Service Instructions Model and Manufacturing numbers listed on page 5 RCA, RCB, RCC, RCE, VCA & VCB Models Remote Condensing Units Blowers, Coils & Accessories This manual is to be used by qualified HVAC technicians only. Amana does not assume any responsibility for property damage or personal injury for improper service procedures done by an unqualified person. ® Heating ¡ Air Conditioning A higher standard of comfort RS6100002 Revision 3 August 1998 1 Rev.
INDEX PRODUCT IDENTIFICATION .................................................................................... 5 - 8 SPECIFICATIONS RCA Models ................................................................................................... 9 - 11 RCB Models ................................................................................................... 9 - 11 RCC Models ................................................................................................... 12 RCE Models ................
IMPORTANT INFORMATION Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual.
IMPORTANT INFORMATION WARNING SYSTEM CONTAMINANTS, IMPROPER SERVICE PROCEDURE AND/OR PHYSICAL ABUSE AFFECTING HERMETIC COMPRESSOR ELECTRICAL TERMINALS MAY CAUSE DANGEROUS SYSTEM VENTING. System contaminants, improper Service Procedure and/or physical abuse affecting hermetic compressor electrical terminals may cause dangerous system venting.
PRODUCT IDENTIFICATION RCA18A2A RCA24A2A RCA30A2A RCA36A2A RCA36A3A RCA36A4A RCA42A2A RCA48A2A RCA48A3A RCA48A4A RCA60A2A RCA60A3A RCA60A4A P1173301C P1173302C P1173303C P1173304C P1173305C P1173306C P1173307C P1173308C P1173309C P1173310C P1173311C P1173312C P1173313C RCB18A2A RCB18A2B RCB18A2B RCB18B2A RCB24A2A RCB24A2B RCB24A2B RCB24B2A RCB30A2A RCB30A2B RCB30A2C RCB30A2C RCB30B2A RCB36A2A RCB36A2B RCB36A2B RCB36A3A RCB36A3B RCB36A3B RCB36A4A RCB36A4B RCB36A4B RCB36B2A RCB42A2A RCB42A2B RCB42A2B RCB42B
PRODUCT IDENTIFICATION CCA36FKC CCA36FSC CCA36FUA CCA36TCA CCA36TCB CCA36TDB CCA42FCC CCA42FDC CCA42FSC CCA42FUA CCA42TCA CCA42TCB CCA42TDB CCA48FCC CCA48FDC CCA48FSC CCA48TCA CCA48TCB CCA54FCC CCA54FSC CCA57FCC CCA57FSC CCA60FCC CCA60FSC CCA60TCA CCA60TCB P1203917C P1204004C P1111001C P1178604C P1178704C P1178709C P1203905C P1203912C P1204005C P1111002C P1178605C P1178705C P1178710C P1203906C P1203913C P1204006C P1178606C P1178706C P1203907C P1204007C P1203908C P1204008C P1203909C P1204009C P1178607C P117
PRODUCT IDENTIFICATION R C C 24 A 2 A ProductType Design Series R: Remote A: B: C: D: System Type C: Cooling H: Heat Pump Voltage 2: 230v/60Hz/1ph 3: 230v/60Hz/3ph 4: 460v/60Hz/3ph Product Family A: B: C: D: E: First Series Second Series Third Series Fourth Series 10 SEER 10 SEER 12 SEER 13 SEER 14 SEER Marketing Designator A: First Series B: Second Series Nominal Capacity 18: 24: 30: 36: 42: 48: 60: B C A 18000 BTUH 24000 BTUH 30000 BTUH 36000 BTUH 42000 BTUH 48000 BTUH 60000 BTUH 24 T
PRODUCT IDENTIFICATION C C A 24 T U A ProductType Design Series C: Coil A: B: C: D: System Type A & B Design Series C: Cooling H: Heat Pump C & D Design Series C: Standard Efficiency H: High Efficiency System Type C: Cased D: Wide Body K: Extra Wide S: Uncased U: Uncased Configuration A: "A" Coil H: Horizontal Coil F: Horizontal "A" Coil Expansion Device Nominal Capacity 18: 24: 30: 36: 42: 48: 60: B B A 18000 BTUH 24000 BTUH 30000 BTUH 36000 BTUH 42000 BTUH 48000 BTUH 60000 BTUH 24 F: Flow
CONDENSING UNIT SPECIFICATIONS RCA/B18 A2A 18400 RCB18 A2B 18000 RCB18 B2A 18000 RCA/B24 A2A 23600 RCB24 A2B 24000 RCB24 B2A 24000 RCA/B30 A2A 28200 RCB30 A2B 30000 RCB30 A2C 30000 RCB30 B2A 30000 RCA/B36 A2A 35800 RCB36 A2B 36000 RCB36 B2A 36000 RCA/B36 A3A 35800 RCB36 A3B 36000 RCA/B36 A4A 35800 R.L. AMPS 12.3 13.7 16.1 15.3 15.3 10.0 9.5 5.1 L.R. AMPS 76.0 75.0 82.0 86.0 82.0 72.0 64.5 33.0 HORSEPOWER 1/12 1/6 1/6 1/12 1/4 1/6 1/12 1/6 R.L. AMPS 0.6 1.1 1.
CONDENSING UNIT SPECIFICATIONS MODEL COOLING CAPACITY, BTUH COMPRESSOR R.L. AMPS L.R. AMPS CONDENSER FAN MOTOR HORSEPOWER R.L. AMPS L.R. AMPS LIQUID LINE, INCHES O.D. SUCTION LINE, INCHES O.D. REFRIGERANT CHARGE POWER SUPPLY MIN.CIRCUIT AMPACITY MAX. OVERCURRENT DEVICE ELECT. CONDUIT SIZE POWER SUPPLY LOW VOLTAGE APPROX. SHIPPING WT MODEL COOLING CAPACITY, BTUH RCB36 A4B 36000 RCA/B42 A2A 41500 RCB42 A2B 42000 RCB42 B2A 42000 RCA/B48 A2A 49000 RCB48 A2B 47000 RCB48 B2A 48000 RCA/B48 A3A 49000 5.
CONDENSING UNIT SPECIFICATIONS RCB60 A4B 60000 RCC18 A2A 18600 RCC18 A2B 18000 RCC24 A2A 24000 RCC24 A2B 24000 RCC30 A2A 29800 RCC30 A2B 30000 8.6 55.0 6.2 48.0 7.9 48.0 8.3 49.0 9.1 49.0 12.4 61.0 11.2 61.0 1/4 0.9 1.5 3/8 1-1/8 146.0 oz. 1/12 0.6 1.2 3/8 5/8 90.0 oz. 1/12 0.6 1.2 3/8 5/8 79.0 oz. 1/12 0.6 1.2 3/8 5/8 136.0 oz. 1/12 0.6 1.2 3/8 3/4 83.0 oz. 1/6 1.1 2.1 3/8 3/4 113.0 oz. 1/12 0.6 1.2 3/8 3/4 95.0 oz. 460-60-3 208/230-60-1 208/230-60-1 208/230-60-1 11.7 10.3 10.
CONDENSING UNIT SPECIFICATIONS RCC48 A3A 48600 RCC48 A3B 48000 RCC60 A2A 59500 RCC60 A2B 60000 RCC60 A3A 58800 RCC60 A3B 60000 RCE24 A2A 25000 RCE24 A2B 25000 RCE30 A2A RCE30 A2B RCE36 A2A RCE36 A2B RCE42 A2A RCE42 A2B RCE48 A2A RCE48 A2B 29200 30000 36000 36000 40500 40500 48000 48000 R.L. AMPS 12.2 12.2 14.7 14.7 16.5 16.5 18.3 18.3 L.R. AMPS 67.0 67.0 83.0 83.0 95.0 95.0 109.0 109.0 HORSEPOWER 1/12 1/12 1/4 1/4 1/4 1/4 1/4 1/4 R.L. AMPS 0.6 0.6 2.
CONDENSING UNIT SPECIFICATIONS MODEL COOLING CAPACITY, BTUH RCE60 A2A RCE60 A2B 58000 58000 COMPRESSOR R.L. AMPS 25.0 25.0 L.R. AMPS 169.0 169.0 HORSEPOWER 1/4 1/4 R.L. AMPS 2.1 2.1 L.R. AMPS 3.7 3.7 CONDENSER FAN MOTOR LIQUID LINE, INCHES O.D. SUCTION LINE, INCHES O.D. REFRIGERANT CHARGE POWER SUPPLY MIN.CIRCUIT AMPACITY MAX. OVERCURRENT DEVICE 3/8 3/8 1 1/8 1 1/8 250.0 oz. 250.0 oz. 208/230-60-1 208/230-60-1 33.4 33.4 55 55 1/2" or 3/4" 1/2 or 3/4 ELECT.
CONDENSING UNIT SPECIFICATIONS MODEL VCA60 B2A 60000 VCA60 B3A 60000 VCB18 A2A 18000 COOLING CAPACITY, BTUH COMPRESSOR R.L. AMPS 27.7 18.6 7.2 L.R. AMPS 123.0 128.0 49.0 CONDENSER FAN MOTOR HORSEPOWER 1/4 1/4 1/10 R.L. AMPS 1.7 1.7 0.6 L.R. AMPS 3.7 3.7 1.0 LIQUID LINE, INCHES O.D. 3/8 3/8 1/4 1-1/8 1-1/8 5/8 SUCTION LINE, INCHES O.D. REFRIGERANT CHARGE 119.0 oz. 123.0 oz. 54.0 oz. 208/230-60-1 208/230-60-3 208/230-60-1 POWER SUPPLY MIN.CIRCUIT AMPACITY 36.3 25.0 9.6 MAX.
CONDENSING UNIT SPECIFICATIONS Models RCA18A2A RCB18A2A RCC18A2B VCB18A2B RCA24A2B RCB24A2B RCC24A2B RCE24A2A VCB24A2B RCA30A2A RCB30A2A RCB30A2B RCB30A2C RCC30A2B RCE30A2A VCB30A2B RCA36A2A RCB36A2B RCB36A3B RCB36A4B RCC36A2B RCC36A3B RCE36A2A VCB36A2B RCA42A2A RCB42A2A RCC42A2B RCE42A2A VCB42A2B RCA48A2A RCB48A2B RCB48A3B RCB48A4B RCC48A2B RCC48A3B RCE48A2A VCB48A2B Dimensions Square Base Height 26" 25-1/2" 26" 25-1/2" 29-1/2" 25-1/2" 29-1/2" 29-1/2" Amana Models 29-1/2" 35-5/8" 33-1/2" 33-
BCA/BHA BLOWER COIL SPECIFICATIONS MODEL BCA18TA BHA18FA BCA24TA BHA24FA BCA30TA BHA30FA BCA36TA BHA36FA BCA42TA BHA42FA BCA48TA BHA48FA BCA60TA BHA60FA COOLING CAPACITY, BTUH 18,000 24,000 30,000 36,000 42,000 48,000 60,000 5.2 BCA 5.6 BAH 6.1 BCA 5.6 BHA EVAPORATOR COIL FACE AREA - SQ. FT. 3.8 4.7 ROWS DEEP 3 BCA 2 BHA 2 FINS/INCH 4 BCA 3 BHA 12 BCA 14 BHA 3 14 BLOWER ASSEMBLY BLOWER WHEEL D x W 9x6 MOTOR H.P. 9x8 10 x 7 1/6 10 x 9 1/4 FULL LOAD AMPS 1.0 1.
BCA/BHA BLOWER COIL SPECIFICATIONS BLOWER COIL DIMENSIONS 18 - 36 UNIT SIZE 42 48 - 60 A 49 7/8 50 56 3/8 B 19 23 27 C 20 1/2 25 28 1/2 D 20 5/8 21 20 5/8 E 18 7/8 23 26 7/8 FILTER SIZE (NOMINAL) 16 x 20 x 1 20 x 20 x 1 20 x 23 1/2 x 1 DIMENSION 17 Rev.
BBA/BBC BLOWER COIL SPECIFICATIONS 2 4 11 3/8 "A" 2 3 Knockouts 1 - 3/32 1 - 23/64 1 - 23/32 2 1/16 "H" 19 5/8 "B" 21 1/8 "W" Dimensions, inches (mm) MODEL W H A B BBA24A2A 16 - 1/2 (419) BBA36A2A 1 7/8 Knockout 15 (381) 15 (381) 22 - 1/4 (565) Shipping Weight lbs.(kg) Physical Information Blower Wheel Blower Motor MCA1 (D x W) (HP) MOP1 63 (28.6) 9x7 1/4 1.9 15 68 (30.8) 10 x 7 1/3 3 15 BBA48A2A 20 - 1/2 (521) 19 (483) 19 (483) 78 (35.4) 10 x 10 1/3 3.
Model BBA36A2A BBA48A2A BBA60A2A BBC36A2A BBC60A2A L1/L2 L3/L4 L5/L6 L1/L2 L3/L4 L5/L6 31.3 44.8 57.3 57.3 26 57.3 55 34.7 48.2 60.7 60.7 26 60.7 55 57.3 55 26 60.7 55 26 57.3 52 55 60.7 52 55 83.3 109.2 135.2 161.2 86.6 112.6 138.6 164.5 Maximum Overcurrent Protection Model BBA24A2A BBA36A2A BBA48A2A BBA60A2A BBC36A2A 19 Rev.
BBA/BBC BLOWER CCA_TCACOIL & CCA_TCB SPECIFICATIONS CASED COIL SPECIFICATIONS MODEL EVAPORATOR COIL Face Area (sq. ft.) Rows Deep Fins/Inch DRAIN LINE SIZE AUX. DRAIN SIZE HOLDING CHARGE REFRIGERATION LINE CONNECTIONS (A Mdls) (B Mdls) APPROXIMATE SHIPPING WEIGHT CCA18TCA CCA18TCB CCA24TCA CCA24TCB CCA30/36TCA/B CCA30/36TDB CCA42TCA CCA42TCB CCA42TDB CCA48TCA CCA48TCB CCA60TCA CCA60TCB 3.8 4.7 4.7 4.7 5.2 6.
CCA--FCC & CHA--TCC Cased A-Coil Specifications Evaporator Coil Face Area (Sq. Ft.) Rows FPI Drain Connections Primary Auxiliary Refrig. Line Connection Liquid* Vapor* Approx. Shipping Weight CCA18FCC CCA24FCC CHA18TCC CCA30FCC CHA24TCC CCA30FDC CCA36FCC CHA30TCC CCA36FDC CCA42FCC CHA36TCC CCA42FDC 2.81 2 16 2.81 3 14 3.75 2 16 3.75 3 14 4.
BBA/BBC CCA_FCC, BLOWERFDC COIL & SPECIFICATIONS CHA_TCC CASED COIL SPECIFICATIONS 1/8 or 21 op) m) T o B ( Bott ( C A H 2 H 7 4 3/4 1 W 1 5/8 2 3/4 Cabinet A-Coil Coil Cabinet Width (W) Model ( CCA--F*C ) ( CHA--TCC ) CCA18FCC CCA24FCC CHA18TCC CCA30FCC CHA24TCC CCA36FCC CHA30TCC CCA42FCC CHA36TCC CCA30FDC CCA36FDC CCA42FDC CCA48FCC CHA42TCC CCA36FKC CCA48FDC CCA54FCC CHA48TCC CCA57FCC CHA54TCC CCA60FCC CHA57TCC CHA60TCC Cases CCD-- Height (H) Small ( 16 1/2 ) Medium ( 20 1/2 ) Large ( 24
BBA/BBC BLOWER SPECIFICATIONS CCA_TUACOIL & CCA_FUA "A" COIL SPECIFICATIONS MODEL EVAPORATOR COIL Face Area (sq. ft.) Rows Deep Fins/Inch DRAIN LINE SIZE AUX. DRAIN SIZE HOLDING CHARGE REFRIGERATION LINE CONNECTIONS CCA18TUA/B CCA18FUA/B CCA24TUA/B CCA30FUA/B CCA30TUA CCA36TUA CCA36FUA CCA42TUA/B CCA42FUA/B CCA48TUA/B CCA60TUA CCA60FUA 3.8 4.7 4.7 4.7 5.2 6.1 5.
BBA/BBC BLOWER CCA_FSCCOIL & CHA_TSC SPECIFICATIONS "A" COIL SPECIFICATIONS 9/16 2 5/16 1 1/8 A 20 11/16 3 3/4 6 16 9/16 1 7/8 3 7/8 D C B MODEL CCA18FSC DIMENSIONS (inches) A C D 15 3 7/16 8 1/8 19 3 7/16 12 1/8 23 4 1/4 14 9/16 12 1/4 CCA24FSC CHA18TSC 12 1/2 CCA30FSC CHA24TSC 16 1/4 CCA36FSC CHA30TSC 16 1/2 CCA42FSC CHA36TSC 18 5/8 CCA48FSC CHA42TSC 20 1/4 CCA54FSC CHA48TSC 21 5/8 CCA57FSC CHA54TSC 22 CCA60FSC CHA57TSC 24 CHA60TSC 24 3/8 24 Rev.
CCA_FSCCOIL & CHA_TSC BBA/BBC BLOWER SPECIFICATIONS "A" COIL SPECIFICATIONS CCA--FSC & CHA--TSC Uncased A-Coil Specifications MODEL Evaporator Coil Face Area (Sq. Ft.) Rows FPI Drain Connections Primary Auxiliary Refrig. Line Connection Liquid* Vapor* Approx. Shipping Weight CCA18FSC CCA24FSC CHA18TSC CCA30FSC CHA24TSC CCA36FSC CHA30TSC CCA42FSC CHA36TSC 2.81 2 16 2.81 3 14 3.75 2 16 3.75 3 14 4.
CCF_F_CCOIL & CHF_TCC BBA/BBC BLOWER SPECIFICATIONS COIL SPECIFICATIONS MODEL CCF--F-C & CHF--FCC Horizontal A-Coil Specifications CCF30FCC CCF36FCC CCF24FCC CCF24FDC CHF24TCC CHF30TCC CHF18TCC Evaporator Coil Face Area (Sq. Ft.) Rows FPI Orifice Size Drain Connections Primary, Auxiliary Refrigeration Line Connection Liquid* Vapor* Approx. Shipping W eight (lbs) MODEL Evaporator Coil Face Area (Sq. Ft.
