Honeywell User's Manual NX series Constant and variable torque Variable Speed Drives for induction motors Subject to changes without notice
AT LEAST THE 10 FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING. IF ANY PROBLEMS OCCUR, PLEASE CONTACT YOUR LOCAL DISTRIBUTOR. Start-up Quick Guide 1. Check that the delivery corresponds to your order, see Chapter 1. 2. Before taking any commissioning actions read carefully the safety instructions in Chapter 1. 3. Before the mechanical installation, check the minimum clearances around the unit and check the ambient conditions in Chapter 5. 4.
2(110) CONTENTS NXS/P USER’S MANUAL INDEX 1 SAFETY 2 EU DIRECTIVE 3 RECEIPT OF DELIVERY 4 TECHNICAL DATA 5 INSTALLATION 6 CABLING AND CONNECTIONS 7 CONTROL KEYPAD 8 COMMISSIONING 9 FAULT TRACING
3(110) ABOUT THE NXS/P USER'S MANUAL Congratulations for choosing the Smooth Control provided by NX Frequency Converters! The User's Manual will provide you with the necessary information about the installation, commissioning and operation of NX Frequency Converters. We recommend that you carefully study these instructions before powering up the frequency converter for the first time. This manual is available in both paper and electronic editions. We recommend you to use the electronic version if possible.
4(110) NXS/P User's Manual Index 1. 1.1 1.2 1.3 1.4 SAFETY......................................................................................................................................6 Warnings.....................................................................................................................................6 Safety instructions.......................................................................................................................
5(110) 6.1.6 Cable selection and unit installation in accordance with the UL standards...................64 6.1.7 Cable and motor insulation checks ...............................................................................64 6.2 Control unit................................................................................................................................65 6.2.1 Control connections.......................................................................................................66 6.2.
1 6(110) 1. SAFETY SAFETY ONLY A COMPETENT ELECTRICIAN MAY CARRY OUT THE ELECTRICAL INSTALLATION 1.1 Warnings 1 2 3 4 WARNING 5 6 7 8 9 1.2 The NX frequency converter is meant for fixed installations only. Do not perform any measurements when the frequency converter is connected to the mains. Do not perform any voltage withstand tests on any part of NX. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
SAFETY 1.3 7(110) Earthing and earth fault protection The NX frequency converter must always be earthed with an earthing conductor connected to the earthing terminal . The earth leakage current of NX frequency converters exceeds 3.5mA AC. According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied: a. The protective conductor shall have a cross-sectional area of at least 10 mm2 Cu or 16 mm2 Al, through its total run. b.
2 8(110) EU DIRECTIVE 2. EU DIRECTIVE 2.1 CE marking The CE marking on the product guarantees the free movement of the product within the EEA (European Economic Area). NX frequency converters carry the CE label as a proof of compliance with the Low Voltage Directive (LVD) and the Electro Magnetic Compatibility (EMC). The company SGS FIMKO has acted as the Competent Body. 2.2 2.2.
EU DIRECTIVE 9(110) Class T: Frequency converters of this class fulfil the product standard EN 61800-3 (2004) if intended to be used in IT systems. In IT systems, the networks are isolated from earth, or connected to earth through high impedance to achieve a low leakage current. NOTE: if converters are used with other supplies, no EMC requirements are complied with. Class N: The drives of this class do not provide EMC emission protection. These kinds of drives are mounted in enclosures.
2 10(110) EU DIRECTIVE EU DECLARATION OF CONFORMITY We Manufacturer's name: Manufacturer's address: hereby declare that the product Product name: NXS/P Frequency converter Model designation: NXS/P 0003 5…. to 1030 5…. has been designed and manufactured in accordance with the following standards: Safety: EN 61800-5-1 (2003) EMC: EN61800-3 (2004) and conforms to the relevant safety provisions of the Low Voltage Directive (2006/95/EC) and EMC Directive 2004/108/EC.
EU DIRECTIVE EU DECLARATION OF CONFORMITY We Manufacturer's name: Manufacturer's address: hereby declare that the product Product name: NXS/P Frequency converter Model designation: NXS/P 0004 6…. to 0820 6…. has been designed and manufactured in accordance with the following standards: Safety: EN 61800-5-1 (2003) EMC: EN61800-3 (2004) and conforms to the relevant safety provisions of the Low Voltage Directive (2006/95/EC) and EMC Directive 2004/108/EC.
2 12(110) EU DECLARATION OF CONFORMITY We Manufacturer's name: Manufacturer's address: hereby declare that the product Product name: NXS/P Frequency converter Model designation: NXS/P 0004 2…. to 0300 2…. has been designed and manufactured in accordance with the following standards: Safety: EN 61800-5-1 (2003) EMC: EN61800-3 (2004) and conforms to the relevant safety provisions of the Low Voltage Directive (2006/95/EC) and EMC Directive 2004/108/EC.
RECEIPT OF DELIVERY 3. 13(110) RECEIPT OF DELIVERY NX frequency converters have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code below, Figure 3-1.
3 14(110) 3.2 RECEIPT OF DELIVERY Storage If the frequency converter is to be kept in store before use make sure that the ambient conditions are acceptable: Storing temperature Relative humidity –40…+70°C <95%, no condensation If the converter is to be stored during longer periods power should be connected to the converter once a year and kept on for at least 2 hours. If the storage time exceeds 12 months the electrolytic DC capacitors need to be charged with caution.
RECEIPT OF DELIVERY 3.4 15(110) Warranty Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsibility for damages caused during or resulting from transport, receipt of the delivery, installation, commissioning or use.
4 16(110) TECHNICAL DATA 4. TECHNICAL DATA 4.1 Introduction Figure 4-1 presents the block diagram of the NX frequency converter. The frequency converter mechanically consists of two units, the Power Unit and the Control Unit. Pictures of the mechanical assemblage on pages 54 to 62. The three-phase AC-choke (1) at the mains end together with the DC-link capacitor (2) form an LC-filter, which, again, together with the diode bridge produce the DC-voltage supply to the IGBT Inverter Bridge (3) block.
TECHNICAL DATA 17(110) The control keypad constitutes a link between the user and the frequency converter. The control keypad is used for parameter setting, reading status data and giving control commands. It is detachable and can be operated externally and connected via a cable to the frequency converter. Instead of the control keypad, also a PC can be used to control the frequency converter if connected through a similar cable.
4 18(110) 4.2 TECHNICAL DATA Power ratings 4.2.1 NX_5 – Mains voltage 380—500 V High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min Following continuous operation at rated output current, 150 % rated output current (IH) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.
TECHNICAL DATA 4.2.2 19(110) NX_6 – Mains voltage 525—690 V High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min Following continuous operation at rated output current, 150 % rated output current (IH) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.
4 20(110) 4.2.3 TECHNICAL DATA NX_2 – Mains voltage 208—240 V High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min Following continuous operation at rated output current, 150 % rated output current (IH) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.
TECHNICAL DATA 4.3 21(110) Brake resistor ratings Mains voltage 380-500 V, 50/60 Hz, 3~ Converter type NX 0003 5 NX 0004 5 NX 0005 5 NX 0007 5 NX 0009 5 NX 0012 5 NX 0016 5 NX 0022 5 NX 0031 5 NX 0038 5 NX 0045 5 NX 0061 5 NX 0072 5 NX 0087 5 Max. brake current [I] 12 12 12 12 12 12 12 12 17 35 35 51 111 111 Resistor nom [ohm] 63 63 63 63 63 63 63 63 42 21 21 14 6.5 6.5 NX 0105 5 NX 0140 5 NX 0168 5 NX 0205 5 NX 0261 5 NX 0300 5 Max. brake current [I] 111 222 222 222 222 222 Resistor nom. [ohm] 6.
4 22(110) TECHNICAL DATA Mains voltage 208-240 V, 50/60 Hz, 3~ Converter type NX 0004 2 NX 0007 2 NX 0008 2 NX 0011 2 NX 0012 2 NX 0017 2 NX 0025 2 NX 0031 2 NX 0048 2 Max. brake current [I] 15 15 15 15 15 15 15 23 46 Resistor nom [ohm] 30 30 30 30 30 30 30 20 10 Converter type NX 0061 2 NX 0075 2 NX 0088 2 NX 0114 2 NX 0140 2 NX 0170 2 NX 0205 2 NX 0261 2 NX 0300 2 Table 4-6. Brake resistor ratings, NX, supply voltage 208–240V Max. brake current [I] 46 148 148 148 296 296 296 296 296 Resistor nom.
TECHNICAL DATA 4.4 23(110) Technical data Mains connection Motor connection Control characteristics Input voltage Uin Input frequency Connection to mains Starting delay Output voltage Continuous output current Starting current Output frequency Frequency resolution Control method Switching frequency (see parameter 2.6.
4 24(110) TECHNICAL DATA EMC (at default settings) Safety Immunity Emissions Emissions Average noise level (cooling fan) in dB (A) Control connections (apply to boards OPTA1, OPT-A2 and OPT-A3) Analogue input voltage Analogue input current Digital inputs (6) Auxiliary voltage Output reference voltage Analogue output Digital outputs Relay outputs Protections Overvoltage trip limit Undervoltage trip limit Earth fault protection Mains supervision Motor phase supervision Overcurrent protection Unit ove
INSTALLATION 5. INSTALLATION 5.1 Mounting 25(110) The frequency converter can be mounted in either vertical or horizontal position on the wall or on the back plane of a cubicle. However, if the drive is mounted in a horizontal position, it is not protected against vertically falling drops of water. Enough space shall be reserved around the frequency converter in order to ensure a sufficient cooling, see Figure 5-11, Table 5-10 and Table 5-11. Also see to that the mounting plane is relatively even.
5 26(110) INSTALLATION Ø W2 D1 H1 H2 H3 W1 E1Ø E2Ø* Ø fr5ip21.fh8 Figure 5-1.
INSTALLATION 27(110) W2 H4 D1 H5 D2 H1 H2 H3 W1 Ø fr5ip21kaulus.fh8 Figure 5-2. NX dimensions, FR4 to FR6; Flange mounting Type 0004—0012 NXS2 0003—0012 NX_5 0017—0031 NXS2 0016—0031 NX_5 0048—0061 NXS2 0038—0061 NX_5 0004—0034 NX_6 W1 W2 H1 Dimensions [mm] H2 H3 H4 H5 128 113 337 325 327 30 22 190 77 7 144 120 434 420 419 36 18 214 100 7 195 170 560 549 558 30 20 237 106 6.5 D1 D2 ∅ Table 5-2.
5 28(110) INSTALLATION H2 Ø W3 W2 W1 H4 H1 H3 fr6aukko.fh8 Figure 5-3. The opening needed for the flange mounting, FR4 to FR6 Type 0004—0012 NXS2 0003—0012 NX_5 0017—0031 NXS2 0016—0031 NX_5 0048—0061 NXS2 0038—0061 NX_5 0004—0034 NX_6 Dimensions [mm] W3 H1 H2 H3 H4 ∅ – 5 6.5 420 – 5 6.5 549 7 5 6.5 W1 W2 123 113 – 315 325 135 120 – 410 185 170 157 539 Table 5-3.
