Spec Sheet

3
Specifications and Accessories Catalog
AVH Model Specifications—Heat Pump/Electric Heat
M
1, 5, 6, 7
AVHH
**AXXX
AVHH
**AXXX
AVHH
**AXXX
AVHH
**AXXX
AVHH
**AXXX
AVHH
**AXXX
AVHH
**AXXX
AVHH
**AXXX
Voltage
4
230 / 208 265 230 / 208 265 230 / 208 265 230 / 208 265
Capacity (BTU/h)
9,400 /
9,000
9,400
11,400 /
11,000
11,400
18,600 /
18,000
18,600
22,500 /
22,500
22,500
Amps
3
4.0 / 4.5 3.5 4.5 / 5.0 4.0 7.3 / 7.8 7.3 10.5/10.5 10.5
Watts
3
864 / 818 864
1,050 /
1,000
1,050
1,691 /
1,636
1,691 2,045 2,045
EER
11.0 / 11.0 11.3 11.0 / 11.0 11.0 11.0 / 11.0 11.1 11.0 / 11.0 11.0
Heater Size Options (kW)
2.5 / 3.4
/ 5.0
2.5 / 3.4
/ 5.0
2.5 / 3.4
/ 5.0
2.5 / 3.4
/ 5.0
2.5 / 3.4
/ 5.0
2.5 / 3.4
/ 5.0
2.5 / 3.4 /
5.0 / 7.5 /
10.0
2.5 / 3.4 /
5.0 / 7.5 /
10.0
Indoor CFM at .10" ESP
LOW 430 430 430 430 630 630 660 660
HIGH 490 490 490 490 675 675 700 700
Indoor CFM at .15" ESP
LOW 410 410 410 410 595 595 615 615
HIGH 470 470 470 470 640 640 665 665
Indoor CFM at .20" ESP
LOW 360 360 360 360 550 550 575 575
HIGH 440 440 440 440 600 600 625 625
Indoor CFM at .25" ESP
LOW 310 310 310 310 505 505 525 525
HIGH 400 400 400 400 550 550 580 580
Indoor CFM at .30" ESP
LOW 260 260 260 260 420 455 455 485
HIGH 350 350 350 350 500 500 540 540
Maximum ESP
(Inch of Water Coloumn)
0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
Ventilated Air, CFM
(Fan Only)
2
60 60 60 60 60 60 60 60
Dimensions
(W x D x H) (Inches)
23 x 23
x 32
23 x 23
x 32
23 x 23
x 32
23 x 23
x 32
23 x 23
x 47
23 x 23
x 47
23 x 23
x 52
23 x 23
x 52
Shipping Dimensions
(W x D x H) (Inches)
26 x 25
x 35
26 x 25
x 35
26 x 25
x 35
26 x 25
x 35
26 x 25
x 52
26 x 25
x 52
26 x 25
x 57
26 x 25
x 57
Net Weight (lbs.)
142 144 147 149 190 192 225 227
Shipping Weight (lbs.)
164 166 169 171 216 218 251 253
Notes:
1. Tested in accordance with AHRI Standard 390-93 at 95°F DB/75°F WB OUTDOOR, 80°F DB/67°F WB INDOOR
2. Actual vent CFM performance will vary due ro application and installation conditions
3. Refer to electric heat performance data for total MCA and recommended overcurrent protection.
Amps and Watts notation refers to compressor only.
4. Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage
on 265-volt models is 239 volts; maximum is 292 volts.
5. Specify two-digit heater kW size to complete model number.
6. R-410A refrigerant used in all systems.
7. All specifications are subject to change without notice
X