AIRFLOW CCH-F & CHH-T DATA HORIZONTAL COIL SPECIFICATIONS MODEL A HORIZONTAL CASED COIL DIMENSIONS CCH(48-60)F CCH(24-36)F CHH(24-36)T CHH(48-60)T 30 1/2 34 1/2 B 25 29 C 19 23 D 21 1/2 25 1/2 CONNECTION SIZES AND W EIGHTS MODEL CCH24F CHH24T CCH30F CHH30T CCH36F CHH36T CCH48F CHH48T CCH60F CHH60T Drain Line Size 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT Refrigerant Line Connections 3/8" Liq. 3/8" Liq. 3/8" Liq. 3/8" Liq. 3/8" Liq. 5/8" Suct. 3/4" Suct. 3/4" Suct.
PRODUCT DESIGN CONDENSING UNIT The RCA, RCB, RCC and VCB Remote Condensing Units are made in 1.5 through 5 ton sizes. RCE models are available in 2 through 5 ton sizes. They are designed for 208-240 volt single phase applications. The RCA/RCB 3, 4, and 5 ton models are also available for 230V and 460V 3 phase applications. The RCC 3, 4, and 5 ton models are also available for 230V 3 phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan.
PRODUCT DESIGN lent to insulation used on ductwork, if local codes permit. AeroQuip Flow Control Assembly FLOW CONTROL RESTRICTOR PLUG COPPER SWEAT CONNECTION FACTORY TUBE BULLET NOSE FEMALE FLOW CONTROL ADAPTER MALE FLOW CONTROL HOUSING HALF Chatleff Flow Control Assembly OUTDOOR UNIT Orifice Size AeroQuip ROK01A Kit Orifice Size Chatleff ROK___A Kits RCB18A2B RCB24A2B RCB30A2C RCB36A2B RCB42A2B RCB48A2B RCB60A2B 0.051 0.061 0.063 0.071 0.076 0.081 0.098 0.051 0.061 0.063 0.071 0.076 0.081 0.
SYSTEM OPERATION "A"COILS W ITH SERIAL # 9705 AND LATER "A" COIL ORIFICE SIZE CCA18F*C CCA24F*C CCA30F*C CCA36F*C CCA42F*C CCA48F*C CCA54F*C CCA57F*C CCA60F*C 0.051 0.061 0.063 0.071 0.076 0.081 0.081 0.098 0.098 HORIZONTAL COIL CCH-FCC AeroQuip Orifice size CCH-FCD Chatleff Orifice Size CCH24F CCH30F CCH36F CCH48F CCH60F 0.054 0.063 0.069 0.081 0.092 0.055 0.063 0.068 0.081 0.
SYSTEM OPERATION The indoor evaporator coil functions to cool and dehumidify the air conditioned spaces through the evaporative process taking place within the coil tubes. If the room thermostat fan selector switch should be set on the "ON" position then the indoor blower would run continuous rather than cycling with the compressor. NOTE: The pressures and temperatures shown are for demonstration purposes only. Actual temperatures and pressures are to be obtained from the "Cooling Performance Chart.
SYSTEM OPERATION BBA Electric Heat-Only Operations BBC Cooling-Only Operations As in the cooling-only operations, with the thermostat in the FAN—AUTO position and a “W2” or “E” call, the blower starts within three seconds. The board then starts turning-on banks of electric heat, one every ten seconds, until the supply temperature reaches 90°F.
SYSTEM OPERATION ELECTRIC HEATERS Optional electric heaters may be added, in the quantities shown in the specifications section to provide electric resistance heating. Under no condition shall more heaters than the quantity shown be installed. The low voltage circuit in the air handler is factory wired and terminates at the location provided for the electric heater(s). A minimum of field wiring is required to complete the installation.
AIRFLOW DATA BCA18T BHA18F BCA24T BHA24F BCA30T BHA30F BCA36T BHA36F BCA42T BHA42F BCA48T BHA48TA BCA60T BHA60TA TOTAL EXTERNAL STATIC "W.C. LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH 0.1 640 840 900 1270 1100 1270 1210 1430 1430 1660 1700 1990 1770 2320 0.2 620 820 860 1220 1020 1210 1160 1380 1420 1620 1690 1950 1760 2250 0.3 610 800 820 1150 980 1160 1100 1320 1400 1580 1660 1890 1740 2200 0.
AIRFLOW DATA UPFLOW é AND HORIZONTAL LEFT ç Blower Model BHA24TB002B BHA24TB002B BHA30TB002B BHA36TB002B BHA42TB002B BHA48TB002B BHA60TB002B Nominal Cooling Capacity (MBh) Nominal Cooling CFM (Y+G) Nominal Elec. Ht.
AIRFLOW DATA External BBA24A2A Static Airflow (CFM) (in. w.c.) Low Med High 0.2 590 830 1100 0.3 550 790 1070 0.4 500 740 1040 0.5 680 970 0.6 600 880 0.7 790 0.8 660 0.
CCA--F*C Air Flow Data - Static Pressure Drop Across Coil CCA18F*C Dry Wet 310 330 455 425 600 520 675 590 750 660 825 720 900 780 835 890 CCA24F*C Dry Wet 350 300 440 380 530 460 605 520 680 580 745 630 810 680 865 730 920 780 970 820 1020 860 CCA30F*C Dry Wet CCA36F*C Dry Wet 850 965 1080 1180 1280 1355 1430 1510 1590 780 895 1010 1105 1200 1275 1350 1420 1490 600 680 760 825 890 955 1020 1060 1100 640 730 820 900 980 1040 1100 1155 1210 CCA42F*C Dry Wet 750 890 1030 1120 1210 1330 1450 1555 1660
AIRFLOW DATA CHF--TCC Air Flow Da ta - Sta tic Pre ssure Drop Across Coil Horizonta l Right Applica tions P (in w .c.) .050 .075 .100 .125 .150 .175 .200 .225 .250 .275 .
AIRFLOW DATA Static Pressure Drop Across Coil Versus CFM Static Pressure Drop Across Coil** 0.050 0.075 0.100 0.125 0.150 0.175 0.200 0.225 0.250 0.275 0.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B18A2A / CCA18F*A 65 IDB* Airflow 675 600 525 59 18.4 0.70 18 1.19 4.3 144 65 17.9 0.67 18 1.18 4.3 143 64 16.5 0.65 19 1.15 4.2 139 62 63 19.1 0.59 15 1.22 4.4 155 69 18.5 0.56 16 1.21 4.4 154 68 17.1 0.54 16 1.18 4.3 149 66 67 20.9 0.41 12 1.27 4.6 164 76 20.3 0.39 12 1.26 4.5 162 75 18.7 0.37 12 1.22 4.4 158 73 MBh 18.7 19.3 20.9 S/T 0.80 0.71 0.54 Delta T 20 19 15 675 KW 1.21 1.23 1.28 AMPS 4.4 4.5 4.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B18A2A / CCA18F*A 65 IDB* Airflow 675 600 525 59 19.1 0.88 23 1.22 4.4 147 66 18.5 0.84 24 1.21 4.4 146 66 17.1 0.81 24 1.17 4.3 142 64 63 19.5 0.82 22 1.25 4.5 159 71 18.9 0.78 23 1.23 4.5 157 70 17.5 0.76 23 1.20 4.4 152 68 67 20.8 0.67 19 1.29 4.7 167 77 20.2 0.64 20 1.28 4.6 166 76 18.7 0.62 20 1.24 4.5 161 74 41 Rev. 3 MBh 19.4 19.8 20.7 S/T 0.92 0.89 0.80 Delta T 24 24 23 675 KW 1.23 1.26 1.30 AMPS 4.5 4.6 4.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B24A2A / CCA30F*A 65 IDB* Airflow 900 800 700 59 23.1 0.77 18 1.61 6.8 162 64 22.5 0.74 19 1.60 6.7 160 64 20.7 0.71 19 1.55 6.6 155 62 63 24.0 0.65 16 1.65 7.0 174 68 23.3 0.62 16 1.64 6.9 172 68 21.5 0.59 17 1.59 6.7 167 66 67 26.3 0.45 12 1.71 7.2 184 75 25.5 0.43 13 1.70 7.1 182 74 23.5 0.41 13 1.65 6.9 177 72 MBh 23.5 24.2 26.2 S/T 0.88 0.79 0.60 Delta T 21 19 16 900 KW 1.63 1.67 1.73 AMPS 6.9 7.0 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B24A2A / CCA30F*A 65 IDB* Airflow 71 27.9 0.55 16 1.81 7.6 196 81 27.1 0.52 16 1.79 7.6 194 80 25.0 0.51 17 1.74 7.3 188 78 59 23.4 1.00 24 1.79 7.5 185 69 22.7 0.95 25 1.77 7.4 183 69 21.0 0.92 25 1.73 7.2 178 67 63 23.9 0.94 23 1.84 7.7 199 74 23.2 0.89 24 1.82 7.6 197 73 21.4 0.86 24 1.77 7.4 191 71 MBh 24.4 24.8 26.0 S/T 1.00 0.98 0.88 Delta T 25 25 23 900 KW 1.66 1.70 1.76 AMPS 7.0 7.2 7.4 HI PR 167 179 189 LO PR 66 70 77 MBh 23.6 24.1 25.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B30A2A / CCA30F*A 65 IDB* Airflow 1125 1000 875 59 27.7 0.78 18 1.94 8.3 147 62 26.9 0.75 18 1.92 8.2 145 61 24.8 0.72 19 1.87 8.0 141 60 63 28.7 0.65 15 1.98 8.5 158 66 27.9 0.62 16 1.97 8.4 156 65 25.7 0.60 16 1.91 8.2 152 63 67 31.5 0.45 12 2.05 8.7 167 72 30.6 0.43 12 2.03 8.7 165 71 28.2 0.42 12 1.98 8.4 160 69 MBh 28.2 29.0 31.4 S/T 0.89 0.80 0.60 Delta T 21 19 15 1125 KW 1.96 2.00 2.07 AMPS 8.3 8.5 8.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B30A2A / CCA30F*A 65 IDB* Airflow 71 33.5 0.56 15 2.17 9.2 178 78 32.5 0.53 16 2.15 9.2 176 78 30.0 0.51 16 2.09 8.9 171 75 59 28.0 1.00 23 2.14 9.1 168 67 27.2 0.97 24 2.12 9.0 166 66 25.1 0.93 25 2.07 8.8 161 64 63 28.6 0.95 22 2.19 9.3 181 71 27.8 0.91 23 2.17 9.2 179 70 25.7 0.87 24 2.12 9.0 174 68 MBh 29.2 29.7 31.2 S/T 1.00 0.99 0.89 Delta T 24 24 23 1125 KW 1.99 2.04 2.11 AMPS 8.5 8.7 9.0 HI PR 151 163 172 LO PR 64 68 74 MBh 28.3 28.9 30.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B36A2A / CCA36F*A 65 IDB* Airflow 1350 1200 1050 59 35.2 0.78 19 2.42 10.7 163 64 34.1 0.75 20 2.40 10.6 161 64 31.5 0.72 20 2.33 10.3 157 62 63 36.5 0.65 16 2.48 11.0 175 68 35.4 0.62 17 2.46 10.9 174 68 32.7 0.60 17 2.39 10.6 168 66 67 39.9 0.45 12 2.57 11.4 185 75 38.8 0.43 13 2.54 11.3 183 74 35.8 0.42 13 2.47 10.9 178 72 MBh 35.8 36.8 39.9 S/T 0.89 0.80 0.60 Delta T 22 20 16 1350 KW 2.44 2.50 2.59 AMPS 10.8 11.1 11.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B36A2A / CCA36F*A 65 IDB* Airflow 71 42.5 0.56 16 2.71 12.0 197 81 41.2 0.53 17 2.69 11.9 195 80 38.1 0.51 17 2.61 11.6 189 78 59 35.6 1.00 24 2.68 11.8 187 69 34.5 0.97 26 2.66 11.7 185 69 31.9 0.93 26 2.58 11.4 179 67 63 36.3 0.95 23 2.75 12.1 201 74 35.3 0.91 24 2.72 12.0 199 73 32.6 0.87 25 2.65 11.7 193 71 MBh 37.0 37.8 39.5 S/T 1.00 0.99 0.89 Delta T 25 25 24 1350 KW 2.49 2.55 2.64 AMPS 11.0 11.3 11.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B36A3A / CCA36T*A 65 IDB* Airflow 1350 1200 1050 59 35.1 0.78 19 2.42 7.5 163 64 34.1 0.75 19 2.40 7.4 161 64 31.4 0.72 20 2.33 7.2 157 62 63 36.4 0.65 16 2.48 7.6 175 68 35.3 0.62 17 2.46 7.6 174 68 32.6 0.60 17 2.39 7.4 168 66 67 39.8 0.45 12 2.57 7.9 185 75 38.7 0.43 13 2.54 7.8 183 74 35.7 0.42 13 2.47 7.6 178 72 MBh 35.7 36.7 39.8 S/T 0.89 0.80 0.60 Delta T 22 20 16 1350 KW 2.44 2.50 2.59 AMPS 7.5 7.7 8.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B36A3A / CCA36T*A 65 IDB* Airflow 71 42.4 0.56 16 2.71 8.3 197 81 41.1 0.53 17 2.69 8.3 195 80 38.0 0.51 17 2.61 8.0 189 78 59 35.5 1.00 24 2.68 8.2 187 69 34.4 0.97 25 2.66 8.1 185 69 31.8 0.93 26 2.58 7.9 179 67 63 36.2 0.95 23 2.75 8.4 201 74 35.2 0.91 24 2.72 8.3 199 73 32.5 0.87 25 2.65 8.1 193 71 MBh 36.9 37.7 39.4 S/T 1.00 0.99 0.89 Delta T 25 25 24 1350 KW 2.49 2.55 2.64 AMPS 7.7 7.9 8.1 HI PR 168 181 191 LO PR 66 70 77 MBh 35.9 36.6 38.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B36A4A / CCA36T*A 65 IDB* Airflow 1350 1200 1050 59 35.1 0.78 19 2.42 4.1 163 64 34.1 0.75 19 2.40 4.1 161 64 31.4 0.72 20 2.33 4.0 157 62 63 36.4 0.65 16 2.48 4.2 175 68 35.3 0.62 17 2.46 4.2 174 68 32.6 0.60 17 2.39 4.1 168 66 67 39.8 0.45 12 2.57 4.4 185 75 38.7 0.43 13 2.54 4.3 183 74 35.7 0.42 13 2.47 4.2 178 72 MBh 35.7 36.7 39.8 S/T 0.89 0.80 0.60 Delta T 22 20 16 1350 KW 2.44 2.50 2.59 AMPS 4.2 4.3 4.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B36A4A / CCA36T*A 65 IDB* Airflow 71 42.4 0.56 16 2.71 4.6 197 81 41.1 0.53 17 2.69 4.6 195 80 38.0 0.51 17 2.61 4.4 189 78 59 35.5 1.00 24 2.68 4.5 187 69 34.4 0.97 25 2.66 4.5 185 69 31.8 0.93 26 2.58 4.4 179 67 63 36.2 0.95 23 2.75 4.6 201 74 35.2 0.91 24 2.72 4.6 199 73 32.5 0.87 25 2.65 4.5 193 71 MBh 36.9 37.7 39.4 S/T 1.00 0.99 0.89 Delta T 25 25 24 1350 KW 2.49 2.55 2.64 AMPS 4.2 4.3 4.5 HI PR 168 181 191 LO PR 66 70 77 MBh 35.9 36.6 38.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B42A2A / CCA42F*A 65 IDB* Airflow 1575 1400 1225 59 41.1 0.76 18 2.80 11.7 161 62 39.9 0.73 19 2.77 11.6 159 61 36.8 0.70 19 2.69 11.2 154 60 63 42.6 0.64 16 2.87 12.0 173 66 41.3 0.61 17 2.84 11.9 171 65 38.2 0.59 17 2.76 11.5 166 63 67 46.7 0.44 12 2.97 12.4 183 72 45.3 0.42 13 2.94 12.3 181 71 41.8 0.41 13 2.86 11.9 175 69 MBh 41.8 43.0 46.6 S/T 0.87 0.78 0.59 Delta T 21 19 16 1575 KW 2.82 2.89 3.00 AMPS 11.8 12.1 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B42A2A / CCA42F*A 65 IDB* Airflow 71 49.6 0.54 16 3.14 13.1 194 78 48.2 0.52 16 3.11 13.0 192 78 44.5 0.50 17 3.02 12.6 187 75 59 41.5 1.00 24 3.11 12.9 184 67 40.3 0.94 25 3.08 12.8 182 66 37.2 0.91 25 2.99 12.4 177 64 63 42.4 0.93 23 3.18 13.2 198 71 41.2 0.88 24 3.15 13.1 196 70 38.0 0.85 24 3.07 12.7 190 68 MBh 43.3 44.1 46.2 S/T 1.00 0.96 0.87 Delta T 25 25 23 1575 KW 2.88 2.95 3.06 AMPS 12.0 12.3 12.