User manual

10 Functions and operations in the speed control mode
85
Select a desired torque limit value from among the predefined settings, based on a combination of ON/OFF
statuses of M0 to M2 inputs.
Operation data M2 input M1 input M0 input
No.0 OFF OFF OFF
No.1 OFF OFF ON
No.2 OFF ON OFF
No.3 OFF ON ON
No.4 ON OFF OFF
No.5 ON OFF ON
No.6 ON ON OFF
No.7 ON ON ON
Analog setting
1.
Set the system parameter for analog input signals [SyS-1-05] to “Enable.”
Note
When a system parameter has been changed, the new parameter will become
effective after the power is cycled. If a 24 VDC power supply is used, also cycle the
24 VDC power supply.
2.
Combine the ON/OFF statuses of M0 to M2 inputs to select operation data No. 0 or 1.
3.
Connect an external potentiometer or external DC voltage to pins 4 to 6 of the analog I/O
connector (CN6).
Refer to p.42 for details on the connection method.
4.
Set the gain.
Set the torque limit value per 1 V of voltage command in the application parameter for analog torque
limit gain [APP-2-03].
Setting range: 0 to 300%
Initial value: 30%
5.
Adjust the offset.
If there is even a slight margin of error in the voltage value, the torque limit value may not become 0%
even when the voltage command specifies 0 V (minimum value). In this case, adjust the offset using one
of the two methods described below.
Automatic adjustment
1. Set the application parameter for analog input signal automatic offset [APP-2-06] to “Enable.”
2. Input 0 V to the analog input terminal (pin 5 of CN6).
3. Apply the offset for analog torque input using the OPX-2A or MEXE02.
Adjustment using a parameter
1. Set the application parameter for analog input signal automatic offset [APP-2-06] to “Disable.”
2. Set the offset voltage in the application parameter for analog torque limit offset voltage [APP-2-05].
6.
Use an external potentiometer or external DC voltage to set the torque limit value.