Installation Instruction
5
Configuration Settings
The PTAC control will need to be configured to work with the wall thermostat (DS01A Kit) if installed. The PTAC
control will automatically self-configure to activate pre-configured energy management routine when the DD01A is
installed and bound to the PTAC. Additionally, the setback times and setback temperatures can be changed using
the configuration settings. If you are using DP01A Front Desk Platform, the PTAC control will need to be configured
to identify its room number placement.
Standard and DS01A Configuration
To enter configuration feature mode:
Press and continue to hold the up and down arrow keys and quickly press the OFF key twice within
a two (2) second time frame. Once you are in the configuration program, you can use the HEAT button to move
UP the various configuration settings or the COOL button to move DOWN the configuration settings. The + or -
keys will move up or down the selectable codes that you can change for each configuration setting. Ensure that
you are in the proper configuration setting before pressing the + or - key as you may accidentally change a setting
that you did not intent to change.
The display will alternate between displaying the feature code and the option code 0 (factory default setting). The
lower right dot on the display will flash. If using a wireless wall thermostat (DS01A Kit), press the up and down
arrows until is displayed. NOTE: Use the to toggle between the configuration selected option code for
the C1 configuration setting.
Entering Room Number (Skip if not using DP01A Front Desk Platform)
1. The PTAC control can be set for a 4-digit room number. To select the first two digits (floor), press the HEAT
key until appears, then press the up down arrows to select the first two digits.
2. To select the last two digits of the room number, press the HEAT key until appears, then press the up
and down arrows to select the last 2 digits of the room number.
For example for Room “201”, press the HEAT key until appears, then press the up down arrows to
select “02”: = .
Next to select the last two digits of the room number, press the HEAT key until appears, then press the
up and down arrows to select “01”: = .
Setback Temps - DD01A
The DD01A and the DigiSmart control can be programmed for 3 different times to activate temperature setbacks. The
factory default temperature setbacks are 2º from set point in 30 minutes, 4º in three (3) hours, and 8º in eight (8) hours.
For each time, you can select a setback temperature. The amount of setback is the amount of degrees the control will
operate from guest’s setting in degrees F. If a change to the factory default temperature settings is desired, follow the
instructions below.