INSTALLATION 29(110) H7 W4 W2 H6 D1 H4 D2 H3 H1 H2 H4 W3 W1 H5 fr7kaulusip21.fh8 Figure 5-4. NX dimensions, FR7 and FR8, flange mounting Type 0075—0114 NXS2 0072—0105 NX_5 0041—0052 NX_6 0140—0205 NXS2 0140—0205 NX_5 0062—0100 NX_6 W1 W2 W3 W4 H1 Dimensions [mm] H2 H3 H4 237 175 270 253 652 632 630 188.5 289 - 355 330 832* – 759 258 H5 H6 H7 D2 ∅ 188.5 23 20 257 117 5.5 265 57 344 110 9 43 Table 5-4.
5 30(110) INSTALLATION H2 H5 H2 H4 H3 H6 H1 W1 W2 W3 Ø fr7aukko.fh8 Figure 5-5. The opening needed for the flange mounting, FR7 Type 0075—0114 NXS2 0072—0105 NX_5 0041—0052 NX_6 W1 W2 W3 H1 233 175 253 619 Dimensions [mm] H2 H3 188.5 188.5 H4 H5 H6 ∅ 34.5 32 7 5.5 Table 5-5. Dimensions for the opening for flange mounting, FR7 Bottom edge of the opening H4 H3 H1 H1 H2 Figure 5-6.
INSTALLATION 31(110) Ø D1 D2 H4 H6 H3 W4 W1 W3 H2 fr9ip21.fh8 H5 H1 D3 Figure 5-7. The dimensions NX, FR9 Type W1 W2 W3 W4 0261—0300 NXS2 0261—0300 NX_5 480 400 165 9 0125—0208 NX_6 W5 Dimensions [mm] H1 H2 H3 H4 54 1150* 1120 H5 721 205 16 Table 5-7. The dimensions NX, FR9 *Brake resistor terminal box (H6) not included, see page 60.
5 32(110) INSTALLATION Ø D1 D2 D3 H4 H2 H4 H7 W5 W1 H3 H5 H3 H3 H5 W4 Opening W3 W2 W4 fr9collar.fh8 H1 H6 Figure 5-8. NX dimensions. FR9 flange mounting Type 0261-0300 NXS2 0261-0300 NX_5 0125-0208 NX_6 W1 W2 W3 W4 W5 H1 530 510 485 200 5.5 1312 Table 5-8. NX dimensions.
INSTALLATION 33(110) W4 Type plate W2 W3 W1 Warning plate Figure 5-9. NX dimensions, FR10 and FR11 (floorstanding units) Type Dimensions [mm] W1 W2 W3 W4 H1 H2 H3 0385…0520 NX_5 595 291 131 15 2018 1900 0261…0416 NX_6 0590…0730 NX_5 794 390 230 15 2018 1900 0460…0590 NX_6 H4 H5 D1 1435 512 40 602 1435 512 40 602 Table 5-9.
5 34(110) INSTALLATION Ty pe plate Y 15 Detail Y, 1:5 X Warning plate Detail X, 1:5 1197 Figure 5-10.
INSTALLATION 5.2 35(110) Cooling Enough free space shall be left around the frequency converter to ensure sufficient air circulation, cooling as well as maintenance. You will find the required dimensions for free space in the tables below. If several units are mounted above each other the required free space equals C + D (see figure below). Moreover, the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit.
5 36(110) INSTALLATION Type 0004—0012 NXS2 0003—0012 NX_5 0017—0031 NXS2 0016—0031 NX_5 0004—0013 NX_6 0048—0061 NXS2 0038—0061 NX_5 0018—0034 NX_6 0075—0114 NXS2 0072—0105 NX_5 0041—0052 NX_6 0140—0205 NXS2 0140—0205 NX_5 0062—0100 NX_6 0261—0300 NXS2 0261—0300 NX_5 0125—0208 NX_6 Table 5-11.
INSTALLATION 5.2.2 37(110) Standalone units (FR10 to FR12) B A A D C Type A 0385—0520 NX_5 0261—0416 NX_6 0590—0730 NX_5 0460—0590 NX_6 0820—1030 NX_5 0650—0820 NX_6 A B C D = = = = Dimensions [mm] B C 50 100 50 100 50 100 70 D 150 Minimum distance to the side walls or adjacent components.
5 38(110) INSTALLATION Mounting space dimensions [mm] A B C B 800 200 20 Table 5-12. Mounting space dimensions Type A C 0385—0520 5 0261—0416 6 0650—0730 5 0460—0590 6 0820—1030 5 0650—0820 6 Cooling air required [m3/h) 2600 3900 5200 Table 5-13. Required cooling air Figure 5-12.
INSTALLATION 5.3 39(110) Power losses 5.3.1 Power losses as function of switching frequency If the operator wants to raise the switching frequency of the drive for some reason (typically e.g. in order to reduce the motor noise), this inevitably affects the power losses and cooling requirements according to the graphs below.
5 40(110) INSTALLATION 1400,00 1200,00 1000,00 P [W] 800,00 600,00 400,00 200,00 0,00 0,00 2,00 4,00 6,00 8,00 10,00 12,00 14,00 16,00 Switching frequency [kHz] 0038NX5 400V 0061NX5 400V 0038NX5 500V 0061NX5 500V 0045NX5 400V 0045NX5 500V Figure 5-15.
INSTALLATION 41(110) 4000,00 3500,00 3000,00 P[W] 2500,00 2000,00 1500,00 1000,00 500,00 0,00 0,00 2,00 4,00 6,00 8,00 10,00 12,00 Switching frequency [kHz] 0140NX5 400V 0140NX5 500V 0168NX5 400V 0168NX5 500V 0205NX5 400V 0205NX5 500V Figure 5-17.
5 42(110) INSTALLATION 8000,00 7000,00 6000,00 P[W] 5000,00 0385NX 400V 4000,00 0385NX 500V 0460NX 400V 0460NX 500V 0520NX 400V 3000,00 0520NX 500V 2000,00 1000,00 0,00 1 2 3 4 Switching frequency [kHz] Figure 5-19.
CABLING AND CONNECTIONS 6. CABLING AND CONNECTIONS 6.1 Power unit 6.1.1 Power connections 6.1.1.1 Mains and motor cables 43(110) The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals marked with U, V and W. A cable entry gland should be used when installing the motor cable at both ends in order to reach the EMC levels. See Table 6-1 for the cable recommmendations for different EMC levels. Use cables with heat resistance of at least +70°C.
6 44(110) 6.1.1.2 CABLING AND CONNECTIONS DC supply and brake resistor cables Frequency converters are equipped with terminals for the DC supply and an optional external brake resistor. These terminals are marked with B–, B+/R+ and R–. The DC bus connection is made to terminals B– and B+ and the brake resistor connection to R+ and R–. Note that the DC connection is optional for drives greater than FR8. 6.1.1.3 Control cable For information on control cables see Chapter 6.2.1.1 and Table 6-1. 6.1.1.
CABLING AND CONNECTIONS 6.1.1.5 45(110) Cable and fuse sizes, NX_6, FR6 to FR9 The table below shows typical cable sizes and types that can be used with the converter. The final selection should be made according to local regulations, cable installation conditions and cable specification. IL [A] Fuse [A] Mains and motor cable Cu [mm2] NX0004 6—0007 6 3—7 10 3*2.5+2.5 NX0010 6—0013 6 10-13 16 3*2.5+2.
6 46(110) 6.1.1.6 CABLING AND CONNECTIONS Cable and fuse sizes, NX_5, FR10 to FR12 The table below shows typical cable sizes and types that can be used with the converter. The final selection should be made according to local regulations, cable installation conditions and cable specification.
CABLING AND CONNECTIONS 6.1.2 47(110) Understanding the power unit topology Figure 6-1 shows the principles for mains and motor connections of the basic 6-pulse drive in frame sizes FR4 to FR12. Note! Min cable length 5m M FR4-9/FR10 Single input Single output M FR11* Double input* Single output M FR12 Double input Double output nk6_1 8.fh8 *The FR11 types 0460 6 and 0502 6 have single input terminals Figure 6-1.
6 48(110) 6.1.3 CABLING AND CONNECTIONS Changing the EMC protection class The EMC protection level of NX frequency converters can be changed from class H to class T (and from class L to T in NX_6 FR6) with a simple procedure presented in the following figures. Note! After having performed the change check EMC Level modified on the sticker included in the NX delivery (see below) and note the date. Unless already done, attach the sticker close to the nameplate of the frequency converter.
CABLING AND CONNECTIONS 49(110) FR7: Remove this screw and replace with plastic screw M4 Remove this screw Figure 6-4. Changing of EMC protection class, FR7 NOTE! Only an authorized service person may change the EMC protection class of NX, FR8 and FR9.
6 50(110) 6.1.4 CABLING AND CONNECTIONS Mounting of cable accessories Enclosed to your NX frequency converter you have received a plastic bag containing components that are needed for the installation of the mains and motor cables in the frequency converter. 2 3 4 1 6 5 8 8 7 Figure 6-5.
CABLING AND CONNECTIONS 51(110) 6
6 52(110) 6.1.5 CABLING AND CONNECTIONS Installation instructions 1 2 Before starting the installation, check that none of the components of the frequency converter is live. Place the motor cables sufficiently far from other cables: Avoid placing the motor cables in long parallel lines with other cables If the motor cables runs in parallel with other cables, note the minimum distances between the motor cables and other cables given in table below.
CABLING AND CONNECTIONS 6.1.5.1 53(110) Stripping lengths of motor and mains cables Earth conductor Earth conductor A1 C1 A2 C2 B1 D1 B2 D2 MAIN S MOTOR nk6141.fh8 Figure 6-6. Stripping of cables Frame FR4 FR5 FR6 FR7 FR8 0140 0168—0205 FR9 A1 15 20 20 25 B1 35 40 90 120 C1 10 10 15 25 D1 20 30 60 120 A2 7 20 20 25 B2 50 60 90 120 C2 7 10 15 25 D2 35 40 60 120 23 28 28 240 240 295 23 28 28 240 240 295 23 28 28 240 240 295 23 28 28 240 240 295 Table 6-6.
6 54(110) 6.1.5.2 CABLING AND CONNECTIONS NX frames and installation of cables Note: In case you want to connect an external brake resistor, see separate Brake Resistor Manual. See also Chapter 'Internal brake resistor connection (P6.7.1)' on page 98 in this manual. Figure 6-7. NX, FR4 DC-terminalsBrake resistor terminals Earth terminals Mains cable Motor cable Figure 6-8. Cable installation in NX, FR4 NOTE: Two protective conductors are required for FR4 according to standard EN61800-5-1.
CABLING AND CONNECTIONS Figure 6-9.
6 56(110) CABLING AND CONNECTIONS Figure 6-10. NX, FR5. DC terminals Brake resistor terminals Earth terminals Mains cable Figure 6-11. Cable installation in NX, FR5 NOTE: See chapter 1.3.
CABLING AND CONNECTIONS Figure 6-12. NX, FR6. Brake resistor DC terminals terminals Brake resistor terminals Earth terminals Earth terminals Mains cable Mains cable Figure 6-13. Cable installation in NX, FR6 NOTE: See chapter 1.3.
