9 Functions and operations in the position control mode
−70−
Digital setting
• When the analog input signal parameter [SyS-1-05] is set to “Enable”
1.
Set the system parameter for analog input signals [SyS-1-05] to “Enable.”
Note
When a system parameter has been changed, the new setting will become effective
after the power is cycled. If a 24 VDC power supply is used, also cycle the 24 VDC
power supply.
2.
Use the OPX-2A or MEXE02 to set one of operation data Nos. 1 to 3 as the damping control
frequency.
Setting range: 7.00 to 100.00 Hz
Initial value: 30.00 Hz
3.
Set the application parameter for damping control [APP-4-02] to “Enable.”
4.
Select one of operation data Nos. 1 to 3 based on a combination of ON/OFF statuses of M0
and M1 inputs.
• When the analog input signal parameter [SyS-1-05] is set to “Disable”
1.
Set the system parameter for analog input signals [SyS-1-05] to “Disable.”
2.
Use the OPX-2A or MEXE02 to set one of operation data Nos. 0 to 3 as the damping control
frequency.
Setting range: 7.00 to 100.00 Hz
Initial value: 30.00 Hz
3.
Set the application parameter for damping control [APP-4-02] to “Enable.”
4.
Select one of operation data Nos. 0 to 3 based on a combination of ON/OFF statuses of M0
and M1 inputs.