Always “On” UPS Systems Inc. GES V-Series – Single Phase Input, Single Phase Output Uninterruptible Power Supply GES-801V, GES-102V, GES-102VR, GES-152V, GES-152VR, GES-222V, GES-222VR Line Interactive (PWM): 800VA, 1kVA, 1.5kVA, 2.2kVA User Manual Version 2.
Always “On” UPS Systems Inc. SAVE THESE INSTRUCTIONS This manual contains important instructions for the GES-801V, GES-102V, GES-102VR, GES-152V, GES-152VR, GES-222V, GES-222VR and should be followed during installation and maintenance of the UPS and batteries. The UPS contains voltages that are potentially hazardous. Please contact our dealers or qualified personnel for service.
Always “On” UPS Systems Inc. SAFETY INSTRUCTIONS 1. The UPS has its own internal energy source (battery), therefore the output receptacles may have electricity present even though the UPS is disconnected from the utility power. 2. The DC voltage provided from the internal battery is 24Vdc for 801V, 102V, 152V, 102VR, 152VR. 48Vdc for 222V, 222VR. 3. The isolated ground wire (green or green with yellow stripe) must meet national wire requirements. 4.
Always “On” UPS Systems Inc. Table of Contents 1. INTRODUCTION 1 2.2. PRESENTATION Front Panel Rear Panel 2 2 4 3.1. 3.2. 3.3. 3.4. 3.5. 3.6. 3.7. 3.8. 3.9. INSTALLATION Unpacking and Inspection Placement Connect Computer Interface (Optional) Connect to Utility Charging the Battery Connecting the Loads Connecting the Telephone / Modem / Ethernet Lines (Optional) Storage Conditions Extended Storage 6 6 6 6 6 6 6 7 7 7 4.1. 4.2. 4.3. 4.4. 4.5. 4.6. 4.7.
Always “On” UPS Systems Inc. 1. INTRODUCTION The V-Series is a Line Interactive UPS system that includes the newest and latest technology enhancements. The Line Interactive technology with AVR function (online voltage boost-up & buck-down) allows for a wide input voltage range of 90 to 150VAC. The V-Series UPS is ideal protection for microprocessor control loads. After the UPS has been turned “On” it will protect the load from transients, spikes and other power aberrations.
Always “On” UPS Systems Inc. 2. PRESENTATION 2.1. Front Panel I 1 2 3 4 5 6 Figure 2.1.1 Tower Front Panel. Always " "On 7 8 9 1 5 6 10 Figure 2.1.2 102VR Front Panel I Line Mode Boost INV Mode Buck Battery Fault Always "On" 6 5 1 2 3 4 Figure 2.1.3 152/222VR Front Panel. 2 Version 2.
Always “On” UPS Systems Inc. 1 2 3 4 5 6 7 8 9 10 REPLACE BATTERY indicator (RED LED) This LED illuminates when the UPS's batteries are no longer useful and must be replaced. Note: When replacing the batteries, disconnect the utility power and then open the case. Take notice of the polarity before installing the new batteries to avoid a short. BUCK AVR (VOLTAGE REDUCTION) indicator (YELLOW LED) This LED illuminates when the UPS is correcting a high utility voltage condition.
Always “On” UPS Systems Inc. 2.2. 2 Rear Panel 3 1 2 4 1 3 5 6 8 7 8 7 Figure 2.2.1 Rear Panel Left GES-801, 102, 152V Right GES-222V 2 3 8 7 5 6 Figure 2.2.2 Rear Panel GES-102VR INPUT BREAKER IN OUT REMOTE PORT OUTPUT 3 6 8 7 2 Figure 2.2.3 Rear Panel GES-152VR OUTPUT INPUT BREAKER REMOTE 3 8 7 6 2 Figure 2.2.2 Rear Panel GES-222VR 4 Version 2.
Always “On” UPS Systems Inc. 1 2 3 4 5 6 7 8 MAIN POWER This toggle switch is the main power cutoff for the UPS. Use of this switch will remove power from loads and completely shutdown the UPS. COMPUTER INTERFACE Both RS-232 and relay signal (Dry Contact) Interfaces are supplied to support WINDOWS, NOVELL, UNIX, DOS, and other operating systems.
Always “On” UPS Systems Inc. 3. INSTALLATION 3.1. Unpacking and Inspection Examine the packaging for damage. Inform the carrier immediately if damage is noticed. Retain the packaging for future use. 3.2. Placement Install the UPS in a protected area with adequate airflow and free of excessive dust. Do not operate the UPS where the temperature and humidity is outside the specified limits. 3.3.
Always “On” UPS Systems Inc. 3.7. Connecting the Telephone / Modem / Ethernet Lines (Optional) Connect a telephone line, modem line, or 10BaseT line into the telephone / modem / ethernet surge protection sockets on the back of the UPS. The RJ-45 / RJ-11 modular sockets accept standard single line telephone connections and 10BaseT connectors. This connection will require another length of cable. This is optional; UPS will work properly without this connection.
Always “On” UPS Systems Inc. 4. OPERATION 4.1. Switching “On” the UPS For all but the GES-102VR: With the UPS plugged in and utility power present, press and hold the On / Off / Test / Silence Button more than 3 seconds or until the LED is lit. The UPS will perform self-testing each time it is switched “On”. For the GES-102VR: With the UPS plugged in and utility power present, turn the Main Power toggle switch to the “On” position. The UPS will perform self-testing each time it is switched “On”. 4.2.
