Specifications

9
SPECIFICATIONS
NOTES:
1. All 265V models must use Amana
®
brand’s subbase (PTSB4**E) or an Amana
®
brand hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included
and factory installed on Amana
®
brand all 265 volt chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09*B*AE.
7. Please specify 2-digit heater kW size to complete model number.
9. Refrigerant used in all systems is R-22.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*B*AE.
10. All units meet or exceed ASHRAE 90.1 standards..
PTC073B***
E - Y
PTC074B***
E - Y
PTC093B***
E - Y
PTC094B***
E - Y
PTC123B***
E - Y
PTC124B***
E - Y
PTC153B***
E - Y
PTC154B***
E - Y
Voltage
1&3
230/208 265 230/208 265 230/208 265 230/208 265
Capacity (BUTH) 7,100/6,900 7,100 9,100/8,900 9,100 12,000 /11,900 12,000 14,000/13,900 14,000
Amps 2.8/3.0 2 3.7/3.8 3 4.6 /5.0 4.3 6.3/6.9 5.9
Watts 610/595 610 790/775 790 1,110 /1,100 1,130 1,470/1,450 1,470
EER 11.6 11.6 11.5 11.5 10.8 10.8 9.5 9.5
UNIT WITHOUT
ELECTRIC HEATER
Minimum Circuit Ampacity
2&4
4.0 3.6 5.1 4.4 6.4 5.7 8.8 7.7
CFM
HI GH 245/ 240 245 245/240 245 325/315 325 325/315 325
LOW 220/205 220 220/205 220 250/229 250 250/220 250
HI GH 265/ 260 265 265/260 265 345/335 345 345/335 345
LOW 230/215 230 230/215 230 265/235 265 265/235 265
COMPRESSOR & FAN* 65 65 65 65 70 70 70 70
Dehumidification
(pints/hr)
1.6 1.6 2.6 2.6 3.5 3.5 4.4 4.4
Net Weight 90 90 95 95 105 105 110 110
Shipping Weight
(approx. lbs.)
105 105 110 110 120 120 125 125
Cool, Wet Coil
COOLING DATA (COOLING with ELECTRIC HEAT)
Ventilated Air
Dr y Coil
PTH073B***
E - Y
PTH074B***
E - Y
PTH093B***
E - Y
PTH094B***
E - Y
PTH123B***
E - Y
PTH124B***
E - Y
PTH153B***
E - Y
PTH154B***
E - Y
Voltage
1&3
230/208 265 230/208 265 230/208 265 230/208 265
Capacity (BUTH) 7,000/6,800 7,000 9,100/8,900 9,100 12,000 /11,800 12,000 14,000/13,900 14,000
Amps 2.8/3.0 2 3.5/3.8 3 4.6 /5.0 4.3 6.3/6.9 5.9
Watts 605/585 605 790/775 790 1,110/1,090 1,110 1,5 05/1,495 1,505
EER 11.6 11.6 11.5 11.5 10.8 10.8 9.3 9.3
UNIT WITHOUT
ELECTRIC HEATER
Minimum Circuit Ampacity
2&4
4.0 3.6 5.1 4.4 6.4 5.7 8.8 7.7
CFM
HI GH 245/ 240 245 245/240 245 325/315 325 325/315 325
LOW 220/205 220 220/205 220 250/229 250 250/220 250
HI GH 265/ 260 265 265/260 265 345/335 345 345/335 345
LOW 230/215 230 230/215 230 265/235 265 265/235 265
COM PR ESSOR & FAN* 65 65 65 65 70 70 70 70
Dehumidification
(pints/hr)
1.6 1.6 2.6 2.6 3.5 3.5 4.4 4.4
Net Weight 95 95 100 100 110 110 115 115
Shipping Weight
(approx. lbs.)
110 110 115 115 125 125 130 130
Cool, Wet Coil
COOLING DATA (COOLING with ELECTRIC HEAT)
Ventilated Air
Dr y Coil
*Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions.