ACM Series Feature:
• 12 or 24 AC or DC operation (setting not required).
• Power supply input options:
a) One (1) common power input (board and lock power).
b) Two (2) isolated power inputs (one (1) for board power
and one (1) for lock/hardware power).
• Eight (8) Access Control System trigger inputs.
• Input options:
a) Eight (8) normally open [NO] inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
• Eight (8) independently controlled fuse protected outputs.
• Output options
(AL400ULACM, AL600ULACM, AL1012ULACM and AL1024ULACM):
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form “C” 5 amp rated relay outputs
c) Any combination of the above.
• Output options (AL400ULACMCB, AL600ULACMCB,
AL1012ULACMCB and AL1024ULACMCB):
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
• Eight (8) auxiliary power outputs (unswitched).
• ACM8 main fuse is rated @ 10 amp.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable
for any or all of the eight (8) outputs.
• Fire Alarm disconnect input options:
a) Normally open [NO] or normally closed [NC] dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• Alarm output relay indicates that FACP input is triggered.
• Green LED indicates FACP disconnect is triggered.
• 115VAC 60Hz. input.
• Filtered and electronically regulated output(s).
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type batteries.
• Zero voltage drop upon transfer to battery backup.
• Automatic switch over to stand-by battery when AC fails.
• AC fail, low battery and battery presence supervision.
• AC input and DC output LED indicators.
• Includes cam lock and battery leads.
AL600ULACM
access power controllers with power supply/chargers