6 58(110) CABLING AND CONNECTIONS Figure 6-14. NX, FR7. Brake resistor DC terminals terminals Earth terminals Mains cable Motor cable Figure 6-15. Cable installation in NX, FR7 NOTE: See chapter 1.3.
CABLING AND CONNECTIONS Figure 6-16.
6 60(110) CABLING AND CONNECTIONS Motor cable Mains cable Earth terminal Figure 6-17. Cable installation in NX, FR8 DC terminals Brake resistor terminals Figure 6-18.
CABLING AND CONNECTIONS 61(110) Figure 6-19. NX, FR9 Motor cables Mains cable Earth terminals Figure 6-20.
6 62(110) CABLING AND CONNECTIONS B– B+/R+ R– Figure 6-21.
CABLING AND CONNECTIONS 63(110) Figure 6-22. Example of NXP standalone drives (FR11) Note: More information on cabling for frames FR10 and greater you will find in the NXP/C User’s Manual.
6 64(110) 6.1.6 CABLING AND CONNECTIONS Cable selection and unit installation in accordance with the UL standards To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with a minimum heat-resistance of +60/75°C. Use Class 1 wire only. The units are suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 600V maximum. The tightening torques of the terminals are given in Table 6-7.
CABLING AND CONNECTIONS 6.2 65(110) Control unit The control unit of the frequency converter consists roughly of the control board and additional boards (see Figure 6-23 and Figure 6-24) connected to the five slot connectors (A to E) of the control board. The control board is connected to the power unit through a D-connector (1) or fibre optic cables (FR9). A Figure 6-23. NX control board B C D E Figure 6-24.
6 66(110) 6.2.1 CABLING AND CONNECTIONS Control connections The basic control connections for boards A1 and A2/A3 are shown in Chapter 6.2.2. The signal descriptions are presented in the All in One Application Manual. Basic I/O board OPT-A1 OPT-A2 OPT-A3 Board OPT-A1 Boards OPT-A2 and in slot A OPT-A3 in slot B Figure 6-25.
CABLING AND CONNECTIONS 6.2.1.1 67(110) Control cables The control cables shall be at least 0.5 mm2 screened multicore cables, see Table 6-1. The maximum terminal wire size is 2.5 mm2 for the relay terminals and 1.5 mm2 for other terminals. Find the tightening torques of the option board terminals in Table below. Terminal screw Relay and thermistor terminals (screw M3) Other terminals (screw M2.6) Tightening torque Nm lb-in. 0.5 4.5 0.2 1.8 Table 6-8. Tightening torques of terminals 6.2.1.
6 68(110) 6.2.2 CABLING AND CONNECTIONS Control terminal signals OPT-A1 1 2 Terminal +10 Vref AI1+ Signal Reference voltage Analogue input, voltage or current Technical information Maximum current 10 mA Selection V or mA with jumper block X1 (see page 71): Default: 0– +10V (Ri = 200 kΩ) (-10V…..
CABLING AND CONNECTIONS 69(110) OPT-A2 21 22 23 Terminal RO1/1 RO1/2 RO1/3 24 25 26 RO2/1 RO2/2 RO2/3 Signal Relay output 1 Relay output 2 Technical information Switching capacity 24VDC/8A 250VAC/8A 125VDC/0.4A Min.switching load 5V/10mA Switching capacity 24VDC/8A 250VAC/8A 125VDC/0.4A Min.switching load 5V/10mA Table 6-10.
6 70(110) 6.2.2.2 CABLING AND CONNECTIONS Jumper selections on the OPT-A1 basic board The user is able to customise the functions of the frequency converter to better suit his needs by selecting certain positions for the jumpers on the OPT-A1 board. The positions of the jumpers determine the signal type of analogue and digital inputs. On the A1 basic board, there are four jumper blocks X1, X2, X3 and X6 each containing eight pins and two jumpers.
CABLING AND CONNECTIONS Jum per block X 1 : AI1 m ode A B C D B C D B C D A B C D Jum per block X 6 : AO 1 m ode A B C D AO1 mode: 0...20mA; Current output A B C D D B C D B C D AI2 mode: Voltage input; 0...10V (differential) A AI1 mode: Voltage input; -10...10V C AI2 mode: Voltage input; 0...10V A AI1 mode: Voltage input; 0...10V (differential) B AI2 mode: 0...20mA; Current input A AI1 mode: Voltage input; 0...10V A Jum per block X 2 : AI2 m ode A AI1 mode: 0...
7 72(110) 7. CONTROL KEYPAD CONTROL KEYPAD The control keypad is the link between the frequency converter and the user. The NX control keypad features an alphanumeric display with seven indicators for the Run status (RUN, , READY, STOP, ALARM, FAULT) and three indicators for the control place (I/O term/ Keypad/BusComm). There are also three Status Indicator LEDs (green - green - red), see Status LEDs (green – green – red) below. The control information, i.e.
CONTROL KEYPAD 7.1.2 73(110) Control place indications (See control keypad) The symbols I/O term, Keypad and Bus/Comm (see Figure 7-1) indicate the choice of control place made in the Keypad control menu (M3) (see chapter 7.3.3). a I/O term = I/O terminals are the selected control place; i.e. START/STOP commands or reference values etc. are given through the I/O terminals. b Keypad = Control keypad is the selected control place; i.e. the motor can be started or stopped, or its reference values etc.
7 74(110) 7.2 CONTROL KEYPAD Keypad push-buttons The alphanumeric control keypad features 9 push-buttons that are used for the control of the frequency converter (and motor), parameter setting and value monitoring. Figure 7-2. Keypad push-buttons 7.2.1 Button descriptions reset = This button is used to reset active faults (see Chapter 7.3.4). select = This button is used to switch between two latest displays.
