12 Functions and operations in the tension control mode
−107−
Note
In the simple mode, keep constant the rate of material feed set by the feed roller, etc. If
the feed rate changes, the tension cannot be kept constant.
Tension [N]
Winding operation
Back tension
Feed rate
Feed roller
Step 2 Setting the tension command value
Set a tension command value calculated per Step 1 under each of eight operation data numbers from 0 to 7.
When the system parameter for analog input signals [SyS-1-05] is set to “Enable,” two analog points and six
digital points are available to assign settings. If the parameter is set to “Disable,” eight digital points are
available to assign settings.
Analog input signals [SyS-1-05]
Operation data Enable (initial value) Disable
No.0
Analog setting
(internal potentiometer VR1)
Digital setting
No.1
Analog setting
(External potentiometer or
external DC voltage)
Digital setting
No.2 to 7 Digital setting
Note
If operation data No. 0 is selected for tension controlled operation, the speed limit value
(p.120) set under operation data No. 0 will also be selected. Different operation data
numbers cannot be selected for the two parameters.
Select a desired tension command value from among the predefined settings, based on a combination of
ON/OFF statuses of M0 to M2 inputs.
Operation data M2 input M1 input M0 input
No.0 OFF OFF OFF
No.1 OFF OFF ON
No.2 OFF ON OFF
No.3 OFF ON ON
No.4 ON OFF OFF
No.5 ON OFF ON
No.6 ON ON OFF
No.7 ON ON ON
Using the internal potentiometer VR1
1.
Set the system parameter for analog input signals [SyS-1-05] to “Enable.”
Note
When a system parameter has been changed, the new parameter will become
effective after the power is cycled. If a 24 VDC power supply is used, also cycle the
24 VDC power supply.
2.
Turn the M0 to M2 inputs OFF and select operation data No. 0.
3.
Set the tension command value using the
internal potentiometer VR1.
Setting range: 0 to 100%
Factory setting: 0%
VR1