User manual
10 Functions and operations in the speed control mode
−86−
Setting example
Setting
example
Analog torque limit
gain [APP-2-03]
Analog torque limit offset
voltage [APP-2-05]
Description
① 30% 0 V
The torque limit value per 1 V of voltage command becomes
30%.
② 10% 0 V
The torque limit value per 1 V of voltage command becomes
10%.
③ 100% 0 V
The torque limit value per 1 V of voltage command becomes
100%.
④ 30% 1 V
The home position of voltage command becomes 1 V. The
gain of torque limit value is the same as in example①.
300
100
-
3
-
10 3
10
4
1
3
2
Voltage command [V]
Output torque [%]
Digital setting
• When the analog input signal parameter [SyS-1-05] is set to “Enable”
1.
Set the system parameter for analog input signals [SyS-1-05] to “Enable.”
Note
When a system parameter has been changed, the new parameter will become
effective after the power is cycled. If a 24 VDC power supply is used, also cycle the
24 VDC power supply.
2.
Use the OPX-2A or MEXE02 to set one of operation data Nos. 2 to 7 as the torque limit value.
3.
Combine the ON/OFF statuses of M0 to M2 inputs to select one of operation data Nos. 2 to 7.
• When the analog input signal parameter [SyS-1-05] is set to “Disable”
1.
Set the system parameter for analog input signals [SyS-1-05] to “Disable.”
Note
When a system parameter has been changed, the new parameter will become
effective after the power is cycled. If a 24 VDC power supply is used, also cycle the
24 VDC power supply.
2.
Use the OPX-2A or MEXE02 to set one of operation data Nos. 0 to 7 as the torque limit value.
3.
Combine the ON/OFF statuses of M0 to M2 inputs to select one of operation data Nos. 0 to 7.