SMP5CTX Series Power Supply/Chargers Models Include: SMP5CTX SMP5PMCTX SMP5PMCTXX - Single Output. SMP5PMP4 - Four (4) Fuse Protected Outputs. SMP5PMP4CB - Four (4) PTC Protected Outputs. SMP5PMP8 - Eight (8) Fuse Protected Outputs. SMP5PMP8CB Eight (8) PTC Protected Outputs. SMP5PMP16 - Sixteen (16) Fuse Protected Outputs. SMP5PMP16CB - Sixteen (16) PTC Protected Outputs. Installation Guide Rev. 093003 More than just power.TM Installing Company: ________________ Service Rep.
Overview: Altronix SMP5CTX Series power supply/chargers convert a 115VAC or 230VAC, 50/60Hz input into a regulated 12VDC or 24VDC output up to 4A of continuous load current (see specifications).
Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding.
Power Supply Board: Terminal Identification: Terminal Legend Function/Description L, G, N Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral. – DC + 12VDC / 24VDC @ 4A continuous output. *AC FAIL NC, C, NO Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC. *Low Battery NC, C, NO Used to indicate low battery condition, e.g. connect to alarm panel.
115VAC/ 230VAC P Dist Mo L Optio St Green Fig. 1 5A 250V Fig. 1a Switch disables power mains line voltage input. If stand-by battery (batteries) are connected, the DC output remains on ON ON OFF AC FAIL NC NC C AC DC C NO NO --- BAT + NC C NO --- BAT + See LED Diagnostics, pg.
Power Distribution Module(s): Fig. 2 - PD4/PD4CB F1 Used on PTC Models F2 F3 F4 1P, 2P, 3P, 4P = FUSED OUTPUTS 1N, 2N, 3N, 4N = COMMON OUTPUTS LED 1N 1P 2P 2N 3N 3P 4P 4N INPUT COMMON POWER OUTPUTS DC Output to devices From Power Supply Board (Factory Installed) Fig. 3 - PD8/PD8CB 1 2 3 4 5 6 7 8 ON Used on PTC Models OFF SW1 P D1 FUSED POWER OUTPUTS R1 N LED INPUT COMMON POWER OUTPUTS DC Output to devices From Power Supply Board (Factory Installed) Fig.
Enclosure Dimensions (BC300): SMP5CTX, SMP5PMCTX, SMP5PMP4, SMP5PMP4CB, SMP5PMP8, SMP5PMP8CB, SMP5PMP16, SMP5PMP16CB 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm) Enclosure accommodates up to two (2) 12VDC/7AH batteries. Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix). 1.40” (35.6mm) 4.85” (123.2mm) 4.85” (123.2mm) 1.40” (35.6mm) 1.20” (30.5mm) 0.75” (19.1mm) 3.25” (82.6mm) 1.20” (30.5mm) 0.75” (19.1mm) 12.5” (317.5mm) 11.0” (279.4mm) 1.20” (30.
Enclosure Dimensions (BC400): SMP5PMCTXX 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) Enclosure accommodates up to two (2) 12VDC/12AH batteries. 1.5” (38.1mm) 4.615” (117.2mm) 4.615” (117.2mm) 1.5” (38.1mm) 1.75” (44.5mm) 1.25” (31.8mm) 4.5” (114.3mm) 1.1” (27.9mm) 12.23” (310.6mm) 4.5” (114.3mm) 1.1” (27.9mm) 1.375” (34.9mm) 1.5” (38.1mm) 1.25” (31.8mm) 1.5” (38.1mm) 0.91” (23.1mm) 0.91” (23.1mm) 1.125” (28.6mm) 15.5” (393.7mm) 2.0” (50.8mm) 2.0” (50.8mm) 5.0” (127.0mm) 0.79” (20.