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B48A2A / CCA60F*A 65 IDB* Airflow 1800 1600 1400 59 48.5 0.75 19 3.40 15.6 143 62 47.1 0.72 19 3.37 15.4 142 61 43.5 0.69 20 3.28 15.0 138 60 63 50.3 0.63 16 3.48 15.9 154 66 48.8 0.60 17 3.45 15.8 153 65 45.0 0.58 17 3.36 15.4 148 63 67 55.1 0.44 12 3.60 16.5 163 72 53.5 0.42 13 3.57 16.3 161 71 49.4 0.40 13 3.47 15.9 156 69 MBh 49.3 50.8 55.0 S/T 0.86 0.77 0.58 Delta T 22 20 16 1800 KW 3.43 3.51 3.63 AMPS 15.7 16.1 16.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B48A2A / CCA60F*A 65 IDB* Airflow 71 58.6 0.54 16 3.79 17.4 173 78 56.9 0.51 17 3.76 17.2 172 78 52.5 0.49 17 3.66 16.7 166 75 59 49.0 1.00 25 3.75 17.1 164 67 47.6 0.93 25 3.72 17.0 162 66 43.9 0.90 26 3.62 16.5 157 64 63 50.1 0.91 23 3.84 17.5 176 71 48.6 0.87 24 3.81 17.4 175 70 44.9 0.84 25 3.71 16.9 169 68 MBh 51.1 52.1 54.5 S/T 0.98 0.95 0.86 Delta T 26 25 24 1800 KW 3.49 3.57 3.70 AMPS 16.0 16.4 16.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B48A3A / CCA60T*A 65 IDB* Airflow 1800 1600 1400 59 48.4 0.75 19 3.40 10.1 143 62 47.0 0.72 19 3.37 10.1 142 61 43.4 0.69 20 3.28 9.8 138 60 63 50.2 0.63 16 3.48 10.4 154 66 48.7 0.60 17 3.45 10.3 153 65 45.0 0.58 17 3.36 10.0 148 63 67 55.0 0.44 12 3.60 10.7 163 72 53.4 0.42 13 3.56 10.6 161 71 49.3 0.40 13 3.47 10.3 156 69 MBh 49.2 50.7 54.9 S/T 0.86 0.77 0.58 Delta T 22 20 16 1800 KW 3.43 3.51 3.63 AMPS 10.2 10.4 10.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B48A3A / CCA60T*A 65 IDB* Airflow 71 58.5 0.54 16 3.79 11.2 173 78 56.8 0.51 17 3.76 11.1 172 78 52.4 0.49 17 3.66 10.8 166 75 59 48.9 1.00 25 3.75 11.1 164 67 47.5 0.93 25 3.72 11.0 162 66 43.9 0.90 26 3.62 10.7 157 64 63 50.0 0.91 23 3.84 11.3 176 71 48.6 0.87 24 3.80 11.2 175 70 44.8 0.84 25 3.70 10.9 169 68 MBh 51.0 52.0 54.4 S/T 0.98 0.95 0.86 Delta T 26 25 24 1800 KW 3.49 3.57 3.69 AMPS 10.4 10.6 10.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B48A4A / CCA60T*A 65 IDB* Airflow 1800 1600 1400 59 48.4 0.75 19 3.40 5.8 143 62 47.0 0.72 19 3.37 5.7 142 61 43.4 0.69 20 3.28 5.6 138 60 63 50.2 0.63 16 3.48 5.9 154 66 48.7 0.60 17 3.45 5.8 153 65 45.0 0.58 17 3.36 5.7 148 63 67 55.0 0.44 12 3.60 6.1 163 72 53.4 0.42 13 3.56 6.0 161 71 49.3 0.40 13 3.47 5.9 156 69 MBh 49.2 50.7 54.9 S/T 0.86 0.77 0.58 Delta T 22 20 16 1800 KW 3.43 3.51 3.63 AMPS 5.8 5.9 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B48A4A / CCA60T*A 65 IDB* Airflow 71 58.5 0.54 16 3.79 6.4 173 78 56.8 0.51 17 3.76 6.3 172 78 52.4 0.49 17 3.66 6.2 166 75 59 48.9 1.00 25 3.75 6.3 164 67 47.5 0.93 25 3.72 6.2 162 66 43.9 0.90 26 3.62 6.1 157 64 63 50.0 0.91 23 3.84 6.4 176 71 48.6 0.87 24 3.80 6.4 175 70 44.8 0.84 25 3.70 6.2 169 68 MBh 51.0 52.0 54.4 S/T 0.98 0.95 0.86 Delta T 26 25 24 1800 KW 3.49 3.57 3.69 AMPS 5.9 6.0 6.2 HI PR 148 159 168 LO PR 64 68 74 MBh 49.5 50.5 52.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B60A2A / CCA60F*A 65 IDB* Airflow 2250 1800 1750 59 60.6 0.71 18 4.22 18.1 143 59 58.6 0.67 20 4.15 17.8 140 58 58.0 0.66 20 4.10 17.6 138 57 63 62.8 0.60 15 4.32 18.6 154 63 60.7 0.56 17 4.24 18.2 151 61 60.1 0.55 18 4.20 18.0 149 61 67 68.9 0.41 12 4.48 19.2 162 68 66.5 0.39 13 4.40 18.8 159 67 65.9 0.38 13 4.34 18.6 157 66 MBh 61.7 63.5 68.7 S/T 0.81 0.72 0.55 Delta T 20 19 15 2250 KW 4.26 4.36 4.52 AMPS 18.3 18.7 19.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B60A2A / CCA60F*A 65 IDB* Airflow 71 73.2 0.51 15 4.72 20.2 173 74 70.8 0.48 17 4.64 19.9 169 73 70.1 0.47 17 4.58 19.6 167 72 59 61.3 0.92 23 4.67 20.0 164 64 59.2 0.87 26 4.59 19.6 160 62 58.6 0.86 26 4.54 19.4 158 61 63 62.6 0.86 22 4.79 20.4 176 68 60.5 0.81 25 4.70 20.1 173 66 59.9 0.80 25 4.65 19.8 170 65 MBh 63.9 65.1 68.2 S/T 0.93 0.90 0.81 Delta T 24 24 23 2250 KW 4.34 4.44 4.60 AMPS 18.6 19.1 19.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B60A3A / CCA60F*A 65 IDB* Airflow 2250 1800 1750 59 60.6 0.71 18 4.22 11.4 143 59 58.6 0.67 20 4.15 11.2 140 58 58.0 0.66 20 4.10 11.1 138 57 63 62.8 0.60 15 4.32 11.6 154 63 60.7 0.56 17 4.24 11.5 151 61 60.1 0.55 18 4.20 11.3 149 61 67 68.9 0.41 12 4.48 12.0 162 68 66.5 0.39 13 4.40 11.8 159 67 65.9 0.38 13 4.34 11.7 157 66 MBh 61.7 63.5 68.7 S/T 0.81 0.72 0.55 Delta T 20 19 15 2250 KW 4.26 4.36 4.52 AMPS 11.5 11.7 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B60A3A / CCA60F*A 65 IDB* Airflow 71 73.2 0.51 15 4.72 12.6 173 74 70.8 0.48 17 4.64 12.4 169 73 70.1 0.47 17 4.58 12.3 167 72 59 61.3 0.92 23 4.67 12.5 164 64 59.2 0.87 26 4.59 12.3 160 62 58.6 0.86 26 4.54 12.1 158 61 63 62.6 0.86 22 4.79 12.7 176 68 60.5 0.81 25 4.70 12.5 173 66 59.9 0.80 25 4.65 12.4 170 65 MBh 63.9 65.1 68.2 S/T 0.93 0.90 0.81 Delta T 24 24 23 2250 KW 4.34 4.44 4.60 AMPS 11.7 11.9 12.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B60A4A / CCA60F*A 65 IDB* Airflow 2250 1800 1750 59 60.6 0.71 18 4.22 6.4 143 59 58.6 0.67 20 4.15 6.3 140 58 58.0 0.66 20 4.10 6.2 138 57 63 62.8 0.60 15 4.32 6.5 154 63 60.7 0.56 17 4.24 6.4 151 61 60.1 0.55 18 4.20 6.4 149 61 67 68.9 0.41 12 4.48 6.7 162 68 66.5 0.39 13 4.40 6.6 159 67 65.9 0.38 13 4.34 6.6 157 66 MBh 61.7 63.5 68.7 S/T 0.81 0.72 0.55 Delta T 20 19 15 2250 KW 4.26 4.36 4.52 AMPS 6.4 6.6 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCA/B60A4A / CCA60F*A 65 IDB* Airflow 71 73.2 0.51 15 4.72 7.1 173 74 70.8 0.48 17 4.64 7.0 169 73 70.1 0.47 17 4.58 6.9 167 72 59 61.3 0.92 23 4.67 7.0 164 64 59.2 0.87 26 4.59 6.9 160 62 58.6 0.86 26 4.54 6.8 158 61 63 62.6 0.86 22 4.79 7.2 176 68 60.5 0.81 25 4.70 7.0 173 66 59.9 0.80 25 4.65 7.0 170 65 MBh 63.9 65.1 68.2 S/T 0.93 0.90 0.81 Delta T 24 24 23 2250 KW 4.34 4.44 4.60 AMPS 6.6 6.7 6.9 HI PR 147 158 167 LO PR 61 65 71 MBh 61.7 62.9 65.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB18A2B / CCA18F*C 65 IDB* Airflow 675 600 525 59 17.2 0.71 17 1.21 4.9 148 61 16.7 0.68 17 1.20 4.9 147 60 15.4 0.66 18 1.16 4.7 142 58 63 17.8 0.60 14 1.24 5.0 159 64 17.3 0.57 15 1.22 5.0 158 64 16.0 0.55 15 1.19 4.9 153 62 67 19.5 0.41 11 1.28 5.2 168 70 19.0 0.39 11 1.27 5.2 167 70 17.5 0.38 12 1.23 5.0 162 68 MBh 17.5 18.0 19.5 S/T 0.81 0.73 0.55 Delta T 19 18 15 675 KW 1.22 1.25 1.29 AMPS 5.0 5.1 5.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB18A2B / CCA18F*C 65 IDB* Airflow 675 600 525 59 17.8 0.89 22 1.23 5.0 151 62 17.3 0.85 22 1.22 5.0 150 61 16.0 0.82 23 1.19 4.8 145 59 63 18.2 0.83 21 1.26 5.1 163 66 17.7 0.80 22 1.25 5.1 161 65 16.3 0.77 22 1.21 4.9 156 63 67 19.4 0.68 18 1.30 5.3 172 72 18.9 0.65 19 1.29 5.3 170 71 17.4 0.62 19 1.26 5.1 165 69 67 Rev. 3 MBh 18.1 18.5 19.3 S/T 0.93 0.90 0.81 Delta T 23 23 21 675 KW 1.24 1.27 1.31 AMPS 5.1 5.2 5.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB24A2B / CCA30F*C 65 IDB* Airflow 900 800 700 59 23.5 0.71 17 1.62 6.7 154 61 22.8 0.68 18 1.60 6.6 152 60 21.1 0.66 18 1.56 6.4 148 58 63 24.4 0.60 15 1.66 6.8 165 64 23.7 0.57 15 1.64 6.8 164 64 21.8 0.55 16 1.60 6.6 159 62 67 26.7 0.41 11 1.72 7.1 175 70 25.9 0.39 12 1.70 7.0 173 70 23.9 0.38 12 1.66 6.8 168 68 MBh 23.9 24.6 26.6 S/T 0.81 0.73 0.55 Delta T 20 18 15 900 KW 1.63 1.67 1.73 AMPS 6.7 6.9 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB24A2B / CCA30F*C 65 IDB* Airflow 71 28.4 0.51 15 1.82 7.5 186 76 27.6 0.48 15 1.80 7.4 184 76 25.4 0.47 16 1.75 7.2 178 73 59 23.8 0.92 22 1.80 7.4 176 65 23.1 0.88 23 1.78 7.3 174 65 21.3 0.85 24 1.73 7.1 169 63 63 24.3 0.86 21 1.84 7.5 189 69 23.6 0.82 22 1.82 7.5 187 69 21.8 0.79 23 1.77 7.3 182 67 MBh 24.8 25.2 26.4 S/T 0.93 0.90 0.81 Delta T 24 23 22 900 KW 1.66 1.71 1.77 AMPS 6.9 7.0 7.3 HI PR 158 170 180 LO PR 62 66 73 MBh 24.0 24.5 25.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB30A2B / CCA30F*A 65 IDB* Airflow 1125 1000 875 59 29.7 0.70 17 2.01 8.9 149 61 28.8 0.67 18 1.99 8.8 148 60 26.6 0.65 18 1.94 8.6 143 58 63 30.8 0.59 15 2.05 9.1 161 65 29.9 0.56 15 2.04 9.1 159 64 27.6 0.54 16 1.98 8.8 154 62 67 33.7 0.41 11 2.13 9.4 170 71 32.7 0.39 12 2.11 9.4 168 70 30.2 0.37 12 2.05 9.1 163 68 MBh 30.2 31.1 33.7 S/T 0.80 0.71 0.54 Delta T 20 18 15 1125 KW 2.03 2.07 2.15 AMPS 9.0 9.2 9.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB30A2B / CCA30F*A 65 IDB* Airflow 71 35.9 0.50 15 2.24 10.0 181 77 34.8 0.48 15 2.22 9.9 179 76 32.1 0.46 16 2.16 9.6 173 74 59 30.0 0.91 22 2.22 9.8 171 66 29.1 0.87 23 2.20 9.7 169 65 26.9 0.84 24 2.14 9.5 164 63 63 30.7 0.85 21 2.27 10.1 184 70 29.8 0.81 22 2.25 10.0 182 69 27.5 0.78 23 2.19 9.7 177 67 MBh 31.3 31.9 33.4 S/T 0.92 0.89 0.80 Delta T 23 23 22 1125 KW 2.06 2.11 2.18 AMPS 9.2 9.4 9.7 HI PR 154 166 175 LO PR 63 67 73 MBh 30.4 30.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB30A2C / CCA30F*C 65 IDB* Airflow 1125 1000 875 59 28.4 0.73 17 1.95 8.2 158 61 27.6 0.70 18 1.94 8.1 156 61 25.5 0.67 18 1.88 7.9 151 59 63 29.5 0.61 15 2.00 8.4 170 65 28.6 0.58 15 1.98 8.3 168 65 26.4 0.56 16 1.93 8.1 163 63 67 32.3 0.42 11 2.08 8.7 179 71 31.3 0.40 12 2.06 8.6 177 71 28.9 0.39 12 2.00 8.4 172 68 MBh 28.9 29.8 32.2 S/T 0.83 0.75 0.56 Delta T 20 18 15 1125 KW 1.97 2.02 2.10 AMPS 8.3 8.5 8.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB30A2C / CCA30F*C 65 IDB* Airflow 71 34.3 0.52 15 2.19 9.2 191 77 33.3 0.50 15 2.17 9.1 189 77 30.8 0.48 16 2.11 8.9 183 74 59 28.7 0.95 22 2.17 9.1 180 66 27.9 0.90 23 2.15 9.0 179 65 25.7 0.87 24 2.09 8.7 173 63 63 29.4 0.89 21 2.22 9.3 194 70 28.5 0.85 22 2.20 9.2 192 70 26.3 0.82 23 2.14 8.9 187 68 MBh 29.9 30.5 31.9 S/T 0.96 0.92 0.83 Delta T 23 23 22 1125 KW 2.01 2.06 2.13 AMPS 8.4 8.7 8.9 HI PR 162 175 185 LO PR 63 67 73 MBh 29.1 29.6 31.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB36A2B / CCA36F*C 65 IDB* Airflow 1350 1200 1050 59 34.3 0.72 17 2.37 9.7 159 62 33.3 0.69 18 2.35 9.6 157 61 30.7 0.67 18 2.28 9.4 153 59 63 35.6 0.60 15 2.43 10.0 171 66 34.5 0.58 15 2.41 9.9 169 65 31.9 0.56 15 2.34 9.6 164 63 67 39.0 0.42 11 2.52 10.3 181 72 37.8 0.40 12 2.49 10.2 179 71 34.9 0.38 12 2.42 9.9 174 69 MBh 34.9 35.9 38.9 S/T 0.82 0.74 0.56 Delta T 20 18 15 1350 KW 2.39 2.45 2.54 AMPS 9.8 10.1 10.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB36A2B / CCA36F*C 65 IDB* Airflow 71 41.4 0.51 15 2.66 10.9 192 78 40.2 0.49 15 2.64 10.8 190 77 37.1 0.47 15 2.56 10.5 185 75 59 34.7 0.93 22 2.63 10.8 182 67 33.7 0.89 23 2.61 10.7 180 66 31.1 0.86 23 2.53 10.4 175 64 63 35.4 0.88 21 2.70 11.0 196 71 34.4 0.84 22 2.67 10.9 194 70 31.8 0.81 22 2.60 10.6 188 68 MBh 36.1 36.8 38.6 S/T 0.95 0.91 0.82 Delta T 23 23 22 1350 KW 2.44 2.50 2.59 AMPS 10.0 10.3 10.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RC36A3B / CHA36T*C 65 IDB* Airflow 1350 1200 1050 59 34.1 0.72 17 2.37 6.5 159 61 33.1 0.69 17 2.35 6.5 157 61 30.6 0.67 18 2.28 6.3 153 59 63 35.3 0.60 15 2.43 6.7 171 65 34.3 0.58 15 2.41 6.6 169 65 31.7 0.56 15 2.34 6.4 164 63 67 38.7 0.42 11 2.52 6.9 180 71 37.6 0.40 11 2.50 6.8 179 71 34.7 0.38 12 2.42 6.7 173 68 MBh 34.7 35.7 38.6 S/T 0.82 0.74 0.56 Delta T 19 18 15 1350 KW 2.39 2.45 2.54 AMPS 6.6 6.7 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RC36A3B / CHA36T*C 65 IDB* Airflow 71 41.2 0.51 14 2.66 7.3 192 77 40.0 0.49 15 2.64 7.2 190 77 36.9 0.47 15 2.56 7.0 184 74 59 34.5 0.93 22 2.63 7.2 182 66 33.5 0.89 23 2.61 7.1 180 65 30.9 0.86 23 2.54 6.9 175 63 63 35.2 0.88 21 2.70 7.3 196 70 34.2 0.84 22 2.67 7.3 194 70 31.6 0.81 22 2.60 7.1 188 68 MBh 35.9 36.6 38.3 S/T 0.95 0.91 0.82 Delta T 23 23 21 1350 KW 2.44 2.50 2.59 AMPS 6.7 6.9 7.1 HI PR 164 176 186 LO PR 63 67 73 MBh 34.9 35.5 37.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB36A4B / CHA36T*C 65 IDB* Airflow 1350 1200 1050 59 34.1 0.72 17 2.45 3.6 159 61 33.1 0.69 17 2.43 3.5 157 61 30.6 0.67 18 2.36 3.5 153 59 63 35.3 0.60 15 2.51 3.7 171 65 34.3 0.58 15 2.49 3.6 169 65 31.7 0.56 15 2.42 3.5 164 63 67 38.7 0.42 11 2.60 3.8 180 71 37.6 0.40 11 2.58 3.7 179 71 34.7 0.38 12 2.50 3.6 173 68 MBh 34.7 35.7 38.6 S/T 0.82 0.74 0.56 Delta T 19 18 15 1350 KW 2.47 2.53 2.62 AMPS 3.6 3.7 3.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB36A4B / CHA36T*C 65 IDB* Airflow 71 41.2 0.51 14 2.74 4.0 192 77 40.0 0.49 15 2.72 3.9 190 77 36.9 0.47 15 2.64 3.8 184 74 59 34.5 0.93 22 2.71 3.9 182 66 33.5 0.89 23 2.69 3.9 180 65 30.9 0.86 23 2.62 3.8 175 63 63 35.2 0.88 21 2.78 4.0 196 70 34.2 0.84 22 2.75 4.0 194 70 31.6 0.81 22 2.68 3.9 188 68 MBh 35.9 36.6 38.3 S/T 0.95 0.91 0.82 Delta T 23 23 21 1350 KW 2.52 2.58 2.67 AMPS 3.7 3.7 3.9 HI PR 164 176 186 LO PR 63 67 73 MBh 34.9 35.5 37.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB42A2B / CCA42F*C 65 IDB* Airflow 1575 1400 1225 59 40.2 0.72 17 2.82 11.8 157 59 39.0 0.69 18 2.80 11.6 155 59 36.0 0.67 18 2.72 11.3 150 57 63 41.7 0.60 15 2.89 12.0 169 63 40.5 0.58 15 2.87 11.9 167 63 37.4 0.56 16 2.79 11.6 162 61 67 45.7 0.42 11 3.00 12.4 178 69 44.3 0.40 12 2.97 12.3 176 68 40.9 0.38 12 2.89 12.0 171 66 MBh 40.9 42.1 45.6 S/T 0.82 0.74 0.56 Delta T 20 18 15 1575 KW 2.85 2.92 3.02 AMPS 11.9 12.1 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB42A2B / CCA42F*C 65 IDB* Airflow 71 48.6 0.51 15 3.16 13.1 189 75 47.2 0.49 15 3.13 13.0 188 74 43.5 0.47 15 3.05 12.7 182 72 59 40.7 0.93 22 3.13 12.9 179 64 39.5 0.89 23 3.10 12.8 178 63 36.4 0.86 23 3.02 12.5 172 62 63 41.5 0.88 21 3.21 13.3 193 68 40.3 0.84 22 3.18 13.1 191 68 37.2 0.81 23 3.09 12.8 185 66 MBh 42.4 43.2 45.2 S/T 0.95 0.91 0.82 Delta T 23 23 22 1575 KW 2.90 2.97 3.08 AMPS 12.1 12.4 12.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB48A2B / CCA54F*C 65 IDB* Airflow 1800 1600 1400 59 46.2 0.70 17 3.06 12.5 150 61 44.8 0.67 17 3.03 12.4 148 60 41.4 0.65 18 2.95 12.0 144 58 63 47.8 0.59 14 3.13 12.8 161 64 46.4 0.56 15 3.10 12.7 160 64 42.9 0.54 15 3.02 12.3 155 62 67 52.4 0.41 11 3.24 13.2 170 70 50.9 0.39 11 3.22 13.1 169 70 47.0 0.37 12 3.13 12.7 164 68 MBh 46.9 48.3 52.3 S/T 0.80 0.71 0.54 Delta T 19 18 14 1800 KW 3.09 3.16 3.27 AMPS 12.6 12.9 13.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB48A2B / CCA54F*C 65 IDB* Airflow 71 55.7 0.50 14 3.42 14.0 181 76 54.1 0.48 15 3.39 13.9 179 76 50.0 0.46 15 3.30 13.5 174 73 59 46.7 0.91 22 3.39 13.8 172 65 45.3 0.87 23 3.36 13.6 170 65 41.8 0.84 23 3.27 13.3 165 63 63 47.7 0.85 21 3.47 14.1 185 69 46.3 0.81 22 3.44 14.0 183 69 42.7 0.78 22 3.34 13.6 177 67 MBh 48.6 49.5 51.9 S/T 0.92 0.89 0.80 Delta T 23 22 21 1800 KW 3.14 3.22 3.33 AMPS 12.8 13.1 13.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB48A3B / CCA54F*C + TXV03A 65 IDB* Airflow 1800 1600 1400 59 45.6 0.71 17 3.03 8.8 150 61 44.2 0.68 17 3.00 8.8 148 60 40.8 0.66 18 2.92 8.5 144 58 63 47.2 0.60 14 3.10 9.1 161 64 45.9 0.57 15 3.07 9.0 160 64 42.3 0.55 15 2.99 8.7 155 62 67 51.7 0.41 11 3.21 9.4 170 70 50.2 0.39 11 3.18 9.3 169 70 46.4 0.38 12 3.10 9.0 164 68 MBh 46.3 47.7 51.6 S/T 0.81 0.73 0.55 Delta T 19 18 14 1800 KW 3.06 3.13 3.24 AMPS 8.9 9.1 9.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB48A3B / CCA54F*C + TXV03A 65 IDB* Airflow 71 55.0 0.51 14 3.39 9.9 181 76 53.4 0.48 15 3.36 9.8 179 76 49.3 0.47 15 3.27 9.5 174 73 59 46.1 0.92 22 3.35 9.7 172 65 44.7 0.88 23 3.32 9.7 170 65 41.3 0.85 23 3.23 9.4 165 63 63 47.1 0.86 21 3.43 10.0 185 69 45.7 0.82 22 3.40 9.9 183 69 42.2 0.79 22 3.31 9.6 177 67 MBh 48.0 48.9 51.2 S/T 0.93 0.90 0.81 Delta T 23 22 21 1800 KW 3.11 3.19 3.30 AMPS 9.1 9.3 9.6 HI PR 154 166 175 LO PR 62 66 73 MBh 46.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB48A4B / CCA54F*C + TXV03A 65 IDB* Airflow 1800 1600 1400 59 45.6 0.71 17 3.18 5.5 150 61 44.2 0.68 17 3.15 5.5 148 60 40.8 0.66 18 3.07 5.4 144 58 63 47.2 0.60 14 3.25 5.7 161 64 45.9 0.57 15 3.22 5.6 160 64 42.3 0.55 15 3.14 5.5 155 62 67 51.7 0.41 11 3.36 5.8 170 70 50.2 0.39 11 3.33 5.8 169 70 46.4 0.38 12 3.25 5.6 164 68 MBh 46.3 47.7 51.6 S/T 0.81 0.73 0.55 Delta T 19 18 14 1800 KW 3.21 3.28 3.39 AMPS 5.6 5.7 5.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB48A4B / CCA54F*C + TXV03A 65 IDB* Airflow 71 55.0 0.51 14 3.54 6.1 181 76 53.4 0.48 15 3.51 6.1 179 76 49.3 0.47 15 3.42 5.9 174 73 59 46.1 0.92 22 3.50 6.1 172 65 44.7 0.88 23 3.47 6.0 170 65 41.3 0.85 23 3.38 5.9 165 63 63 47.1 0.86 21 3.58 6.2 185 69 45.7 0.82 22 3.55 6.1 183 69 42.2 0.79 22 3.46 6.0 177 67 MBh 48.0 48.9 51.2 S/T 0.93 0.90 0.81 Delta T 23 22 21 1800 KW 3.26 3.34 3.45 AMPS 5.7 5.8 6.0 HI PR 154 166 175 LO PR 62 66 73 MBh 46.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB60A2B / CCA60F*C 65 IDB* Airflow 2250 1800 1750 59 59.4 0.70 17 4.28 18.3 155 60 57.4 0.66 19 4.20 17.9 152 59 56.9 0.65 20 4.15 17.7 150 58 63 61.6 0.59 15 4.38 18.7 166 64 59.5 0.55 17 4.30 18.4 163 62 58.9 0.55 17 4.25 18.1 161 62 67 67.5 0.41 11 4.54 19.3 176 70 65.2 0.38 13 4.46 19.0 172 68 64.6 0.38 13 4.41 18.8 170 67 MBh 60.4 62.2 67.4 S/T 0.80 0.71 0.54 Delta T 20 18 15 2250 KW 4.32 4.42 4.59 AMPS 18.4 18.9 19.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB/VCB60A2B / CCA60F*C 65 IDB* Airflow 71 71.8 0.50 15 4.81 20.5 187 76 69.4 0.47 17 4.72 20.1 183 74 68.7 0.47 17 4.66 19.8 181 73 59 60.1 0.91 22 4.75 20.2 177 65 58.1 0.85 25 4.66 19.8 174 63 57.5 0.85 26 4.61 19.6 171 63 63 61.4 0.85 21 4.87 20.7 191 69 59.3 0.80 24 4.78 20.3 187 67 58.7 0.79 24 4.72 20.0 184 67 MBh 62.6 63.8 66.8 S/T 0.92 0.89 0.80 Delta T 23 23 22 2250 KW 4.40 4.51 4.68 AMPS 18.8 19.2 19.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB60A3B / CHA57T*C 65 IDB* Airflow 2250 1900 1750 59 60.8 0.69 17 4.35 11.7 154 61 59.0 0.66 19 4.31 11.6 152 60 58.1 0.64 19 4.24 11.4 150 59 63 63.0 0.58 15 4.46 12.0 166 64 61.1 0.55 16 4.42 11.9 164 64 60.2 0.53 17 4.35 11.7 161 63 67 69.0 0.40 11 4.63 12.4 175 70 67.0 0.38 12 4.58 12.3 173 70 66.0 0.37 13 4.51 12.1 170 68 MBh 61.8 63.6 68.9 S/T 0.79 0.70 0.53 Delta T 20 18 15 2250 KW 4.39 4.50 4.67 AMPS 11.8 12.1 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB60A3B / CHA57T*C 65 IDB* Airflow 71 73.4 0.49 15 4.89 13.1 186 76 71.2 0.47 16 4.85 13.0 184 76 70.2 0.45 17 4.77 12.8 181 74 59 61.4 0.90 22 4.84 12.9 176 65 59.6 0.85 25 4.79 12.8 175 65 58.7 0.82 25 4.72 12.6 172 64 63 62.8 0.84 22 4.96 13.2 190 69 60.9 0.80 24 4.91 13.1 188 69 60.0 0.77 24 4.83 12.9 185 68 MBh 64.0 65.2 68.3 S/T 0.91 0.87 0.79 Delta T 24 23 22 2250 KW 4.48 4.59 4.76 AMPS 12.0 12.3 12.7 HI PR 159 171 180 LO PR 62 66 73 MBh 62.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB60A4B / CHA57T*C 65 IDB* Airflow 2250 1900 1750 59 60.8 0.69 17 4.35 6.0 154 61 59.0 0.66 19 4.31 6.0 152 60 58.1 0.64 19 4.24 5.9 150 59 63 63.0 0.58 15 4.46 6.2 166 64 61.1 0.55 16 4.42 6.1 164 64 60.2 0.53 17 4.35 6.0 161 63 67 69.0 0.40 11 4.63 6.4 175 70 67.0 0.38 12 4.58 6.3 173 70 66.0 0.37 13 4.51 6.2 170 68 MBh 61.8 63.6 68.9 S/T 0.79 0.70 0.53 Delta T 20 18 15 2250 KW 4.39 4.50 4.67 AMPS 6.1 6.2 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB60A4B / CHA57T*C 65 IDB* Airflow 71 73.4 0.49 15 4.89 6.7 186 76 71.2 0.47 16 4.85 6.7 184 76 70.2 0.45 17 4.77 6.6 181 74 59 61.4 0.90 22 4.84 6.6 176 65 59.6 0.85 25 4.79 6.6 175 65 58.7 0.82 25 4.72 6.5 172 64 63 62.8 0.84 22 4.96 6.8 190 69 60.9 0.80 24 4.91 6.7 188 69 60.0 0.77 24 4.83 6.6 185 68 MBh 64.0 65.2 68.3 S/T 0.91 0.87 0.79 Delta T 24 23 22 2250 KW 4.48 4.59 4.76 AMPS 6.2 6.3 6.5 HI PR 159 171 180 LO PR 62 66 73 MBh 62.1 63.3 66.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB18B2A / CCA18F*C 65 IDB* Airflow 675 600 525 59 17.4 0.72 17 1.28 5.5 146 61 16.9 0.69 18 1.27 5.5 145 61 15.6 0.67 18 1.23 5.3 140 59 63 18.1 0.60 15 1.31 5.6 157 65 17.6 0.58 15 1.30 5.6 156 65 16.2 0.56 16 1.26 5.4 151 63 67 19.8 0.42 11 1.36 5.8 166 71 19.2 0.40 12 1.35 5.8 165 70 17.7 0.38 12 1.31 5.6 160 68 MBh 17.7 18.3 19.8 S/T 0.82 0.74 0.56 Delta T 20 18 15 675 KW 1.29 1.32 1.37 AMPS 5.6 5.7 5.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB18B2A / CCA18F*C 65 IDB* Airflow 675 600 525 59 18.1 0.90 22 1.30 5.6 149 63 17.5 0.86 23 1.29 5.6 148 62 16.2 0.83 23 1.26 5.4 143 60 63 18.4 0.85 21 1.34 5.7 161 66 17.9 0.81 22 1.32 5.7 159 66 16.5 0.78 23 1.29 5.5 154 64 67 19.7 0.69 18 1.38 5.9 170 73 19.1 0.66 19 1.37 5.9 168 72 17.7 0.63 20 1.33 5.7 163 70 95 Rev. 3 MBh 18.4 18.7 19.6 S/T 0.95 0.91 0.82 Delta T 24 23 22 675 KW 1.32 1.35 1.40 AMPS 5.7 5.8 6.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB24B2A / CCA24F*C 65 IDB* Airflow 900 800 700 59 23.1 0.70 17 1.68 7.2 160 61 22.4 0.67 17 1.67 7.2 158 60 20.7 0.65 18 1.62 7.0 154 58 63 23.9 0.59 14 1.72 7.4 172 65 23.2 0.56 15 1.71 7.4 170 64 21.4 0.54 15 1.66 7.1 165 62 67 26.2 0.41 11 1.79 7.7 182 71 25.4 0.39 11 1.77 7.6 180 70 23.5 0.37 12 1.72 7.4 175 68 MBh 23.5 24.2 26.2 S/T 0.80 0.71 0.54 Delta T 19 18 14 900 KW 1.70 1.74 1.81 AMPS 7.3 7.5 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB24B2A / CCA24F*C 65 IDB* Airflow 71 27.9 0.50 14 1.89 8.1 194 77 27.1 0.48 15 1.87 8.0 192 76 25.0 0.46 15 1.82 7.8 186 74 59 23.3 0.91 22 1.87 8.0 183 65 22.7 0.87 23 1.85 7.9 181 65 20.9 0.84 23 1.80 7.7 176 63 63 23.8 0.85 21 1.92 8.2 197 70 23.1 0.81 22 1.90 8.1 195 69 21.4 0.78 22 1.85 7.9 189 67 MBh 24.3 24.8 25.9 S/T 0.92 0.89 0.80 Delta T 23 22 21 900 KW 1.73 1.77 1.84 AMPS 7.4 7.6 7.9 HI PR 165 177 187 LO PR 63 67 73 MBh 23.6 24.1 25.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB30B2A / CCA30F*C 65 IDB* Airflow 1125 1000 875 59 29.2 0.71 17 2.13 9.7 156 60 28.4 0.68 18 2.11 9.6 155 59 26.2 0.66 18 2.06 9.4 150 58 63 30.3 0.60 15 2.18 10.0 168 64 29.4 0.57 15 2.16 9.9 167 63 27.1 0.55 16 2.10 9.6 162 61 67 33.2 0.41 11 2.26 10.3 178 70 32.2 0.39 12 2.24 10.2 176 69 29.7 0.38 12 2.18 9.9 171 67 MBh 29.7 30.6 33.1 S/T 0.81 0.73 0.55 Delta T 20 18 15 1125 KW 2.15 2.20 2.28 AMPS 9.8 10.0 10.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB30B2A / CCA30F*C 65 IDB* Airflow 71 35.3 0.51 15 2.39 10.9 189 76 34.2 0.48 15 2.37 10.8 187 75 31.6 0.47 15 2.30 10.5 182 73 59 29.5 0.92 22 2.36 10.7 179 65 28.7 0.88 23 2.34 10.6 177 64 26.5 0.85 24 2.28 10.3 172 62 63 30.2 0.86 21 2.42 11.0 193 69 29.3 0.82 22 2.40 10.9 191 68 27.0 0.79 23 2.33 10.6 185 66 MBh 30.8 31.3 32.8 S/T 0.93 0.90 0.81 Delta T 23 23 22 1125 KW 2.19 2.24 2.32 AMPS 10.0 10.2 10.6 HI PR 161 173 183 LO PR 62 66 72 MBh 29.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB36B2A / CCA36F*C 65 IDB* Airflow 1350 1200 1050 59 34.7 0.72 17 2.87 11.2 148 59 33.7 0.69 18 2.85 11.1 147 59 31.1 0.67 18 2.79 10.8 142 57 63 36.0 0.60 15 2.93 11.4 159 63 34.9 0.58 15 2.91 11.3 158 62 32.2 0.56 16 2.84 11.0 153 61 67 39.4 0.42 11 3.01 11.8 168 69 38.2 0.40 12 2.99 11.7 167 68 35.3 0.38 12 2.92 11.4 162 66 MBh 35.3 36.3 39.3 S/T 0.82 0.74 0.56 Delta T 20 18 15 1350 KW 2.89 2.95 3.04 AMPS 11.3 11.5 11.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB36B2A / CCA36F*C 65 IDB* Airflow 71 41.9 0.51 15 3.15 12.4 179 75 40.7 0.49 15 3.13 12.3 177 74 37.5 0.47 16 3.06 12.0 172 72 59 35.1 0.93 22 3.12 12.3 169 64 34.0 0.89 23 3.10 12.2 168 63 31.4 0.86 24 3.03 11.8 163 61 63 35.8 0.88 21 3.19 12.6 182 68 34.8 0.84 22 3.16 12.4 181 67 32.1 0.81 23 3.09 12.1 175 65 MBh 36.5 37.2 39.0 S/T 0.95 0.91 0.82 Delta T 24 23 22 1350 KW 2.94 2.99 3.08 AMPS 11.5 11.7 12.1 HI PR 153 164 173 LO PR 61 65 71 MBh 35.