d. Close the Bypass breaker – The reserve breaker and reserve static switch are
still conducting. When the maintenance bypass breaker is closed, power will
flow through the bypass loop instead of the reserve loop because the impedance
of the bypass loop is lower.
e. Open the Reserve breaker – You can now open the reserve breaker to put the
ups into manual bypass.
NOTE: To place the unit into Maintenance Bypass mode the fuse holders behind the control
module (where all control PCB’s are stored) must be opened.
The system is now in Manual Bypass mode (or Maintenance Bypass mode).
CAUTION!
If fuse holders have not been opened power is still present and fans will be turning. If fuse
holders are open power is still present at the terminal strip and several terminals on the
PCB’s