CONTROL KEYPAD 7.3 75(110) Navigation on the control keypad The data on the control keypad are arranged in menus and submenus. The menus are used for example for the display and editing of measurement and control signals, parameter settings (chapter 7.3.2), reference values and fault displays (chapter 7.3.4). Through the menus, you can also adjust the contrast of the display (page 97).
7 76(110) CONTROL KEYPAD READY R EADY I/Oterm R EADY I/Ote rm Expander boards A:NXOPTA1 G1ÎG5 STOP I/Oterm Parameters G1ÎG1 R EADY STOP I/Ote rm R EADY I/Ote rm System Menu S1ÎS9 English Browse READY I/Ote rm READY I/Ote rm Fault history H1ÎH3 STOP I/Oterm 11 Output phase T1ÎT7 FAULT STOP I/Ote rm Active faults F0 or: R EADY ST OP Control Place I/O Terminal R EADY RU N I/Ote rm R EADY Monitor 17 enter Browse RUN Change value READY L oc al Basic parameters P
CONTROL KEYPAD 7.3.1 77(110) Monitoring menu (M1) You can enter the Monitoring menu from the Main menu by pushing the Menu button right when the location indication M1 is visible on the first line of the display. How to browse through the monitored values is presented in Figure 7-4. The monitored signals carry the indication V#.# and they are listed in Table 7-1. The values are updated once every 0.3 seconds. This menu is meant only for signal checking. The values cannot be altered here.
7 78(110) 7.3.2 CONTROL KEYPAD Parameter menu (M2) Parameters are the way of conveying the commands of the user to the frequency converter. The parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication M2 is visible on the first line of the display. The value editing procedure is presented in Figure 7-5. Push the Menu button right once to move into the Parameter Group Menu (G#).
CONTROL KEYPAD 7.3.3 79(110) Keypad control menu (M3) In the Keypad Controls Menu, you can choose the control place, edit the frequency reference and change the direction of the motor. Enter the submenu level with the Menu button right. Code Parameter Min Max P3.1 Control place 1 3 R3.2 Keypad reference Par. 2.1.1 Par. 2.1.2 P3.3 Direction (on keypad) 0 R3.
7 80(110) 7.3.3.2 CONTROL KEYPAD Keypad reference The keypad reference submenu (P3.2) displays and allows the operator to edit the frequency reference. The changes will take place immediately. This reference value will not, however, influence the rotation speed of the motor unless the keypad has been selected as source of reference. NOTE: The maximum difference in RUN mode between the output frequency and the keypad reference is 6 Hz.
CONTROL KEYPAD 7.3.4 81(110) Active faults menu (M4) The Active faults menu can be entered from the Main menu by pushing the Menu button right when the location indication M4 is visible on the first line of the keypad display. When a fault brings the frequency converter to a stop, the location indication F1, the fault code, a short description of the fault and the fault type symbol (see Chapter 7.3.4.1) will appear on the display. In addition, the indication FAULT or ALARM (see Figure 7-1 or Chapter 7.1.
7 82(110) 7.3.4.1 CONTROL KEYPAD Fault types In the NX frequency converter, there are four different types of faults. These types differ from each other on the basis of the subsequent behaviour of the drive. See Table 7-3. I/Oterm Operation hours 34:21:05 STOP FAULT I/Oterm Fault type symbol 11 Output phase F T1 ÎT13 STOP FAULT I/Oterm Operations days 17 Figure 7-7. Fault display Fault type symbol A (Alarm) F (Fault) AR (Fault Autoreset) FT (Fault Trip) Table 7-3.
CONTROL KEYPAD 7.3.4.2 83(110) Fault codes The fault codes, their causes and correcting actions are presented in the table below. The shadowed faults are A faults only. The items written in white on black background present faults for which you can program different responses in the application. See parameter group Protections. Note: When contacting distributor or factory because of a fault condition, always write down all texts and codes on the keypad display.
7 84(110) Fault code 9 CONTROL KEYPAD Fault Undervoltage 10 Input line supervision 11 Output phase supervision Brake chopper supervision 12 13 14 Frequency converter undertemperature Frequency converter overtemperature Possible cause DC-link voltage is under the voltage limits defined. − most probable cause: too low a supply voltage − frequency converter internal fault − defect input fuse − external charge switch not closed Input line phase is missing. Subcode in T.
CONTROL KEYPAD Fault code 31 Fault IGBT temperature (hardware) 32 Fan cooling 34 35 CAN bus communication Application 36 Control unit 37 Device changed (same type) Device added (same type) Device removed Device unknown 38 39 40 41 IGBT temperature 42 Brake resistor overtemperature Encoder fault 43 44 Device changed (different type) 45 Device added (different type) Division by zero in application 49 50 51 52 Possible cause IGBT Inverter Bridge overtemperature protection has detected t
7 86(110) Fault code 53 CONTROL KEYPAD Fault Possible cause Fieldbus fault The data connection between the fieldbus Master and the fieldbus board is broken 54 Slot fault Defective option board or slot 56 PT100 board temp. fault 57 Identification Temperature limit values set for the PT100 board parameters have been exceeded Identification run has failed. 58 Brake 59 60 Follower communication Cooling 61 Speed error 62 63 Run disable Emergency stop Input switch open 64 Table 7-4.
CONTROL KEYPAD 7.3.4.3 87(110) Fault time data record When a fault occurs the information described above in 7.3.4 is displayed. By pushing the Menu button right here you will enter the Fault time data record menu indicated by T.1ÆT.13. In this menu, some selected important data valid at the time of the fault are recorded. This feature is intended to help the user or the service person to determine the cause of fault. The data available are: Counted operation days T.
7 88(110) 7.3.5 CONTROL KEYPAD Fault history menu (M5) The Fault history menu can be entered from the Main menu by pushing the Menu button right when the location indication M5 is visible on the first line of the keypad display. Find the fault codes in Table 7-4. All faults are stored in the Fault history menu in which you can browse through them using the Browser buttons. Additionally, the Fault time data record pages (see Chapter 7.3.4.3) are accessible at each fault.
CONTROL KEYPAD 7.3.6 89(110) System menu (M6) The System menu can be entered from the main menu by pushing the Menu button right when the location indication M6 is visible on the display. The controls associated with the general use of the frequency converter, such as application selection, customised parameter sets or information about the hardware and software are located under the System menu. The number of submenus and subpages is shown with the symbol S (or P) on the value line.
7 90(110) P6.7.2 P6.7.3 P6.7.4 S6.8 S6.8.1 C6.8.1.1 C6.8.1.2 C6.8.1.3 S6.8.2 T6.8.2.1 CONTROL KEYPAD Fan control HMI acknowledg. timeout HMI number of retries System information Total counters MWh counter Power On day counter Power On hours counter I6.8.5.2 I6.8.5.3 I6.8.5.4 S6.8.
CONTROL KEYPAD 7.3.6.1 91(110) Language selection The HMI control keypad offers the user the possibility to control the frequency converter through the keypad in the language of your choice. Locate the language selection page under the System menu. Its location indication is S6.1. Press the Menu button right once to enter the edit mode. As the name of the language starts to blink you are able to choose another language for the keypad texts.
7 92(110) CONTROL KEYPAD STOP STOP READY READY I/Oterm I/Oterm Application System Menu S1ÎS11 STOP Standard STOP READY READY I/Oterm I/Oterm Application enter Application Multi-step Standard Figure 7-10. Change of application 7.3.6.3 Copy parameters The parameter copy function is used when the operator wants to copy one or all parameter groups from one drive to another or to store parameter sets in the internal memory of the converter.
CONTROL KEYPAD 93(110) Upload parameters to keypad (To keypad, S6.3.2) This function uploads all existing parameter groups to the keypad provided that the drive is stopped. Enter the To keypad page (S6.3.2) from the Parameter copy menu. Push the Menu button right to enter the edit mode. Use the Browser buttons to select the option All parameters and press the Enter button. Wait until 'OK' appears on the display.
7 94(110) 7.3.6.4 CONTROL KEYPAD Parameter comparison In the Parameter comparison submenu (S6.4), you can compare the actual parameter values to the values of your customised parameter sets and those loaded to the control keypad. The comparison is performed by pushing the Menu button right when in the Compare parameters submenu. The actual parameter values are first compared to those of the customised parameter Set1. If no differences are detected a '0' is displayed on the lowermost line.
CONTROL KEYPAD 7.3.6.5 95(110) Security NOTE: The Security submenu is protected with a password. Store the password in a safe place! Password (S6.5.1) The application selection can be protected against unauthorised changes with the Password function (S6.5.1). By default, the password function is not in use. If you want to activate the function, enter the edit mode by pushing the Menu button right. A blinking zero appears in the display and now you can set a password with the Browser buttons.
7 96(110) CONTROL KEYPAD Start-up Wizard (P6.5.3) The Start-up Wizard is a feature on the control keypad to facilitate the commissioning of the frequency converter. If selected active (default), the Start-up Wizard prompts the operator for the language and application of his/her choice plus for the values for a set of parameters common to all applications as well as for a set of application-dependent parameters.
CONTROL KEYPAD 97(110) Default page (P6.6.1) Here you can set the location (page) to which the display automatically moves as the Timeout time (see below) has expired or as the power is switched on to the keypad. If the Default Page value is 0 the function is not activated, i.e. the last displayed page remains on the keypad display. Press the Menu button right once to enter the edit mode. Change the number of the Main menu with the Browser buttons.
7 98(110) 7.3.6.7 CONTROL KEYPAD Hardware settings NOTE: The Hardware settings submenu is protected with a password (see chapter Password (S6.5.1)). Store the password in a safe place! In the Hardware settings submenu (S6.7) under the System menu you can further control some functions of the hardware in your frequency converter. The functions available in this menu are Internal brake resistor connection, Fan control, HMI acknowledge timeout and HMI retry. Internal brake resistor connection (P6.7.
CONTROL KEYPAD 99(110) Enter the edit mode by pushing the Menu button right. The present mode shown starts to blink. Use the Browser buttons to change the fan mode. Accept the change with the Enter button or return to the previous level with the Menu button left. READY READY I/Oterm READY I/Oterm I/Oterm Fan control Fan control Continuous Continuous enter Fan control Temperature Figure 7-22. Fan control function HMI acknowledge timeout (P6.7.
7 100(110) CONTROL KEYPAD Number of retries to receive HMI acknowledgement (P6.7.4) With this parameter you can set the number of times the drive will try receive acknowledgement if this does not succeed within the acknowledgement time (P6.7.3) or if the received acknowledgement is faulty. Enter the edit mode by pushing the Menu button right. The present value shown starts to blink. Use the Browser buttons to change the amount of retries.
CONTROL KEYPAD STOP STOP READY Trip counters T1ÎT5 STOP Reset READY Clr Optime cntr Not reset Not reset STOP enter READY Clr Optime cntr READY Clr Optime cntr 101(110) READY STOP READY Clr Optime cntr Clr Optime cntr Reset Not reset Figure 7-24. Counter reset Software (S6.8.3) The Software information page includes information on the following frequency converter software related topics: Page 6.8.3.1 6.8.3.2 6.8.3.3 6.8.3.