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB42B2A / CCA42F*C 65 IDB* Airflow 1575 1400 1225 59 40.2 0.72 17 2.82 11.8 157 59 39.0 0.69 18 2.79 11.6 155 59 36.0 0.67 18 2.72 11.3 150 57 63 41.7 0.60 15 2.89 12.0 169 63 40.5 0.58 15 2.86 11.9 167 63 37.4 0.56 16 2.78 11.6 162 61 67 45.7 0.42 11 2.99 12.4 178 69 44.3 0.40 12 2.96 12.3 176 68 40.9 0.38 12 2.88 12.0 171 66 MBh 40.9 42.1 45.6 S/T 0.82 0.74 0.56 Delta T 20 18 15 1575 KW 2.84 2.91 3.02 AMPS 11.9 12.1 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB42B2A / CCA42F*C 65 IDB* Airflow 71 48.6 0.51 15 3.16 13.1 189 75 47.2 0.49 15 3.13 13.0 188 74 43.5 0.47 15 3.04 12.7 182 72 59 40.7 0.93 22 3.12 12.9 179 64 39.5 0.89 23 3.09 12.8 178 63 36.4 0.86 23 3.01 12.5 172 62 63 41.5 0.88 21 3.20 13.3 193 68 40.3 0.84 22 3.17 13.1 191 68 37.2 0.81 23 3.08 12.8 185 66 MBh 42.4 43.2 45.2 S/T 0.95 0.91 0.82 Delta T 23 23 22 1575 KW 2.90 2.97 3.07 AMPS 12.1 12.4 12.8 HI PR 161 174 183 LO PR 61 65 71 MBh 41.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB48B2A / CCA48F*C 65 IDB* Airflow 1800 1600 1400 59 46.0 0.72 17 3.65 16.0 153 60 44.6 0.69 18 3.62 15.9 152 59 41.2 0.67 18 3.53 15.5 147 57 63 47.6 0.60 15 3.73 16.4 165 64 46.3 0.58 15 3.70 16.3 163 63 42.7 0.56 16 3.61 15.8 159 61 67 52.2 0.42 11 3.85 17.0 174 70 50.7 0.40 12 3.82 16.8 173 69 46.8 0.38 12 3.72 16.4 167 67 MBh 46.7 48.1 52.1 S/T 0.82 0.74 0.56 Delta T 20 18 15 1800 KW 3.68 3.76 3.89 AMPS 16.2 16.6 17.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB48B2A / CCA48F*C 65 IDB* Airflow 71 55.5 0.51 15 4.05 17.9 186 76 53.9 0.49 15 4.02 17.8 184 75 49.8 0.47 15 3.92 17.3 178 73 59 46.5 0.93 22 4.01 17.7 176 65 45.1 0.89 23 3.98 17.5 174 64 41.6 0.86 23 3.88 17.0 169 62 63 47.5 0.88 21 4.11 18.1 189 69 46.1 0.84 22 4.07 17.9 187 68 42.6 0.81 23 3.97 17.5 182 66 MBh 48.4 49.3 51.7 S/T 0.95 0.91 0.82 Delta T 23 23 22 1800 KW 3.74 3.83 3.95 AMPS 16.5 16.9 17.5 HI PR 158 170 180 LO PR 62 66 72 MBh 47.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB60B2A / CCA60F*C 65 IDB* Airflow 2250 1900 1750 59 57.3 0.72 17 4.12 20.2 161 60 55.6 0.69 19 4.08 20.1 160 59 54.8 0.67 19 4.01 19.7 157 58 63 59.4 0.60 15 4.22 20.7 173 64 57.7 0.58 16 4.18 20.6 172 63 56.8 0.56 17 4.11 20.2 169 62 67 65.1 0.42 11 4.37 21.4 183 70 63.2 0.40 12 4.33 21.2 181 69 62.2 0.38 13 4.26 20.9 178 68 MBh 58.3 60.0 65.0 S/T 0.82 0.74 0.56 Delta T 20 18 15 2250 KW 4.15 4.26 4.41 AMPS 20.4 20.9 21.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCB60B2A / CCA60F*C 65 IDB* Airflow 71 69.2 0.51 15 4.62 22.7 195 76 67.2 0.49 16 4.58 22.5 193 75 66.2 0.47 16 4.50 22.1 190 74 59 57.9 0.93 22 4.57 22.4 185 65 56.3 0.89 24 4.53 22.1 183 64 55.4 0.86 25 4.46 21.8 180 63 63 59.2 0.88 21 4.68 22.9 199 69 57.5 0.84 23 4.64 22.7 197 68 56.6 0.81 24 4.57 22.3 193 67 MBh 60.4 61.5 64.4 S/T 0.95 0.91 0.82 Delta T 23 23 22 2250 KW 4.23 4.34 4.50 AMPS 20.8 21.3 22.1 HI PR 166 179 189 LO PR 62 66 72 MBh 58.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC18A2A / CCA18T*A 65 IDB* Airflow 675 600 525 59 18.5 0.70 18 1.14 5.0 139 61 17.9 0.67 18 1.13 5.0 137 60 16.5 0.65 19 1.10 4.8 133 59 63 19.1 0.59 15 1.17 5.1 149 65 18.6 0.56 16 1.16 5.1 148 64 17.1 0.54 16 1.13 5.0 143 62 67 21.0 0.41 12 1.21 5.3 158 71 20.3 0.39 12 1.20 5.3 156 70 18.8 0.37 12 1.17 5.1 151 68 MBh 18.8 19.3 20.9 S/T 0.80 0.71 0.54 Delta T 20 19 15 675 KW 1.15 1.18 1.22 AMPS 5.1 5.2 5.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC18A2A / CCA18T*A 65 IDB* Airflow 71 22.3 0.50 15 1.28 5.6 168 77 21.6 0.48 16 1.27 5.5 166 76 20.0 0.46 16 1.23 5.4 161 74 59 18.7 0.91 23 1.27 5.5 159 66 18.1 0.87 24 1.25 5.5 157 65 16.7 0.84 24 1.22 5.3 152 63 63 19.1 0.85 22 1.30 5.6 171 70 18.5 0.81 23 1.28 5.6 169 69 17.1 0.78 23 1.25 5.4 164 67 MBh 19.4 19.8 20.7 S/T 0.92 0.89 0.80 Delta T 24 24 23 675 KW 1.18 1.20 1.25 AMPS 5.2 5.3 5.4 HI PR 143 154 162 LO PR 63 67 73 MBh 18.9 19.2 20.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC24A2A / CCA24T*A 65 IDB* Airflow 900 800 700 59 23.6 0.72 17 1.46 6.3 144 61 22.9 0.69 18 1.45 6.2 142 60 21.2 0.67 18 1.41 6.1 138 58 63 24.5 0.60 15 1.50 6.5 155 65 23.8 0.58 16 1.48 6.4 153 64 21.9 0.56 16 1.44 6.2 149 62 67 26.8 0.42 11 1.55 6.7 163 71 26.0 0.40 12 1.54 6.6 162 70 24.0 0.38 12 1.49 6.4 157 68 MBh 24.0 24.7 26.8 S/T 0.82 0.74 0.56 Delta T 20 19 15 900 KW 1.48 1.51 1.57 AMPS 6.4 6.5 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC24A2A / CCA24T*A 65 IDB* Airflow 71 28.5 0.51 15 1.64 7.1 174 77 27.7 0.49 16 1.62 7.0 172 76 25.6 0.47 16 1.58 6.8 167 74 59 23.9 0.93 23 1.62 6.9 165 66 23.2 0.89 24 1.61 6.9 163 65 21.4 0.86 24 1.56 6.7 158 63 63 24.4 0.88 22 1.66 7.1 177 70 23.7 0.84 23 1.65 7.1 175 69 21.9 0.81 23 1.60 6.9 170 67 MBh 24.9 25.4 26.6 S/T 0.95 0.91 0.82 Delta T 24 24 22 900 KW 1.50 1.54 1.59 AMPS 6.5 6.6 6.9 HI PR 148 159 168 LO PR 63 67 73 MBh 24.2 24.6 25.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC30A2A / CCA30T*A 65 IDB* Airflow 1125 1000 875 59 29.2 0.72 17 1.82 8.0 140 62 28.4 0.69 18 1.81 8.0 139 61 26.2 0.67 18 1.76 7.8 135 59 63 30.3 0.60 15 1.87 8.2 151 66 29.4 0.58 16 1.85 8.2 149 65 27.1 0.56 16 1.80 7.9 145 63 67 33.2 0.42 11 1.93 8.5 159 72 32.2 0.40 12 1.91 8.4 158 71 29.7 0.38 12 1.86 8.2 153 69 MBh 29.7 30.6 33.1 S/T 0.82 0.74 0.56 Delta T 20 18 15 1125 KW 1.84 1.88 1.95 AMPS 8.1 8.3 8.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC30A2A / CCA30T*A 65 IDB* Airflow 71 35.3 0.51 15 2.03 9.0 170 78 34.3 0.49 15 2.02 8.9 168 77 31.6 0.47 16 1.96 8.7 163 75 59 29.5 0.93 23 2.01 8.9 160 66 28.7 0.89 23 2.00 8.8 159 66 26.5 0.86 24 1.94 8.5 154 64 63 30.2 0.88 22 2.06 9.1 173 71 29.3 0.84 23 2.04 9.0 171 70 27.1 0.81 23 1.99 8.7 166 68 MBh 30.8 31.4 32.9 S/T 0.95 0.91 0.82 Delta T 24 23 22 1125 KW 1.87 1.92 1.98 AMPS 8.3 8.5 8.7 HI PR 144 155 164 LO PR 64 68 74 MBh 29.9 30.5 31.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A2A / CCA36T*A 65 IDB* Airflow 1350 1250 1050 59 34.0 0.71 16 2.14 9.9 145 61 33.6 0.70 17 2.14 9.8 145 61 31.0 0.67 18 2.08 9.6 140 59 63 35.2 0.60 14 2.20 10.1 156 65 34.9 0.58 15 2.19 10.1 156 65 32.2 0.56 16 2.13 9.8 151 63 67 38.6 0.41 11 2.27 10.4 165 71 38.2 0.40 11 2.27 10.4 164 71 35.3 0.39 12 2.21 10.1 159 69 MBh 34.5 35.6 38.5 S/T 0.81 0.73 0.55 Delta T 19 18 14 1350 KW 2.16 2.22 2.29 AMPS 10.0 10.2 10.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A2A / CCA36T*A 65 IDB* Airflow 71 41.0 0.51 14 2.40 11.0 175 78 40.6 0.50 15 2.39 11.0 175 77 37.5 0.48 16 2.33 10.7 170 75 59 34.3 0.92 22 2.37 10.9 166 66 34.0 0.90 23 2.37 10.9 165 66 31.4 0.87 24 2.30 10.6 161 64 63 35.1 0.86 21 2.43 11.2 179 71 34.7 0.85 22 2.42 11.1 178 70 32.1 0.82 23 2.36 10.8 173 68 MBh 35.8 36.5 38.2 S/T 0.93 0.90 0.81 Delta T 23 22 21 1350 KW 2.20 2.26 2.34 AMPS 10.1 10.4 10.7 HI PR 149 161 170 LO PR 63 67 74 MBh 35.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A3A / CCA36T*A 65 IDB* Airflow 1350 1250 1050 59 34.0 0.71 16 2.14 6.7 146 62 33.6 0.70 17 2.14 6.7 145 61 31.0 0.67 18 2.08 6.5 141 60 63 35.2 0.60 14 2.20 6.9 157 66 34.9 0.58 15 2.19 6.8 156 65 32.2 0.56 16 2.13 6.7 152 63 67 38.6 0.41 11 2.27 7.1 166 72 38.2 0.40 11 2.27 7.1 165 71 35.3 0.39 12 2.21 6.9 160 69 MBh 34.5 35.6 38.5 S/T 0.81 0.73 0.55 Delta T 19 18 14 1350 KW 2.16 2.22 2.29 AMPS 6.8 6.9 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A3A / CCA36T*A 65 IDB* Airflow 71 41.0 0.51 14 2.40 7.5 176 78 40.6 0.50 15 2.39 7.4 176 78 37.5 0.48 16 2.33 7.3 171 75 59 34.3 0.92 22 2.37 7.4 167 66 34.0 0.90 23 2.37 7.3 166 66 31.4 0.87 24 2.30 7.1 161 64 63 35.1 0.86 21 2.43 7.5 180 71 34.7 0.85 22 2.42 7.5 179 70 32.1 0.82 23 2.36 7.3 174 68 MBh 35.8 36.5 38.2 S/T 0.93 0.90 0.81 Delta T 23 22 21 1350 KW 2.20 2.26 2.34 AMPS 6.9 7.0 7.3 HI PR 150 162 171 LO PR 64 68 74 MBh 35.4 36.1 37.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC42A2A / CCA42T*A 65 IDB* Airflow 1575 1450 1225 59 39.2 0.72 17 2.34 10.2 141 61 38.8 0.71 17 2.34 10.2 141 61 35.8 0.68 18 2.28 9.9 137 59 63 40.6 0.60 14 2.40 10.5 152 65 40.2 0.59 15 2.39 10.5 152 65 37.1 0.57 16 2.33 10.2 147 63 67 44.5 0.42 11 2.49 10.8 161 71 44.0 0.41 11 2.48 10.8 160 71 40.6 0.40 12 2.41 10.5 155 68 MBh 39.8 41.0 44.4 S/T 0.82 0.74 0.56 Delta T 19 18 14 1575 KW 2.37 2.42 2.51 AMPS 10.3 10.6 10.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC42A2A / CCA42T*A 65 IDB* Airflow 71 47.3 0.51 14 2.62 11.5 171 77 46.8 0.50 15 2.62 11.4 170 77 43.2 0.49 16 2.55 11.1 165 74 59 39.6 0.93 22 2.60 11.3 162 66 39.2 0.92 23 2.59 11.3 161 66 36.2 0.88 24 2.52 10.9 157 64 63 40.4 0.88 21 2.66 11.6 174 70 40.0 0.86 22 2.65 11.5 174 70 37.0 0.83 23 2.58 11.2 168 68 MBh 41.2 42.0 44.0 S/T 0.94 0.91 0.82 Delta T 23 22 21 1575 KW 2.41 2.47 2.56 AMPS 10.5 10.8 11.1 HI PR 146 157 166 LO PR 63 67 73 MBh 40.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A2A / CCA48T*A 65 IDB* Airflow 1800 1600 1400 59 47.1 0.72 17 2.92 15.6 138 61 45.7 0.69 18 2.90 15.4 137 61 42.2 0.67 18 2.82 15.0 132 59 63 48.8 0.60 15 2.99 15.9 148 65 47.4 0.58 16 2.96 15.8 147 65 43.8 0.56 16 2.89 15.4 143 63 67 53.5 0.42 11 3.09 16.5 157 71 51.9 0.40 12 3.06 16.3 155 71 47.9 0.38 12 2.98 15.9 150 68 MBh 47.9 49.3 53.4 S/T 0.82 0.74 0.56 Delta T 20 19 15 1800 KW 2.95 3.01 3.11 AMPS 15.7 16.1 16.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A2A / CCA48T*A 65 IDB* Airflow 71 56.9 0.51 15 3.25 17.4 167 77 55.3 0.49 16 3.22 17.2 165 77 51.0 0.47 16 3.14 16.7 160 74 59 47.6 0.93 23 3.22 17.1 158 66 46.2 0.89 24 3.19 17.0 156 65 42.7 0.86 24 3.11 16.5 152 63 63 48.7 0.88 22 3.29 17.5 170 70 47.3 0.84 23 3.26 17.4 168 70 43.6 0.81 23 3.18 16.9 163 68 MBh 49.6 50.6 53.0 S/T 0.95 0.91 0.82 Delta T 24 24 22 1800 KW 3.00 3.06 3.17 AMPS 16.0 16.4 16.9 HI PR 142 153 161 LO PR 63 67 73 MBh 48.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A3A / CCA48T*A 65 IDB* Airflow 1800 1600 1400 59 47.6 0.72 18 2.95 8.9 138 62 46.2 0.69 18 2.93 8.8 137 61 42.7 0.67 19 2.85 8.6 133 60 63 49.4 0.60 15 3.02 9.1 149 66 47.9 0.58 16 2.99 9.0 147 65 44.2 0.56 16 2.91 8.8 143 63 67 54.1 0.42 12 3.12 9.4 157 72 52.5 0.40 12 3.09 9.3 156 71 48.5 0.38 12 3.01 9.1 151 69 MBh 48.4 49.9 54.0 S/T 0.82 0.74 0.56 Delta T 20 19 15 1800 KW 2.98 3.04 3.15 AMPS 9.0 9.2 9.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A3A / CCA48T*A 65 IDB* Airflow 71 57.5 0.51 15 3.28 9.8 167 78 55.8 0.49 16 3.26 9.7 166 78 51.5 0.47 16 3.17 9.5 161 75 59 48.1 0.93 23 3.25 9.7 159 67 46.7 0.89 24 3.22 9.6 157 66 43.1 0.86 24 3.14 9.4 152 64 63 49.2 0.88 22 3.32 9.9 171 71 47.8 0.84 23 3.30 9.8 169 70 44.1 0.81 23 3.21 9.6 164 68 MBh 50.2 51.1 53.5 S/T 0.95 0.91 0.82 Delta T 24 24 23 1800 KW 3.03 3.10 3.20 AMPS 9.1 9.3 9.6 HI PR 143 154 162 LO PR 64 68 74 MBh 48.7 49.6 52.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A2A / CCA60T*A 65 IDB* Airflow 2250 1850 1750 59 58.7 0.71 17 3.68 15.9 140 60 56.7 0.67 19 3.61 15.6 137 59 55.9 0.65 19 3.56 15.3 135 58 63 60.9 0.60 15 3.76 16.2 151 64 58.8 0.56 16 3.70 15.9 148 62 57.9 0.54 16 3.64 15.7 145 61 67 66.7 0.41 11 3.89 16.8 159 70 64.4 0.39 12 3.83 16.5 156 68 63.5 0.37 12 3.77 16.2 153 67 MBh 59.7 61.5 66.6 S/T 0.81 0.72 0.55 Delta T 20 18 15 2250 KW 3.71 3.80 3.93 AMPS 16.0 16.4 16.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A2A / CCA60T*A 65 IDB* Airflow 71 70.9 0.51 15 4.10 17.7 169 76 68.5 0.48 16 4.03 17.4 166 74 67.5 0.46 16 3.97 17.1 163 73 59 59.4 0.92 22 4.06 17.4 160 65 57.4 0.87 25 3.99 17.1 157 63 56.5 0.84 25 3.93 16.9 154 62 63 60.7 0.86 21 4.16 17.8 172 69 58.6 0.81 24 4.09 17.5 169 67 57.7 0.78 24 4.02 17.3 166 66 MBh 61.8 63.0 66.0 S/T 0.93 0.90 0.81 Delta T 24 23 22 2250 KW 3.77 3.86 4.00 AMPS 16.3 16.7 17.2 HI PR 144 155 164 LO PR 62 66 72 MBh 59.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A3A / CCA60T*A 65 IDB* Airflow 2250 1800 1750 59 57.9 0.71 17 3.63 11.3 140 60 55.9 0.67 19 3.57 11.1 137 59 55.4 0.66 19 3.53 11.0 135 58 63 60.0 0.60 15 3.72 11.6 150 64 58.0 0.56 17 3.65 11.4 147 62 57.4 0.55 17 3.61 11.3 146 61 67 65.7 0.41 11 3.84 11.9 159 69 63.5 0.39 13 3.78 11.7 156 68 62.9 0.38 13 3.73 11.6 154 67 MBh 58.9 60.6 65.6 S/T 0.81 0.72 0.55 Delta T 19 18 15 2250 KW 3.66 3.75 3.88 AMPS 11.4 11.7 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A3A / CCA60T*A 65 IDB* Airflow 71 69.9 0.51 14 4.05 12.6 169 75 67.6 0.48 16 3.98 12.3 166 74 66.9 0.47 17 3.94 12.2 164 73 59 58.5 0.92 22 4.01 12.4 160 64 56.6 0.87 25 3.94 12.2 157 63 56.0 0.86 25 3.89 12.0 155 62 63 59.8 0.86 21 4.11 12.7 172 68 57.8 0.81 24 4.03 12.5 169 67 57.2 0.80 24 3.99 12.3 167 66 MBh 61.0 62.2 65.1 S/T 0.93 0.90 0.81 Delta T 23 23 22 2250 KW 3.73 3.82 3.95 AMPS 11.6 11.9 12.2 HI PR 144 155 164 LO PR 62 65 71 MBh 58.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC18A2B / CHA18T*C 65 IDB* 75 Outdoor Am bie nt Te m pe rature 85 95 Ente ring Indoor We t Bulb Te m pe rature 59 63 67 71 59 63 67 71 17.9 18.6 20.4 17.5 18.1 19.9 0.74 0.62 0.43 0.76 0.63 0.44 18 16 12 18 16 12 1.40 1.43 1.48 1.48 1.51 1.57 5.6 5.7 5.9 6.0 6.1 6.3 180 193 204 205 220 233 68 73 79 72 76 83 - 59 16.6 0.79 18 1.54 6.4 230 75 63 17.2 0.66 15 1.58 6.5 248 80 67 18.9 0.46 12 1.64 6.7 262 87 71 - 59 15.4 0.80 17 1.60 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC18A2B / CHA18T*C 65 IDB* 85 Outdoor Am bie nt Te m pe rature 85 95 Ente ring Indoor We t Bulb Te m pe rature 63 67 71 59 63 67 71 105 115 129 Rev. 3 59 63 67 71 59 63 67 71 59 59 63 67 71 59 63 67 71 675 MBh S/T Delta T KW AMPS HI PR LO PR 19.5 0.86 23 1.23 4.9 144 63 19.9 0.81 22 1.26 5.0 155 67 21.3 0.66 19 1.30 5.1 163 74 22.7 0.49 15 1.35 5.3 170 78 19.0 0.90 23 1.33 5.3 161 67 19.4 0.84 22 1.36 5.4 174 71 20.8 0.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC24A2B / CHA30T*C 65 IDB* Airflow 900 800 700 59 23.1 0.73 17 1.53 6.3 150 61 22.5 0.70 18 1.52 6.3 148 61 20.7 0.67 18 1.48 6.1 144 59 63 24.0 0.61 15 1.57 6.5 161 65 23.3 0.58 16 1.56 6.4 160 65 21.5 0.56 16 1.51 6.2 155 63 67 26.3 0.42 11 1.63 6.7 170 71 25.5 0.40 12 1.61 6.6 169 71 23.5 0.39 12 1.57 6.5 164 68 MBh 23.5 24.2 26.2 S/T 0.83 0.75 0.56 Delta T 20 18 15 900 KW 1.55 1.58 1.64 AMPS 6.4 6.5 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC24A2B / CHA30T*C 65 IDB* Airflow 71 27.9 0.52 15 1.72 7.1 181 77 27.1 0.50 16 1.70 7.0 179 77 25.0 0.48 16 1.66 6.8 174 74 59 23.4 0.95 23 1.70 7.0 172 66 22.7 0.90 24 1.68 6.9 170 65 21.0 0.87 24 1.64 6.7 165 63 63 23.9 0.89 22 1.74 7.1 185 70 23.2 0.85 23 1.72 7.1 183 70 21.4 0.82 23 1.68 6.9 177 68 MBh 24.4 24.8 26.0 S/T 0.96 0.92 0.83 Delta T 24 23 22 900 KW 1.58 1.61 1.67 AMPS 6.5 6.7 6.9 HI PR 154 166 175 LO PR 63 67 73 MBh 23.6 24.1 25.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC30A2B / CHA30T*C 65 IDB* Airflow 1125 1000 875 59 27.6 0.74 17 1.77 7.2 155 61 26.8 0.71 17 1.75 7.1 153 61 24.8 0.68 18 1.70 6.9 148 59 63 28.6 0.62 15 1.81 7.4 166 65 27.8 0.59 15 1.79 7.3 165 65 25.7 0.57 15 1.74 7.1 160 63 67 31.4 0.43 11 1.88 7.6 176 71 30.5 0.41 11 1.86 7.5 174 71 28.1 0.40 12 1.81 7.3 169 68 MBh 28.1 28.9 31.3 S/T 0.84 0.76 0.57 Delta T 19 18 15 1125 KW 1.78 1.83 1.89 AMPS 7.3 7.4 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC30A2B / CHA30T*C 65 IDB* Airflow 71 33.4 0.53 14 1.98 8.1 187 77 32.4 0.50 15 1.97 8.0 185 77 29.9 0.49 15 1.91 7.8 180 74 59 27.9 0.96 22 1.96 7.9 177 66 27.1 0.92 23 1.94 7.9 175 65 25.0 0.88 23 1.89 7.6 170 63 63 28.5 0.90 21 2.01 8.1 191 70 27.7 0.86 22 1.99 8.1 189 70 25.6 0.83 22 1.94 7.8 183 68 MBh 29.1 29.7 31.1 S/T 0.97 0.94 0.85 Delta T 23 23 21 1125 KW 1.82 1.86 1.93 AMPS 7.4 7.6 7.8 HI PR 159 171 181 LO PR 63 67 73 MBh 28.3 28.8 30.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A2B / CHA36T*C 65 IDB* Airflow 1350 1200 1050 59 34.5 0.73 17 2.11 9.3 153 64 33.5 0.70 18 2.09 9.2 151 64 30.9 0.67 18 2.03 8.9 147 62 63 35.8 0.61 15 2.16 9.5 164 68 34.7 0.58 16 2.14 9.4 163 68 32.0 0.56 16 2.08 9.2 158 66 67 39.2 0.42 11 2.24 9.8 174 75 38.0 0.40 12 2.22 9.7 172 74 35.1 0.39 12 2.16 9.5 167 72 MBh 35.1 36.1 39.1 S/T 0.83 0.75 0.56 Delta T 20 18 15 1350 KW 2.13 2.18 2.26 AMPS 9.4 9.6 9.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A2B / CHA36T*C 65 IDB* Airflow 71 41.7 0.52 15 2.37 10.4 185 81 40.5 0.50 15 2.35 10.3 183 80 37.3 0.48 16 2.28 10.0 177 78 59 34.9 0.95 22 2.34 10.2 175 69 33.9 0.90 23 2.32 10.1 173 69 31.2 0.87 24 2.26 9.9 168 67 63 35.6 0.89 22 2.40 10.5 188 74 34.6 0.85 22 2.38 10.4 186 73 31.9 0.82 23 2.31 10.1 181 71 MBh 36.3 37.0 38.8 S/T 0.96 0.92 0.83 Delta T 24 23 22 1350 KW 2.17 2.22 2.31 AMPS 9.5 9.8 10.1 HI PR 157 169 179 LO PR 66 70 77 MBh 35.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A3B / CHA36T*C 65 IDB* Airflow 1350 1200 1050 59 34.5 0.73 17 2.11 6.3 153 64 33.5 0.70 18 2.09 6.2 151 64 30.9 0.67 18 2.03 6.0 147 62 63 35.8 0.61 15 2.16 6.4 164 68 34.7 0.58 16 2.14 6.3 163 68 32.0 0.56 16 2.08 6.2 158 66 67 39.2 0.42 11 2.24 6.6 174 75 38.0 0.40 12 2.22 6.6 172 74 35.1 0.39 12 2.16 6.4 167 72 MBh 35.1 36.1 39.1 S/T 0.83 0.75 0.56 Delta T 20 18 15 1350 KW 2.13 2.18 2.26 AMPS 6.3 6.5 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC36A3B / CHA36T*C 65 IDB* Airflow 71 41.7 0.52 15 2.37 7.0 185 81 40.5 0.50 15 2.35 6.9 183 80 37.3 0.48 16 2.28 6.7 177 78 59 34.9 0.95 22 2.34 6.9 175 69 33.9 0.90 23 2.32 6.8 173 69 31.2 0.87 24 2.26 6.6 168 67 63 35.6 0.89 22 2.40 7.1 188 74 34.6 0.85 22 2.38 7.0 186 73 31.9 0.82 23 2.31 6.8 181 71 MBh 36.3 37.0 38.8 S/T 0.96 0.92 0.83 Delta T 24 23 22 1350 KW 2.17 2.22 2.31 AMPS 6.4 6.6 6.8 HI PR 157 169 179 LO PR 66 70 77 MBh 35.3 35.9 37.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC42A2B / CHA42T*C 65 IDB* Airflow 1575 1400 1225 59 41.2 0.71 17 2.59 11.0 153 60 40.0 0.68 18 2.56 10.9 151 59 36.9 0.66 18 2.49 10.6 147 57 63 42.7 0.60 15 2.65 11.3 164 64 41.4 0.57 15 2.63 11.2 163 63 38.2 0.55 16 2.55 10.9 158 61 67 46.7 0.41 11 2.75 11.7 174 70 45.4 0.39 12 2.72 11.6 172 69 41.9 0.38 12 2.65 11.2 167 67 MBh 41.9 43.1 46.6 S/T 0.81 0.73 0.55 Delta T 20 18 15 1575 KW 2.61 2.68 2.77 AMPS 11.1 11.4 11.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC42A2B / CHA42T*C 65 IDB* Airflow 71 49.7 0.51 15 2.90 12.3 185 76 48.3 0.48 15 2.87 12.2 183 75 44.5 0.47 16 2.79 11.9 177 73 59 41.6 0.92 22 2.87 12.2 175 65 40.4 0.88 23 2.84 12.1 173 64 37.3 0.85 24 2.76 11.7 168 62 63 42.5 0.86 21 2.94 12.5 188 69 41.3 0.82 22 2.91 12.4 186 68 38.1 0.79 23 2.83 12.0 181 66 MBh 43.3 44.2 46.3 S/T 0.93 0.90 0.81 Delta T 24 23 22 1575 KW 2.66 2.73 2.82 AMPS 11.3 11.6 12.0 HI PR 157 169 179 LO PR 62 66 72 MBh 42.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A2B / CHA54T*C 65 IDB* Airflow 1800 1550 1400 59 46.1 0.71 17 2.96 12.7 147 61 44.7 0.68 18 2.93 12.6 145 61 44.0 0.66 19 2.89 12.4 143 60 63 47.7 0.60 15 3.03 13.0 158 65 46.3 0.57 16 3.00 12.8 156 65 45.7 0.55 16 2.96 12.7 154 63 67 52.3 0.41 11 3.14 13.4 167 71 50.8 0.39 12 3.11 13.3 165 71 50.0 0.38 12 3.06 13.1 162 69 MBh 46.8 48.2 52.2 S/T 0.81 0.73 0.55 Delta T 19 18 15 1800 KW 2.99 3.06 3.17 AMPS 12.8 13.1 13.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A2B / CHA54T*C 65 IDB* Airflow 71 55.6 0.51 14 3.32 14.1 178 77 54.0 0.48 15 3.28 14.0 176 77 53.2 0.47 16 3.23 13.8 173 75 59 46.6 0.92 22 3.28 13.9 168 66 45.2 0.88 24 3.25 13.8 166 65 44.5 0.85 25 3.20 13.6 164 64 63 47.6 0.86 21 3.36 14.2 181 70 46.2 0.82 23 3.33 14.1 179 70 45.5 0.79 24 3.28 13.9 176 68 MBh 48.5 49.4 51.8 S/T 0.93 0.90 0.81 Delta T 23 23 21 1800 KW 3.04 3.11 3.23 AMPS 13.0 13.3 13.7 HI PR 151 163 172 LO PR 63 67 73 MBh 47.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A3B / CHA54T*C 65 IDB* Airflow 1800 1550 1400 59 46.1 0.71 17 2.96 8.8 147 61 44.7 0.68 18 2.93 8.7 145 61 44.0 0.66 19 2.89 8.6 143 60 63 47.7 0.60 15 3.03 9.0 158 65 46.3 0.57 16 3.00 8.9 156 65 45.7 0.55 16 2.96 8.8 154 63 67 52.3 0.41 11 3.14 9.3 167 71 50.8 0.39 12 3.11 9.2 165 71 50.0 0.38 12 3.06 9.1 162 69 MBh 46.8 48.2 52.2 S/T 0.81 0.73 0.55 Delta T 19 18 15 1800 KW 2.99 3.06 3.17 AMPS 8.9 9.1 9.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC48A3B / CHA54T*C 65 IDB* Airflow 71 55.6 0.51 14 3.32 9.8 178 77 54.0 0.48 15 3.28 9.7 176 77 53.2 0.47 16 3.23 9.6 173 75 59 46.6 0.92 22 3.28 9.6 168 66 45.2 0.88 24 3.25 9.6 166 65 44.5 0.85 25 3.20 9.4 164 64 63 47.6 0.86 21 3.36 9.9 181 70 46.2 0.82 23 3.33 9.8 179 70 45.5 0.79 24 3.28 9.6 176 68 MBh 48.5 49.4 51.8 S/T 0.93 0.90 0.81 Delta T 23 23 21 1800 KW 3.04 3.11 3.23 AMPS 9.0 9.2 9.5 HI PR 151 163 172 LO PR 63 67 73 MBh 47.1 48.0 50.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A2B / CHA60T*C 65 IDB* Airflow 2250 1830 1750 59 59.6 0.71 17 3.78 15.9 156 61 57.6 0.67 19 3.71 15.6 152 60 57.0 0.66 20 3.66 15.5 151 59 63 61.7 0.60 15 3.87 16.3 167 65 59.7 0.56 17 3.80 16.0 164 64 59.1 0.55 17 3.75 15.8 162 63 67 67.7 0.41 11 4.01 16.8 177 71 65.4 0.39 13 3.94 16.5 173 70 64.7 0.38 13 3.89 16.3 171 69 MBh 60.6 62.4 67.5 S/T 0.81 0.72 0.55 Delta T 20 18 15 2250 KW 3.81 3.91 4.05 AMPS 16.1 16.5 17.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A2B / CHA60T*C 65 IDB* Airflow 71 72.0 0.51 15 4.25 17.8 188 77 69.5 0.48 17 4.17 17.5 184 76 68.8 0.47 17 4.12 17.3 182 75 59 60.2 0.92 23 4.20 17.5 178 66 58.2 0.87 25 4.12 17.2 175 65 57.6 0.86 26 4.07 17.0 172 64 63 61.5 0.86 22 4.30 18.0 192 70 59.5 0.81 24 4.22 17.6 188 69 58.9 0.80 25 4.17 17.4 185 68 MBh 62.7 64.0 67.0 S/T 0.93 0.90 0.81 Delta T 24 23 22 2250 KW 3.89 3.98 4.13 AMPS 16.4 16.8 17.3 HI PR 160 173 182 LO PR 63 67 73 MBh 60.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A3B / CHA60T*C 65 IDB* Airflow 2250 1830 1750 59 59.6 0.71 17 3.78 11.2 156 61 57.6 0.67 19 3.71 11.0 152 60 57.0 0.66 20 3.66 10.9 151 59 63 61.7 0.60 15 3.87 11.5 167 65 59.7 0.56 17 3.80 11.3 164 64 59.1 0.55 17 3.75 11.2 162 63 67 67.7 0.41 11 4.01 11.9 177 71 65.4 0.39 13 3.94 11.7 173 70 64.7 0.38 13 3.89 11.5 171 69 MBh 60.6 62.4 67.5 S/T 0.81 0.72 0.55 Delta T 20 18 15 2250 KW 3.81 3.91 4.05 AMPS 11.3 11.6 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCC60A3B / CHA60T*C 65 IDB* Airflow 71 72.0 0.51 15 4.25 12.5 188 77 69.5 0.48 17 4.17 12.3 184 76 68.8 0.47 17 4.12 12.1 182 75 59 60.2 0.92 23 4.20 12.3 178 66 58.2 0.87 25 4.12 12.1 175 65 57.6 0.86 26 4.07 12.0 172 64 63 61.5 0.86 22 4.30 12.6 192 70 59.5 0.81 24 4.22 12.4 188 69 58.9 0.80 25 4.17 12.3 185 68 MBh 62.7 64.0 67.0 S/T 0.93 0.90 0.81 Delta T 24 23 22 2250 KW 3.89 3.98 4.13 AMPS 11.5 11.8 12.2 HI PR 160 173 182 LO PR 63 67 73 MBh 60.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE24A2A / CHA24T*C 65 IDB* Airflow 900 800 700 59 23.9 0.71 17 1.33 5.9 134 61 23.2 0.68 18 1.32 5.8 132 61 21.4 0.66 18 1.28 5.7 128 59 63 24.8 0.60 15 1.36 6.0 144 65 24.1 0.57 16 1.35 6.0 142 65 22.2 0.55 16 1.31 5.8 138 63 67 27.2 0.41 11 1.41 6.2 152 71 26.4 0.39 12 1.40 6.2 150 71 24.3 0.38 12 1.36 6.0 146 68 MBh 24.3 25.0 27.1 S/T 0.81 0.73 0.55 Delta T 20 19 15 900 KW 1.34 1.38 1.42 AMPS 5.9 6.1 6.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE24A2A / CHA24T*C 65 IDB* Airflow 71 28.9 0.51 15 1.49 6.6 162 77 28.0 0.48 16 1.48 6.5 160 77 25.9 0.47 16 1.44 6.3 155 74 59 24.2 0.92 23 1.47 6.5 153 66 23.5 0.88 24 1.46 6.4 151 65 21.7 0.85 24 1.42 6.3 147 63 63 24.7 0.86 22 1.51 6.6 165 70 24.0 0.82 23 1.50 6.6 163 70 22.1 0.79 23 1.45 6.4 158 68 MBh 25.2 25.7 26.9 S/T 0.93 0.90 0.81 Delta T 24 24 22 900 KW 1.37 1.40 1.45 AMPS 6.1 6.2 6.4 HI PR 138 148 157 LO PR 63 67 73 MBh 24.4 24.9 26.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE30A2A / CHA30T*C 65 IDB* Airflow 1125 1000 875 59 28.2 0.73 17 1.58 7.1 137 62 27.4 0.70 18 1.57 7.0 136 61 25.3 0.67 18 1.53 6.8 132 60 63 29.3 0.61 15 1.62 7.2 148 66 28.4 0.58 15 1.61 7.2 146 65 26.2 0.56 16 1.56 7.0 142 63 67 32.0 0.42 11 1.68 7.5 156 72 31.1 0.40 12 1.67 7.4 154 71 28.7 0.39 12 1.62 7.2 150 69 MBh 28.7 29.5 32.0 S/T 0.83 0.75 0.56 Delta T 20 18 15 1125 KW 1.60 1.64 1.70 AMPS 7.1 7.3 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE30A2A / CHA30T*C 65 IDB* Airflow 71 34.1 0.52 15 1.78 7.9 166 78 33.1 0.50 15 1.76 7.8 164 78 30.5 0.48 15 1.71 7.6 159 75 59 28.5 0.95 22 1.76 7.8 157 67 27.7 0.90 23 1.74 7.7 156 66 25.6 0.87 23 1.69 7.5 151 64 63 29.2 0.89 21 1.80 8.0 169 71 28.3 0.85 22 1.78 7.9 167 70 26.1 0.82 22 1.73 7.7 162 68 MBh 29.7 30.3 31.7 S/T 0.96 0.92 0.83 Delta T 23 23 22 1125 KW 1.63 1.67 1.73 AMPS 7.2 7.4 7.7 HI PR 141 152 161 LO PR 64 68 74 MBh 28.9 29.4 30.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE36A2A / CHA36T*C 65 IDB* Airflow 1350 1200 1050 59 35.3 0.73 18 1.93 8.8 130 61 34.2 0.70 18 1.91 8.7 129 61 31.6 0.67 19 1.86 8.5 125 59 63 36.6 0.61 15 1.97 9.0 140 65 35.5 0.58 16 1.95 8.9 139 65 32.8 0.56 16 1.90 8.7 134 63 67 40.1 0.42 12 2.04 9.3 148 71 38.9 0.40 12 2.02 9.2 146 71 35.9 0.39 12 1.97 8.9 142 68 MBh 35.9 36.9 40.0 S/T 0.83 0.75 0.56 Delta T 20 19 15 1350 KW 1.94 1.99 2.05 AMPS 8.9 9.1 9.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE36A2A / CHA36T*C 65 IDB* Airflow 71 42.6 0.52 15 2.15 9.8 157 77 41.4 0.50 16 2.13 9.7 156 77 38.2 0.48 16 2.07 9.4 151 74 59 35.7 0.95 23 2.12 9.6 149 66 34.6 0.90 24 2.10 9.6 147 65 32.0 0.87 24 2.05 9.3 143 63 63 36.4 0.89 22 2.17 9.9 160 70 35.4 0.85 23 2.15 9.8 159 70 32.7 0.82 23 2.10 9.5 154 68 MBh 37.2 37.9 39.7 S/T 0.96 0.92 0.83 Delta T 24 24 23 1350 KW 1.98 2.02 2.09 AMPS 9.0 9.2 9.5 HI PR 134 144 152 LO PR 63 67 73 MBh 36.1 36.8 38.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE42A2A / CHA42T*C 65 IDB* Airflow 1575 1400 1225 59 39.2 0.74 17 2.17 9.9 132 61 38.1 0.71 18 2.15 9.8 131 61 35.1 0.68 18 2.10 9.5 127 59 63 40.6 0.62 15 2.22 10.1 142 65 39.4 0.59 15 2.20 10.0 140 65 36.4 0.57 16 2.14 9.7 136 63 67 44.5 0.43 11 2.30 10.4 150 71 43.2 0.41 12 2.28 10.3 148 71 39.9 0.40 12 2.22 10.1 144 68 MBh 39.9 41.0 44.4 S/T 0.84 0.76 0.57 Delta T 20 18 15 1575 KW 2.19 2.24 2.32 AMPS 10.0 10.2 10.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE42A2A / CHA42T*C 65 IDB* Airflow 71 47.3 0.53 15 2.42 11.0 159 77 46.0 0.50 15 2.40 10.9 158 77 42.4 0.49 15 2.34 10.6 153 74 59 39.6 0.96 22 2.40 10.9 151 66 38.5 0.92 23 2.38 10.8 149 65 35.5 0.88 24 2.31 10.5 145 63 63 40.5 0.90 21 2.46 11.1 162 70 39.3 0.86 22 2.43 11.0 161 70 36.3 0.83 23 2.37 10.7 156 68 MBh 41.3 42.1 44.1 S/T 0.97 0.94 0.85 Delta T 23 23 22 1575 KW 2.23 2.28 2.36 AMPS 10.1 10.4 10.7 HI PR 136 146 154 LO PR 63 67 73 MBh 40.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE48A2A / CHA54T*C 65 IDB* Airflow 1800 1600 1400 59 46.1 0.74 17 2.52 11.5 137 61 44.7 0.71 18 2.50 11.4 135 61 41.3 0.68 19 2.43 11.1 131 59 63 47.7 0.62 15 2.58 11.7 147 65 46.3 0.59 16 2.56 11.6 146 65 42.8 0.57 16 2.49 11.3 141 63 67 52.3 0.43 11 2.67 12.1 155 71 50.8 0.41 12 2.65 12.0 154 71 46.9 0.40 12 2.58 11.7 149 68 MBh 46.8 48.2 52.2 S/T 0.84 0.76 0.57 Delta T 20 19 15 1800 KW 2.54 2.61 2.70 AMPS 11.6 11.8 12.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE48A2A / CHA54T*C 65 IDB* Airflow 71 55.6 0.53 15 2.82 12.8 165 77 54.0 0.50 16 2.80 12.7 164 77 49.9 0.49 16 2.72 12.3 159 74 59 46.6 0.96 23 2.79 12.6 156 66 45.2 0.92 24 2.77 12.5 155 65 41.7 0.88 24 2.69 12.2 150 63 63 47.6 0.90 22 2.86 12.9 168 70 46.2 0.86 23 2.83 12.8 167 70 42.6 0.83 23 2.76 12.5 162 68 MBh 48.5 49.4 51.8 S/T 0.97 0.94 0.85 Delta T 24 24 22 1800 KW 2.59 2.65 2.75 AMPS 11.8 12.1 12.5 HI PR 141 152 160 LO PR 63 67 73 MBh 47.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE60A2A / CHA60T*C 65 IDB* Airflow 2250 1800 1750 59 58.1 0.74 18 3.31 15.0 140 61 56.1 0.70 20 3.25 14.7 138 60 55.6 0.69 20 3.21 14.5 136 59 63 60.2 0.62 15 3.39 15.4 151 65 58.2 0.58 17 3.33 15.1 148 64 57.6 0.58 17 3.29 14.9 146 63 67 66.0 0.43 12 3.51 15.9 160 71 63.7 0.40 13 3.45 15.6 156 70 63.1 0.40 13 3.41 15.4 154 69 MBh 59.1 60.8 65.8 S/T 0.84 0.76 0.57 Delta T 20 19 15 2250 KW 3.34 3.42 3.55 AMPS 15.1 15.5 16.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: RCE60A2A / CHA60T*C 65 IDB* Airflow 71 70.2 0.53 15 3.71 16.8 170 77 67.8 0.50 17 3.64 16.5 166 76 67.1 0.49 17 3.60 16.3 164 75 59 58.7 0.96 23 3.67 16.5 161 66 56.7 0.90 26 3.60 16.2 158 65 56.2 0.89 26 3.56 16.0 156 64 63 60.0 0.90 22 3.76 16.9 173 70 58.0 0.85 25 3.69 16.6 170 69 57.4 0.84 25 3.65 16.4 167 68 MBh 61.2 62.4 65.3 S/T 0.97 0.94 0.85 Delta T 24 24 23 2250 KW 3.40 3.49 3.61 AMPS 15.4 15.8 16.3 HI PR 145 156 164 LO PR 63 67 73 MBh 59.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA18B2A / CCA18F*C 65 IDB* Airflow 675 600 525 59 17.3 0.72 17 1.25 5.2 144 60 16.8 0.69 18 1.24 5.1 143 59 15.5 0.66 18 1.21 5.0 139 58 63 17.9 0.60 15 1.28 5.3 155 64 17.4 0.57 15 1.27 5.2 154 63 16.1 0.55 16 1.24 5.1 149 61 67 19.7 0.42 11 1.32 5.5 164 70 19.1 0.40 12 1.31 5.4 162 69 17.6 0.38 12 1.28 5.3 158 67 MBh 17.6 18.1 19.6 S/T 0.82 0.73 0.55 Delta T 20 18 15 675 KW 1.26 1.29 1.34 AMPS 5.2 5.3 5.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA18B2A / CCA18F*C 65 IDB* Airflow 71 20.9 0.51 15 1.40 5.8 175 76 20.3 0.49 15 1.38 5.7 173 75 18.7 0.47 15 1.35 5.6 168 73 59 17.5 0.93 22 1.38 5.7 165 65 17.0 0.89 23 1.37 5.6 164 64 15.7 0.85 23 1.33 5.5 159 62 63 17.9 0.87 21 1.41 5.8 178 69 17.4 0.83 22 1.40 5.8 176 68 16.0 0.80 22 1.36 5.6 171 66 MBh 18.2 18.6 19.5 S/T 0.94 0.91 0.82 Delta T 23 23 22 675 KW 1.28 1.31 1.36 AMPS 5.3 5.4 5.6 HI PR 149 160 169 LO PR 62 66 72 MBh 17.7 18.0 18.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA24B2A / CCA24F*C 65 IDB* Airflow 900 800 700 59 22.9 0.70 16 1.65 7.0 159 61 22.3 0.67 17 1.63 7.0 158 60 20.5 0.65 17 1.59 6.8 153 58 63 23.8 0.59 14 1.69 7.2 172 64 23.1 0.56 15 1.67 7.1 170 64 21.3 0.54 15 1.62 6.9 165 62 67 26.0 0.41 11 1.75 7.4 181 70 25.3 0.39 11 1.73 7.4 179 70 23.3 0.37 11 1.68 7.2 174 68 MBh 23.3 24.0 26.0 S/T 0.80 0.71 0.54 Delta T 19 18 14 900 KW 1.66 1.70 1.77 AMPS 7.1 7.3 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA24B2A / CCA24F*C 65 IDB* Airflow 71 27.7 0.50 14 1.85 7.9 193 76 26.9 0.48 15 1.83 7.8 191 76 24.8 0.46 15 1.78 7.6 185 73 59 23.2 0.91 22 1.83 7.8 183 65 22.5 0.87 22 1.81 7.7 181 65 20.8 0.84 23 1.76 7.5 175 63 63 23.7 0.85 21 1.87 7.9 196 69 23.0 0.81 21 1.86 7.9 194 69 21.2 0.78 22 1.80 7.7 189 67 MBh 24.1 24.6 25.8 S/T 0.92 0.89 0.80 Delta T 23 22 21 900 KW 1.69 1.73 1.80 AMPS 7.2 7.4 7.7 HI PR 164 177 187 LO PR 62 66 73 MBh 23.4 23.9 25.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA30B2A / CCA30F*C 65 IDB* Airflow 1125 1000 875 59 29.6 0.71 17 2.17 9.1 154 59 28.8 0.68 18 2.16 9.0 152 58 26.6 0.66 18 2.10 8.8 148 57 63 30.7 0.60 15 2.23 9.3 166 63 29.8 0.57 16 2.21 9.2 164 62 27.5 0.55 16 2.15 9.0 159 60 67 33.7 0.41 11 2.30 9.6 175 68 32.7 0.39 12 2.28 9.5 173 68 30.2 0.38 12 2.22 9.3 168 66 MBh 30.1 31.0 33.6 S/T 0.81 0.73 0.55 Delta T 20 18 15 1125 KW 2.19 2.25 2.32 AMPS 9.2 9.4 9.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA30B2A / CCA30F*C 65 IDB* Airflow 71 35.8 0.51 15 2.43 10.1 186 74 34.8 0.48 15 2.40 10.0 184 74 32.1 0.47 16 2.34 9.8 179 71 59 30.0 0.92 23 2.40 10.0 176 64 29.1 0.88 24 2.38 9.9 174 63 26.9 0.85 24 2.32 9.6 169 61 63 30.6 0.86 22 2.46 10.2 190 68 29.7 0.82 23 2.44 10.1 188 67 27.4 0.79 23 2.37 9.8 182 65 MBh 31.2 31.8 33.3 S/T 0.93 0.90 0.81 Delta T 24 23 22 1125 KW 2.23 2.29 2.36 AMPS 9.3 9.5 9.8 HI PR 159 171 180 LO PR 61 65 71 MBh 30.3 30.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA36B3A / CCA36F*C 65 IDB* Airflow 1350 1200 1050 59 33.5 0.73 17 2.41 7.3 144 58 32.6 0.70 17 2.39 7.2 142 58 30.0 0.67 18 2.33 7.0 138 56 63 34.8 0.61 14 2.47 7.4 155 62 33.7 0.58 15 2.45 7.4 153 62 31.1 0.56 15 2.38 7.2 149 60 67 38.1 0.42 11 2.55 7.6 163 68 37.0 0.40 11 2.53 7.6 162 67 34.1 0.39 12 2.46 7.4 157 65 MBh 34.1 35.1 38.0 S/T 0.83 0.75 0.56 Delta T 19 18 15 1350 KW 2.43 2.49 2.58 AMPS 7.3 7.5 7.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA36B3A / CCA36F*C 65 IDB* Airflow 71 40.5 0.52 14 2.69 8.0 174 74 39.3 0.50 15 2.67 8.0 172 73 36.3 0.48 15 2.60 7.8 167 71 59 33.9 0.95 22 2.66 7.9 165 63 32.9 0.90 23 2.64 7.9 163 62 30.4 0.87 23 2.57 7.7 158 61 63 34.6 0.89 21 2.73 8.1 177 67 33.6 0.85 22 2.70 8.0 175 66 31.0 0.82 22 2.63 7.8 170 64 MBh 35.3 36.0 37.7 S/T 0.96 0.92 0.83 Delta T 23 23 21 1350 KW 2.48 2.53 2.62 AMPS 7.5 7.6 7.8 HI PR 148 160 168 LO PR 60 64 70 MBh 34.3 34.9 36.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA42B2A / CCA48F*C 65 IDB* Airflow 1575 1400 1225 59 41.0 0.72 17 2.91 12.3 152 60 39.8 0.69 18 2.89 12.2 150 59 36.7 0.67 18 2.81 11.9 146 57 63 42.5 0.60 15 2.98 12.6 163 64 41.2 0.58 16 2.96 12.5 162 63 38.1 0.56 16 2.88 12.2 157 61 67 46.5 0.42 11 3.09 13.0 172 70 45.2 0.40 12 3.06 12.9 171 69 41.7 0.38 12 2.98 12.6 165 67 MBh 41.7 42.9 46.4 S/T 0.82 0.74 0.56 Delta T 20 18 15 1575 KW 2.94 3.01 3.12 AMPS 12.5 12.8 13.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA42B2A / CCA48F*C 65 IDB* Airflow 71 49.5 0.51 15 3.26 13.8 183 76 48.0 0.49 15 3.23 13.6 182 75 44.3 0.47 16 3.14 13.3 176 73 59 41.4 0.93 23 3.23 13.6 174 65 40.2 0.89 24 3.20 13.5 172 64 37.1 0.86 24 3.11 13.1 167 62 63 42.3 0.88 22 3.30 13.9 187 69 41.1 0.84 23 3.27 13.8 185 68 37.9 0.81 23 3.19 13.4 179 66 MBh 43.1 44.0 46.1 S/T 0.95 0.91 0.82 Delta T 24 23 22 1575 KW 2.99 3.07 3.18 AMPS 12.7 13.0 13.4 HI PR 156 168 178 LO PR 62 66 72 MBh 41.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA48B2A / CCA48F*C 65 IDB* Airflow 1800 1600 1400 59 46.2 0.71 17 3.25 13.9 154 56 44.8 0.68 18 3.23 13.8 152 56 41.4 0.66 18 3.14 13.4 148 54 63 47.9 0.60 15 3.33 14.2 166 60 46.5 0.57 15 3.30 14.1 164 59 42.9 0.55 15 3.21 13.7 159 58 67 52.4 0.41 11 3.45 14.7 175 65 50.9 0.39 12 3.42 14.6 173 65 47.0 0.38 12 3.33 14.2 168 63 MBh 47.0 48.4 52.3 S/T 0.81 0.73 0.55 Delta T 19 18 15 1800 KW 3.28 3.36 3.48 AMPS 14.0 14.4 14.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA48B2A / CCA48F*C 65 IDB* Airflow 71 55.8 0.51 14 3.64 15.5 186 71 54.2 0.48 15 3.61 15.4 184 70 50.0 0.47 15 3.51 15.0 179 68 59 46.7 0.92 22 3.60 15.3 176 61 45.3 0.88 23 3.57 15.2 174 60 41.8 0.85 23 3.47 14.8 169 58 63 47.7 0.86 21 3.69 15.7 190 65 46.3 0.82 22 3.66 15.5 188 64 42.8 0.79 22 3.56 15.1 182 62 MBh 48.6 49.6 51.9 S/T 0.93 0.90 0.81 Delta T 23 23 22 1800 KW 3.34 3.43 3.55 AMPS 14.3 14.6 15.1 HI PR 159 171 180 LO PR 58 62 67 MBh 47.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA60B2A / CCA60F*C 65 IDB* Airflow 2250 1900 1750 59 57.0 0.72 17 4.47 19.1 168 60 55.4 0.69 18 4.43 18.9 167 60 54.5 0.67 19 4.36 18.6 164 59 63 59.1 0.60 15 4.59 19.5 181 64 57.4 0.58 16 4.54 19.3 179 63 56.5 0.56 16 4.47 19.0 176 62 67 64.7 0.42 11 4.75 20.2 191 70 62.9 0.40 12 4.71 20.0 190 69 61.9 0.38 13 4.64 19.7 186 68 MBh 58.0 59.7 64.6 S/T 0.82 0.74 0.56 Delta T 19 18 15 2250 KW 4.52 4.63 4.80 AMPS 19.2 19.7 20.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA60B2A / CCA60F*C 65 IDB* Airflow 71 68.9 0.51 14 5.03 21.3 204 76 66.9 0.49 16 4.98 21.2 202 75 65.9 0.47 16 4.90 20.8 198 74 59 57.6 0.93 22 4.97 21.0 193 65 56.0 0.89 24 4.92 20.8 191 64 55.1 0.86 25 4.85 20.5 188 63 63 58.9 0.88 21 5.10 21.6 208 69 57.2 0.84 23 5.05 21.4 206 68 56.3 0.81 24 4.97 21.0 202 67 MBh 60.0 61.2 64.1 S/T 0.95 0.91 0.82 Delta T 23 23 22 2250 KW 4.60 4.72 4.89 AMPS 19.6 20.1 20.8 HI PR 174 187 197 LO PR 62 66 72 MBh 58.
