CHARGE CURRENT increases the amount of charge current the rectifier/charge supplies the
battery bank. There are three possible options (LO/ME/HI). The factory will set the system at the
optimal charge level for the battery bank provided. To change the level of charge select the
CHARGE CURRENT option then select the level of charge via the UP () and DOWN () keys.
Once the level of charge has been selected confirm with the ENTER () key.
The CHARGE CURRENT can be roughly selected by the simple rule listed below:
CHARGE CURRENT SETTING
10 – 30 min battery back-up LOW
30 min – 1 hour battery back-up MEDIUM
> 1 hour battery back-up HIGH
Selecting the ‘EXIT’ option (blinking instead of pointed by cursor) will return you to MENU 5.
BOOST CHARGE SETTI NG
AUTO- BOOST( MONTH) =04
AUTO- BOOST( BATT LOW) =04 08 12 16 20 24
CHARGE CURRENT=LO EXI T
Figure 14.11.3
B
oost Char
g
e Settin
g
Menu Dis
p
la
y
Pro
g
ram Settin
g
s