7 102(110) CONTROL KEYPAD In the Applications information page, push the Menu button right to enter the Application pages of which there are as many as there are applications loaded into the frequency converter. Locate the application you want information about with the Browser buttons and then enter the Information pages with the Menu button right. Use again the Browser buttons to see the different pages. Hardware (S6.8.
CONTROL KEYPAD 7.3.7 103(110) Expander board menu (M7) The Expander board menu makes it possible for the user 1) to see what expander boards are connected to the control board and 2) to reach and edit the parameters associated with the expander board. Enter the following menu level (G#) with the Menu button right. At this level, you can browse through slots (see page 65) A to E with the Browser buttons to see what expander boards are connected.
8 104(110) COMMISSIONING 8. COMMISSIONING 8.1 Safety Before commissioning, note the following directions and warnings: 1 2 3 4 5 WARNING 6 7 HOT SURFACE 8.2 8 Internal components and circuit boards of the frequency converter (except for the galvanically isolated I/O terminals) are live when NX is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
COMMISSIONING 7 105(110) Set the parameters of group 1 (See Application Manual) according to the requirements of your application. At least the following parameters should be set: - motor nominal voltage motor nominal frequency motor nominal speed motor nominal current You will find the values needed for the parameters on the motor rating plate. 8 Perform run test without motor Perform either Test A or Test B: A Controls from the I/O terminals: a) Turn the Start/Stop switch to ON position.
8 106(110) 11 COMMISSIONING Connect the motor to the process (if the startup test was run without the motor being connected) a) Before running the tests, make sure that this can be done safely. b) Inform your co-workers of the tests.
FAULT TRACING 9. 107(110) FAULT TRACING When a fault is detected by the frequency converter control electronics, the drive is stopped and the symbol F together with the ordinal number of the fault, the fault code and a short fault description appear on the display. The fault can be reset with the Reset button on the control keypad or via the I/O terminal. The faults are stored in the Fault history menu (M5) which can be browsed. The different fault codes you will find in the table below.
9 108(110) Fault code 9 FAULT TRACING Fault Undervoltage 10 Input line supervision 11 Output phase supervision Brake chopper supervision 12 13 14 Frequency converter undertemperature Frequency converter overtemperature Possible cause DC-link voltage is under the voltage limits defined. − most probable cause: too low a supply voltage − frequency converter internal fault − defect input fuse − external charge switch not closed Input line phase is missing. Subcode in T.
FAULT TRACING Fault code 31 Fault IGBT temperature (hardware) 32 Fan cooling 34 35 CAN bus communication Application 36 Control unit 37 Device changed (same type) Device added (same type) Device removed Device unknown 38 39 40 41 IGBT temperature 42 Brake resistor overtemperature Encoder fault 43 44 Device changed (different type) 45 Device added (different type) Division by zero in application 49 50 51 52 Possible cause IGBT Inverter Bridge overtemperature protection has detected to
9 110(110) Fault code 53 FAULT TRACING Fault Possible cause Fieldbus fault The data connection between the fieldbus Master and the fieldbus board is broken 54 Slot fault Defective option board or slot 56 PT100 board temp. fault 57 Identification Temperature limit values set for the PT100 board parameters have been exceeded Identification run has failed. 58 Brake 59 60 Follower communication Cooling 61 Speed error 62 63 Run disable Emergency stop Input switch open 64 Table 9-1.
NX QUICK HELP Start-up wizard The Start Up Wizard is activated when the power to the drive is turned on for the first time, or if the Start Up Wizard is activated from the System menu (P6.5.3) AND the power is turned OFF and back ON. The Start-up Wizard is a feature on the control keypad to facilitate the commissioning of the frequency converter.
Monitoring values Fault code 1 2 3 5 6 7 8 9 10 11 12 13 14 15 16 17 18 22 24 25 26 29 30 31 32 34 35 36 37 38 39 40 41 42 43 44 45 49 50 51 52 53 54 56 57 58 59 Fault Overcurrent Overvoltage Earth fault Charging switch Emergency stop Saturation trip System fault Undervoltage Input line supervision Output phase supervision Brake chopper supervision Frequency converter undertemperature Frequency converter overtemperature Motor stalled Motor overtemperature Motor underload Unbalance EEPROM checksum fault Cou
Actual value special display The Actual value special display parameters are used to convert and display the actual value signal in a form more informative to the user.
Selection of language 1. 2. 3. 4. Find the System Menu (M6) Enter the Language selection page (S6.1). Push the Menu button right to make the name of language blink. Browse through the languages with the Browser buttons and select another language with the Enter button. For closer information on language selection, see Chapter 7.3.6. READY READY I/Ot erm I/Oterm Language System Menu S1ÎS11 English READY READY I/Oterm I/Ot erm Language enter English Langue Francais Selection of application: 1.
Control panel menus READY R EADY I/Oterm R EADY I/Ote rm Expander boards A:NXOPTA1 G1ÎG5 STOP I/Oterm Parameters G1ÎG1 R EADY STOP I/Ote rm R EADY I/Ote rm System Menu S1ÎS9 English Browse READY I/Ote rm READY I/Ote rm Fault history H1ÎH3 STOP I/Oterm 11 Output phase T1ÎT7 FAULT STOP I/Ote rm Active faults F0 or: R EADY ST OP Control Place I/O Terminal R EADY RU N I/Ote rm R EADY I/Ote rm Monitor V1ÎV15 17 enter Browse Change value READY L oc al Basic paramet
Keypad shortcuts 1. Quick activation of keypad contol If you have selected either the I/O terminal control (I/O term) or the fieldbus control (Bus/Comm) as the active control place but wish to take over the control from these to the keypad, this can be done in two different ways. A.