Rev. 3 EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA60B3A / CCA60F*C 65 IDB* Airflow 2250 1900 1750 59 58.7 0.72 17 4.39 12.8 167 59 57.0 0.69 19 4.35 12.7 166 58 56.2 0.67 20 4.28 12.5 163 57 63 60.9 0.60 15 4.50 13.1 180 63 59.1 0.58 16 4.46 13.0 178 62 58.2 0.56 17 4.39 12.8 175 61 67 66.7 0.42 11 4.67 13.5 190 69 64.8 0.40 13 4.62 13.4 188 68 63.8 0.38 13 4.55 13.2 185 67 MBh 59.7 61.5 66.6 S/T 0.82 0.74 0.56 Delta T 20 18 15 2250 KW 4.44 4.54 4.71 AMPS 12.9 13.2 13.
EXPANDED PERFORMANCE DATA COOLING OPERATION MODEL: VCA60B3A / CCA60F*C 65 IDB* Airflow 71 70.9 0.51 15 4.93 14.3 202 75 68.9 0.49 16 4.89 14.2 200 74 67.8 0.47 17 4.81 14.0 197 73 59 59.4 0.93 23 4.88 14.1 191 64 57.7 0.89 25 4.83 14.0 190 63 56.8 0.86 26 4.76 13.8 186 62 63 60.7 0.88 22 5.00 14.4 206 68 58.9 0.84 24 4.95 14.3 204 67 58.0 0.81 25 4.88 14.1 201 66 MBh 61.9 63.1 66.0 S/T 0.95 0.91 0.82 Delta T 24 23 22 2250 KW 4.52 4.63 4.80 AMPS 13.2 13.5 13.9 HI PR 172 185 196 LO PR 61 65 71 MBh 60.
COOLING PERFORMANCE DATA PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (∆T). Low and high side pressures, power will not change. 2.
COOLING SCHEDULED PERFORMANCE MAINTENANCE DATA The owner should be made aware of the fact that, as with any mechanical equipment the remote air conditioner requires regularly scheduled maintenance to preserve high performance standards, prolong the service life of the equipment, and lessen the chances of costly failure. ONCE A YEAR 1. Clean the indoor and outdoor coils.
SERVICING TEST EQUIPMENT Proper test equipment for accurate diagnosis is as essential as regular hand tools. The following is a must for every service technician and service shop: 1. Thermocouple type temperature meter - measure dry bulb temperature. 2. Sling psychrometer- measure relative humidity and wet bulb temperature. 3. Amprobe - measure amperage and voltage. 4. Refrigeration test cord - check compressors, motors, and continuity testing.
SERVICING Pow er Failure Blow n Fuse Loose Connection Shorted or Broken Wires Open Overload Faulty Thermostat Faulty Transformer Shorted or Open Capacitor Internal Overload Open Shorted or Grounded Compressor Compressor Stuck Faulty Compressor Contactor Faulty Fan Relay Open Control Circuit Low Voltage Faulty Evap.
SERVICING S-1 CHECKING VOLTAGE WARNING S-2 CHECKING WIRING WARNING Disconnect Electrical Power Supply: Disconnect Electrical Power Supply: 1. Remove outer case, control panel cover, etc. from unit being tested. 1. Check wiring visually for signs of overheating, damaged insulation and loose connections. With power ON: 2. Use an ohmmeter to check continuity of any suspected open wires. WARNING LINE VOLTAGE NOW PRESENT 3.
SERVICING Resistance Heaters 1. Set room thermostat to a higher setting than room temperature so both stages call for heat. 2. With voltmeter, check for 24 volts at each heater relay. 3. No voltage, indicates the trouble is in the thermostat or wiring. WARNING Disconnect Electrical Power Supply: 1. Remove control panel cover or etc. to gain access to transformer. With power ON: 4. Check the continuity of the thermostat and wiring. Repair or replace as necessary.
SERVICING S-6 CHECKING TIME DELAY RELAY Time delay relays are used in some of the blower cabinets to improve efficiency by delaying the blower off time. Time delays are also used in electric heaters to sequence in multiple electric heaters. WARNING Disconnect Electrical Power Supply: 1. Tag and disconnect all wires from male spade connections of relay. 2. Using an ohmmeter, measure the resistance across terminals H1 and H2. Should read approximately 150 ohms. 3.
SERVICING 4 3 OHMMETER 2 5 1 TESTING FAN RELAY S-12 CHECKING HIGH PRESSURE CONTROL (some models) The high pressure control capillary senses the pressure in the compressor discharge line. If abnormally high condensing pressures develop, the contacts of the control open, breaking the control circuit before the compressor motor overloads. This control is manually reset. WARNING Disconnect Electrical Power Supply: 1. Using an ohmmeter, check across terminals of high pressure control, with wire removed.
SERVICING To prevent the compressor from starting and running backwards a Time Delay Relay (Cycle Protector) has been added to the low voltage circuit. K3 model scroll compressors equalize in less than one second after shut down and do not require a Time Delay Relay (Cycle Protector) for proper operation. ALL OTHER MODELS CAPACITOR, RUN A run capacitor is wired across the auxiliary and main windings of a single phase permanent split capacitor motor.
SERVICING S-15B Capacitance Check S-17 CHECKING COMPRESSOR WINDINGS Using a hookup as shown below, take the amperage and voltage readings and use them in the formula: Capacitance (MFD) = 2650 X Amperage Voltage WARNING DISCHARGE CAPACITOR THROUGH A 20 TO 30 OHM RESISTOR BEFORE HANDLING.
SERVICING WARNING Disconnect Electrical Power Supply: 1. Remove the leads from the compressor terminals. HI-POT WARNING SEE WARNING S-17 PAGE 44 BEFORE REMOVING COMPRESSOR TERMINAL COVER. 2. Using an ohmmeter, test continuity between terminals S-R, C-R, and C-S, on single phase units or terminals T2, T2 and T3, on 3 phase units. COMPRESSOR GROUND TEST 3.
SERVICING Compressor Serial Number Identification COPELAND COMPRESSOR . E 93 J 123456 Motor Shift Year Month Serial No. TECUMSEH COMPRESSOR T: G 22 93C Month Day Year 123456 Serial No. BRISTOL COMPRESSOR 291 93 123456 Day of Year Year Serial No. S-18 TESTING CRANKCASE HEATER The crankcase heater must be energized a minimum of four (4) hours before the condensing unit is operated.
SERVICING Failures such as opens, shorts across the device, shorts to ground, shorts to power and leakage path to ground shall be sensed. The thermistor (or wire(s)) should be replaced for proper operation. If the LED indicates 6 flashes (system error) then the setup and configuration of the system should be checked. This error mode could indicate an abnormal operating condition such as a restricted inlet, blocked outlet, or possibly a leak in the unit or ductwork.
SERVICING 3. Using an ohmmeter, test the element for continuity - no reading indicates the element is open. Replace as necessary. S-53 OUTDOOR TEMPERATURE CONTROL (OPTIONAL ITEM) Outdoor temperature controls (ODT or ATK) are not required to control the electric heat in BBA/BBC blower cabinets. Electric heater operation is controlled by the thermistor located in discharge airstream of the blower cabinet. See the "System Operation" section for additional information.
SERVICING 2. If the service dill valves are to be used for evacuation, it is recommended that a core remover be used to lift the core for greater efficiency. 1. When using an ambient compensated calibrated charging cylinder, allow only liquid refrigerant to enter the high side. 3. Start the vacuum pump and open the shut off valve to the high vacuum gauge manifold only. After the compound gauge (low side) has dropped to approximately 29 inches of vacuum, open the valve to the vacuum thermocouple gauge.
SERVICING S-105 THERMOSTATIC EXPANSION VALVE S-107 UNDERFEEDING The expansion valve is designed to control the rate of liquid refrigerant flow into an evaporator coil in exact proportion to the rate of evaporation of the refrigerant in the coil. The amount of refrigerant entering the coil is regulated since the valve responds to temperature of the refrigerant gas leaving the coil (feeler bulb contact) and the pressure of the refrigerant in the coil.
SERVICING On systems using capillary tubes or flow control restrictors, superheat is adjusted in accordance with the "DESIRED SUPERHEAT vs. OUTDOOR TEMP" chart as explained in section S-103 CHARGING a. Liquid Line Pressure = 260 b. Corresponding Temp. °F. = 120° c. Thermometer on Liquid line = 105°F. To obtain the amount of subcooling subtract 105 from 120°F.
SERVICING S-111 CAPILLARY TUBES TEMPERATURE - PRESSURE (R-22) The capillary tubes used in conjunction with the indoor and outdoor coil, are a predetermined length and bore (I.D.). Temp. °F. Gauge Pressure (PSIG) Freon-22 Temp. °F. Gauge Pressure (PSIG) Freon-22 They are designed to control the rate of liquid refrigerant flow into an evaporator coil.
SERVICING S-113 OVERCHARGE OF REFRIGERANT An overcharge of refrigerant is normally indicated by an excessively high head pressure. An evaporator coil, using an expansion valve metering device, will basically modulate and control a flooded evaporator and prevent liquid return to the compressor. An evaporator coil, using a capillary tube metering device, could allow refrigerant to return to the compressor under extreme overcharge conditions.
SERVICING The maximum recommended length of tubing to be used with a remote cooling system is 50 feet; this includes a minimum of turns with a maximum permissible rise of 20 feet for the liquid line. 1. Sketch the system and determine the number of traps required. Traps are required only if the condensing unit is above the evaporator coil. Traps are only necessary in the suction line. 1. All horizontal suction line runs must be pitched towards the compressor (one inch per ten feet).
SERVICING LIQUID LINE SIZING CONDENSING UNIT ABOVE EVAPORATOR Additional refrigerant will be 65 feet of 1/2" line = 1.3 x 65 feet = 85 oz. EFFECTIVE LENGTH 50 75 100 125 150 18 3/8 3/8 3/8 3/8 3/8 24 3/8 3/8 3/8 3/8 3/8 70 oz. charge will need to be added to the system. 30 3/8 3/8 3/8 3/8 3/8 36 3/8 3/8 3/8 3/8 3/8 6. Check the system nameplate.
SERVICING S-201 AIR HANDLER EXTERNAL STATIC 1. Using a draft gauge (inclined manometer) measure the static pressure of the return duct at the inlet of the unit, (Negative Pressure). 2. Measure the static pressure of the supply duct, (Positive Pressure). 3. Add the two readings together. NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired. 4. Consult proper table for quantity of air.
SERVICING REFRIGERANT LINE SIZING Known Factors: 1. RCC48A2A and CCA48TUA coil. Evaporator above Condenser. 2. Liquid Line 65 linear feet w/ 8 short radius elbows, and 30 ft. vertical lift. 3. Suction Line 65 linear feet w/ 8 long radius elbows. Determine Suction and Liquid Line sizes: Procedures: A. Measure length of suction line. (65 ft.) B. Count the number of suction line elbows. (8 long radius) 2' C. Calculate the equivalent length of fittings using the Fitting Losses in Equivalent Feet Chart.
SERVICING REFRIGERANT LINE SIZING Known Factors: 1. RCC36A2A and matching "A" coil. Condenser above Evaporator. 2. Liquid Line 72 linear feet w/ 9 long radius elbows 3. Suction Line 72 linear feet, and 43 ft. vertical lift. Determine Suction and Liquid Line sizes: Procedures: A. Measure length of suction line. (72 ft.) B. Measure the vertical lift of the suction line (43'). Using the Suction Line Traps Chart determine the number of traps required in the suction line (3).
WIRING DIAGRAMS BDK01A BLOWER DELAY KIT INSTALLED IN THIS FURNACE. DOOR SWITCH BK -6 GY-38 BK -20 PARK P P PARK HEAT HEAT FURNACE CONTROL COOL COOL LINE XFMR XFMR INDR HOT 120VAC VAC HOT 120 VAC. LINE INDR IGNR IGNR TO BLOWER MOTOR (COOLING SPEED) LINE NEUTRAL CIRC INDC NEUTRAL IGNC XFMR C Y G W R NOTE: BLOWER DELAY RELAY MAINTAINS POWER TO BLOWER MOTOR FOR 30-65 SECONDS AFTER COMPLETION OF COOLING CYCLE.
Y C/X T1 L1 CAP C CC F H GND R S OD FAN CC C COMP WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING. T2 L2 BK 27 YL 12 BR 11 CAPACITOR COM BK1 SEE NOTE 5 YL1 VT 20 VT 20 T2 L2 L1 T1 BK 14 RD 10 WIRING DIAGRAMS RD10 BK 15 CONTACTOR (CC) GND FIELD CONNECTIONS 1í POWER SEE NOTES 1&6 WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING.
Y C/X T3 CC3 L3 T2 CAP C R C COMP 3ø S R OD FAN CC2 L2 S L1 T1 CC CC1 INTERNAL CRANKCASE HEATER GND WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING.
Y C/X T1 L1 R1 LPC HPC SCP R2 F H Y1 1 R S OD FAN 2 C COMP START RELAY START CAP C CAP CC CRKC HTR GRD DISCH STAT WARNING 5 CC T2 L2 BK 27 BR 11 YL 8 YL 12 1 VT 20 T2 L1 T1 RD 10 L2 VT 20 OR 5 START RELAY RD10 5 2 OR 5 RD10 YL1 SEE NOTE 5 BK1 SEE NOTE 4 CONTACTOR (CC) YL 1 8 8. CRANKCASE HEATER WIRES GOING FROM COMPRESSOR TO CONTACTOR MAY NOT BE IDENTIFIED AS BK14 AND BK15.
Rev. 3 Y C/X T1 L1 R1 C CAP CC LPC HPC R2 SCP F H Y1 CRKC HTR GRD R S OD FAN C COMP DISCH STAT WARNING CC T2 L2 BK 27 BR 11 YL 8 BK1 BK1 VT 20 T2 L1 T1 VT 20 L2 YL 1 8 8. CRANKCASE HEATER WIRES GOING FROM COMPRESSOR TO CONTACTOR MAY NOT BE IDENTIFIED AS BK14 AND BK15. NOTE: READ THE FOLLOWING NOTES BEFORE OPERATING OR SERVICING THIS UNIT. 1. AMANA APPROVED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 2.
Y C/X T1 L1 R1 CAP C PTCR CC LPC HPC R2 SCP F H Y1 CRKC HTR GRD R S OD FAN C COMP DISCH STAT WARNING CC T2 L2 BK 27 YL 12 PTCR START 8 BK1 BK1 YL BR 11 RD10 RD10 BK1 YL1 BK 15 SEE NOTE 5 SEE NOTE 4 CONTACTOR (CC) T1 RD 10 T2 L1 VT 20 L2 YL 1 8 8. CRANKCASE HEATER WIRES GOING FROM COMPRESSOR TO CONTACTOR MAY NOT BE IDENTIFIED AS BK14 AND BK15.
Rev. 3 Y C/X T1 L1 R1 CAP C CC LPC HPC SCP R2 H F Y1 START CAP R S OD FAN 2 C COMP 1 START RELAY INTERNAL CRANKCASE HEATER 5 GND WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING.
Y C/X T1 L1 R1 CAP C CC LPC HPC SCP R2 F H Y1 R S OD FAN C COMP GND WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING. CC T2 L2 BK 27 BR 11 RD10 Y1 YL 1 RD 10 VT 20 SHORT CYCLE PROTECTOR (SCP) L1 T1 VT20 VT20 T2 L2 Y2 GND R1 R2 BK 1 WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING.
Y C/X T3 R1 CC3 L3 LPC HPC SCP R2 T2 Y1 C R C COMP 3ø S R OD FAN CAP S L1 T1 CC CC1 INTERNAL CRANKCASE HEATER CC2 L2 GND WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING. BK 27 BR 11 CAPACITOR RD 10 YL 12 T1 VT VT 20 20 YL 1 BK 1 SHORT Y1 R1 CYCLE Y2 R2 PROTECTOR (SCP) SEE NOTE 5 T2 L1 YL 1 T3 L2 BK 1 L3 BK 14 GND RCC36-60A3A/B BU YL VT20 BK27 BR11 YL12 VT20 RD10 BK15 HIGH PRESS.
Y C/X T3 R1 CC3 L3 LPC HPC SCP R2 Y1 T2 CAP C R C COMP 3ø S R OD FAN CC2 L2 S L1 T1 CC CC1 GND WARNING: WIRING TO UNIT MUST BE PROPERLY POLARIZED (AS APPLICABLE) AND GROUNDED. DISCONNECT POWER BEFORE SERVICING.
Rev. 3 WIRING DIAGRAMS BHAxxF / BCAxxTA WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS EHK05A (4.8KW HEATER KIT) w/ BHA-FA or BCA-TA 211 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS EHK07A (7.2KW HEATER KIT) or EHK10A (9.6KW HEATER KIT) w/ BHA-FA or BCA-TA WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS EHK15A (14.4KW HEATER KIT) w/ BHA-FA or BCA-TA 213 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS EHK20A (19.2KW HEATER KIT) w/ BHA-FA or BCA-TA WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS EHK25A (24.0KW HEATER KIT) w/ BHA-FA or BCA-TA 215 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS EHK30A (28.8KW HEATER KIT) w/ BHA-FA or BCA-TA WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBA24-60A2A 217 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev.
WIRING DIAGRAMS BBA w/DSK02A 219 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/EHK05B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/EHK05B/C 221 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/EHK07/10B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/EHK07/10B/C 223 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/EHK15B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/EHK15B/C 225 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/EHK20B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/EHK20B/C 227 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/EHK25B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/EHK25B/C 229 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/EHK30B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/EHK30B/C 231 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/ECB05B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/ECB05B/C 233 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/ECB07/10B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/ECB07/10B/C 235 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/ECB15B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/ECB15B/C 237 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/ECB20B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/ECB20B/C 239 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/ECB25B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/ECB25B/C 241 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
Rev. 3 WIRING DIAGRAMS BBA w/ECB30B/C WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .
WIRING DIAGRAMS BBC w/ECB30B/C 243 Rev. 3 WARNING TO AVO ID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCO NNECT THE POW ER BEFORE SERVICING .