Always “On” UPS Systems Inc. 4.6. Shutdown Mode In shutdown mode the UPS stops supplying power to the load and waits for the return of utility power. If there is no utility power present, external devices (e.g., servers) connected to the computer interface can command the UPS to shutdown. This is normally done to preserve battery capacity after the graceful shutdown of protected servers. 4.7.
Always “On” UPS Systems Inc. 5. 6. AUDIBLE ALARM 5.1. Back-Up (Slow Alarm) When in back-up mode, the LED flashes every 2 seconds and the UPS sounds an audible alarm. The alarm stops when the UPS returns to line normal operation. Press the On / Off / Test / Silence Button during backup mode to silence the beeping. 5.2. Low Battery (Rapid Alarm) In back-up mode, when the battery energy runs low, the UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to line normal operation.
Always “On” UPS Systems Inc. 6.3. Computer Interface Port The communication port on the back of the UPS may be connected to a host computer. This port allows the computer to monitor the status of the UPS and control the operation of the UPS. Its major functions include the following: 1. The ability to broadcast a warning when the power fails. 2. The ability to close any open files before the battery reserves are exhausted. 3. The ability to turn off the UPS. 4.
Always “On” UPS Systems Inc.
Always “On” UPS Systems Inc. 7. BATTERY REPLACEMENT WARNING: Completing the procedure below will void any remaining warranty on the UPS system. Caution: Do not dispose of battery in a fire. Do not attempt to open the battery. When replacing the battery use tools with insulated handles and remove watches, rings, etc… Your battery should run anywhere from 3-5 years before it needs to be replaced. Please follow the instructions below for easy, trouble free, battery replacement. 1.
Always “On” UPS Systems Inc. 8. TROUBLESHOOTING Please follow the guidelines below for common problems: Check UPS input plug and wiring. Check UPS input voltage. Please prepare the information as follows for service personnel: UPS model number and serial number Description of problem(s) in detail. 8.1.
Always “On” UPS Systems Inc. 9. TOWER SPECIFICATIONS MODEL GES-801V Capacity INPUT 800VA Voltage 1kVA 1.5kVA 2.2kVA Simulated sine wave at Line Input +/-5% Frequency (on battery) 50 or 60Hz +/-0.5% OUTPUT ±13% of nominal (120V) Voltage Regulation AVR Transfer Time 2/4 milliseconds, including detection time Spike Protection 320 joules, 2ms UPS automatic shutdown if overload exceeds 110% of nominal for 60 second or 130% for 3 seconds.
Always “On” UPS Systems Inc. 10. RACK MOUNT SPECIFICATIONS V-SERIES GENERAL INPUT MODEL NO. MAXIMUM CAPACITY GES-801V GES-102V GES-152V GES-222V 800VA / 495W 1kVA / 600W 1.5kVA / 900W 2.2kVA/1320W UPC ORDER CODE 825433 20500 825433 20600 825433 20700 825433 20850 NOMINAL VOLTAGE 120VAC (optional 220VAC) VOLTAGE RANGE + / - 25% FREQUENCY RANGE 50 or 60 Hz (+ / - 5%) NOMINAL VOLTAGE 120VAC VOLTAGE REGULATION CURRENT + / - 13% of nominal 6.87A FREQUENCY OUTPUT 8.33A 12.5A 118.
Always “On” UPS Systems Inc. BATTERY TYPE BATTERY SEALED LEAD ACID - MAINTENANCE FREE QUANTITY 2 VOLTAGE 2 2 24VDC RECHARGE TIME 4 HOURS; FULL LOAD BACKUP HALF LOAD POWER TIME PENTIUM & 17" MON OUTPUT SHORT 4 48VDC RECOVERY = 90%, TYPICALLY ≥ 10 MIN. ≥ 10 MIN. ≥ 10 MIN. ≥ 10 MIN. ≥ 25 MIN. ≥ 25 MIN. ≥ 25 MIN. ≥ 25 MIN. ≥ 35 MIN. ≥ 35 MIN. ≥ 45 MIN. ≥ 70 MIN.
Always “On” UPS Systems Inc. OPERATING TEMPERATURE 0 - 40°C (32 - 104°F) ENVIRONMENT HUMIDITY 0% ~ 90% (Non-Condensing) < 40 dBA AT 1 METER FROM UNIT AUDIBLE NOISE SAFETY APPROVAL SAFETY cUL, EMI / RFI FCC CLASS B SURGE / TRANSIENT PHYSICAL DATA UL1778, CSA C22.2 WxDxH mm (in.) IEEE C62.41 CAT.A 170x450x214 (6.8x18x8.6) 130x382x201 (5.2x15.3x8) WEIGHT in kg (lbs) 13 (28.7) MODEL NO. 15 (33.1) 15.6 (34.4) 26.2 (57.
Always “On” UPS Systems Inc. 11. CONTACT INFORMATION 11.1. Additional Purchases or Upgrades Always “On” UPS Systems Inc. Bldg 1 – 150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext 451 Fax: (250) 491-9775 Email: sales@alwaysonups.com Website: www.alwaysonups.com 11.2. QA / Warranty Questions Always “On” UPS Systems Inc. Bldg 1 – 150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext 209 Fax: (250) 491-9775 Email: qa@alwaysonups.com Website: www.alwaysonups.com 11.3.