Service manual

SERVICING
85
Diagnostic/Status LED Codes
ComfortNet
Thermostat Only
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
Green Yellow Red Red Y1
Fa ult
Description
Message Code
Possible Causes
Corrective Actions No tes & Cauti ons
Compressor and outdoor fan are off.
Compressor protector trips four
consecutive times .
Average run time between trips is less
than 15 seconds.
Integrated control module
diagno stic/status LED’s display the
indicated code.
ComfortNetthermostat “Call for
Service” icon illuminated.
ComfortNet™ thermostat scrolls
“Check Air Conditioner” or “Check
Heat Pump” message.
OFF 4
Flashes
ON ON if call
present;
OFF if no
call
Locked Rotor LOCKED
ROTO R
04 Compressor bearings are
seized.
Failed compressor r un
capacitor.
Faulty run capacitor
wiring.
Low line voltage.
Check compressor
operation;
repair/ rep lac e as
needed.
Check run capacitor;
replace as needed.
Check wiring;
repair/ rep lac e as
needed.
Verify line voltage is
within range on rating
plate; contact local
utility is out of range.
Turn power OFF prior
to repair.
Must clear fault by
cycling 24VAC to
control.
Replace with correct
replacement part(s).
Compressor and outdoor fan are off for
greater than 4 hours.
Low pressure and high pressure
switches are closed.
Integrated control module
diagno stic/status LED’s display the
indicated code.
ComfortNetthermostat “Call for
Service” icon illuminated.
ComfortNet™ thermostat scrolls
“Check Air Conditioner” or “Check
Heat Pump” message.
OFF 5
Flashes
OFF ON if call
present;
OFF if no
call
Open Circuit OPEN
CIRCUIT
05 Power is disconnected.
Failed compressor
protector.
Co mpress or n ot properly
wired to control.
Check circuit breakers
and fuses.
Check wiring to unit;
repair/ rep lac e as
needed.
Check compressor;
repair/ rep lac e as
needed.
Check compressor
wiri ng ; repair/rep lace
as needed.
Turn power OFF prior
to repair.
Fault will clear after 1
normal cycle.
Fault may be cleared by
cycling 24VAC to
control.
Replace with correct
replacement part(s).
Compressor and outdoor fan are off.
Low pressure and high pressure
switches are closed.
Integrated control module
diagno stic/status LED’s display the
indicated code.
ComfortNetthermostat “Call for
Service” icon illuminated.
ComfortNet™ thermostat scrolls
“Check Air Conditioner” or “Check
Heat Pump” message.
OFF 6
Flashes
OFF ON if call
present;
OFF if no
call
Open Start
Circuit
OPEN STA RT 06 Comp ress or start wi nding
is open.
Failed compressor r un
capacitor.
Faulty run capacitor
wiring.
Co mpress or n ot properly
wired to control.
Faulty compressor wiring.
Check compressor;
repair/ rep lac e as
needed.
Check run capacitor;
replace as needed.
Check wiring;
repair/ rep lac e as
needed.
Turn power OFF prior
to repair.
Fault will clear after 1
normal cycle.
Fault may be cleared by
cycling 24VAC to
control.
Replace with correct
replacement part(s).
Compressor and outdoor fan are off.
Low pressure and high pressure
switches are closed.
Open start circuit has been detected 4
times with 5 minu te delay between each
detection.
Integrated control module
diagno stic/status LED’s display the
indicated code.
ComfortNetthermostat “Call for
Service” icon illuminated.
ComfortNet™ thermostat scrolls
“Check Air Conditioner” or “Check
Heat Pump” message.
OFF 6
Flashes
ON ON if call
present;
OFF if no
call
Open Start
Circuit Lockout
OPEN STA RT
LOCK
06 Comp ress or start winding
is open.
Failed compressor r un
capacitor.
Faulty run capacitor
wiring.
Co mpress or n ot properly
wired to control.
Faulty compressor wiring.
Check compressor;
repair/ rep lac e as
needed.
Check run capacitor;
replace as needed.
Check wiring;
repair/replace as
needed.
Turn power OFF prior
to repair.
Must clear fault by
cycling 24VAC to
control.
Replace with correct
replacement part(s).