in display. Depress ENTER BK=SA/SU will appear in display. TIME=DS Flashing cursor will appear at the location of the first day of the week desired. Depress UP and DWN to select day. Depress ENTER to confirm selection, then cursor will appear at the location of the last day of the week desired. Depress UP and DWN to select day. Depress ENTER to confirm selection. Depress ENTER again to escape.
G. Delete All Events: All previously programmed events can be deleted by depressing SET until ENTER to CLR MEM appears in display. Depress ENTER CLEAR MEMORY? will appear in display. Depress ENTER PRESS UP & ACCEPT will appear in display. Depressing UP push button will now clear all events previously programmed. If you wish to escape from this selection depress any of the other push buttons: SET, ENTER and DWN. PT724AE Enclosure Dimensions: 8.5”H x 7.5”W x 3.5”D 7.25" 3.63" 0 1.25" TOP ONLY 3.
Customer Event Log Event # Relay # Day/Block Holiday Dates -7- Event Type
Customer Event Log Event # Relay # Day/Block Holiday Dates Event Type Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Made in U.S.A. L09D IIPT724A/PT724AE/DPT724A series - Rev.