Packaged Terminal Air Conditioners and Heat Pumps with our DigiSmart® Control Board & EMS PTAC Specifications and Accessories Catalog First-Year Warranty: Parts & Labor on entire unit Second through Fifth Year: Parts & Labor on certain sealed system components Second through Fifth Year: on certain functional parts only * Complete warranty details available at www.amana-ptac.com. MC-DPTAC www.amana-ptac.
Standard Features • Energy Efficiencies: With EERs up to 11.7 and COPs up to 3.4, our unit’s high efficiencies may qualify you for many of the rebates offered by electrical power companies. • Quiet Operation: Our PTAC has been redesigned to be the quietest PTAC we’ve ever built. The unit’s state-of-the-art design and construction provide a quiet environment, allowing guests to enjoy peaceful, sleep-filled nights.
Standard Features (cont.) • Condensate Dispersion System: Our condensate dispersion system removes condensate from indoor cooling operation by throwing water directly on to the outdoor coil for rapid evaporation and increased cooling efficiencies. The slinger ring on the new, enhanced fan draws water up and into the fan blades. This water is then atomized and evaporated into the atmosphere through the condenser.
brings together our best PTAC ever with our best Energy Management Software and now integration with Property Management and Front Desk Management Software. Reduce PTAC energy consumption by 35% OR MORE* through the power of the in-unit Energy Management System, programmable temperature set-back and limits combined. Reduce PTAC maintenance cost through our automated maintenance notification system.
Enterprise — Multiple Wireless Controllers Central Monitoring and Control of Multiple Properties > > > > > Data Warehousing Savings Analysis Email Reporting Virtual Metering Load Shedding Web-Based, Real-Time Monitoring Amana® Brand DigiSmart™ Controller: All of the PTACs in the building can be managed through a single interface on a PC.
Nomenclature PTC 07 3 E 1,2,3 4 5 6 35 AXXX AA 7,8,9 10,11,12,13 14 Basic Model Type Engineering PTC Standard Cooler PTAC Major & Minor Revisions PTH Standard Heat Pump PTHP DRY Dehumid Cooler PTAC Features Code Cooling Capacity A Standard Model C Corrosion Protec>on (Seacoast) 07 7000BTU/h 60 Hz D Power Door 09 9000 BTU/h 60 Hz E Future Use 12 12000 BTU/h 60 Hz F Fuse Holder 15 1
Product Specifications: PTC Models — Cooling/Electric Heat (cont.) 230/208 Volts Model ¹, ⁶, ⁸, ⁹ Voltage ¹, ³ Capacity (BTU/h) Amps ¹⁰ Watts ¹⁰ EER PTC 073G***XXX 230 / 208 7,700 / 7,700 3.5 / 3.5 670/660 11.5/11.7 PTC 093G***XXX 230 / 208 9,000 / 9,000 4.1 / 4.1 805/785 11.2/11.5 PTC 123G***XXX 230 / 208 11,700 / 11,500 5.6 / 5.6 1135/1105 10.3/10.4 PTC 153G***XXX 230 / 208 15,000 / 14,700 7.0 / 7.0 1500/1470 10.0/10.0 4.2 290 264 310 282 65* 6* 1.7 98 113 4.9 290 264 310 282 65* 6* 2.2 102 117 6.
Product Specifications: PTH Models — Cooling/Heat Pump/Electric Heat 230208 Volts PTH 073E**AXXX Model ¹, ⁶, ⁸, ⁹ Voltage ¹, ³ Capacity (BTU/h) PTH 093E**AXXX PTH 123E**AXXX PTH 153E**AXXX 230 / 208 230 / 208 230 / 208 230 / 208 7,600 / 7,500 9,000 / 8,900 11,500 / 11,100 14,000 / 13,900 Amps ¹² 3.5 / 3.5 4.1 / 4.1 5.6 / 5.6 7.0 / 7.0 Watts ¹² 650 / 620 770 / 765 1095 / 1065 1460 / 1465 EER 11.3 / 11.4 11.1 / 11.1 10.2 / 10.1 9.6 / 9.5 Unit without Electric Heater Min.
Product Specifications: PTC / PTH Models — Electric Heat Performance (Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Configuration) Electric Heat (kW) No. of Stages 230/208V 2.5 230/208V 230/208V Voltage Nominal Heating (BTU/h) Total Watts6 Total Amps Min. Circuit Ampacity² MOP4 (amps) Power Cord @ 230V @ 208V @ 265V 1 8,500 6,800 -- 2,570 / 2,115 11.2 / 10.1 14.0 15 6-15 P 3.5 1 12,000 9,900 -- 3,570 / 2,935 15.5 / 14.1 19.
Accessories Custom Color Sleeves We offer over 150 different custom colors to choose from for your wall sleeves. In addition, we can custom paint the exterior a different color from the interior to meet your needs. Outdoor Grilles Available in stamped-aluminum or architecturally louvered for application with an Amana brand WS900D wall sleeve. AGK—Extruded aluminum architectural grille available with anodized aluminum finish and a baked-on paint finish for durability.
Accessories (cont.) Power Disconnect Switch The PSHW**A power disconnect switch can be used for 265-volt or 230/208-volt physical disconnect, where required by local codes. The switch is rated at 30amp capacity. The switch is for use with and Amana® brand standard sub-bases or PTPWHWK4 Hard Wire Kit. Fuse Holder Kit Cartridge-style fuses can be installed in the fuse holder for use in the sub-base or chassis. Available in 15, 20 and 30 amp (included on 265-volt unit).
Accessories (cont.) Security Key Locks In conjunction with the tamper-resistant front, the installation of Amana® brand security key locks prevents tampering of the controls used to set temperature, heating and cooling functions. UL approved for institutional use only. Power Door Kit Vent door will automatically open when unit fan is on. Thermostats The following thermostats offer remote control. Any thermostat other than those listed must be submitted to Goodman Company, L.P., for approval prior to use.
Accessories (cont.) Remote Temperature Sensor Unit can be wired to sense room temperature away from the PTAC to have accurate readings. RTS03 Remote wall-mounted sensor Wired Energy Management Control Includes PIR occupancy sensor power from the DigiSmart control and door switch; cannot be used with a remote wired thermostat.
Unit with Accessory Wall Sleeve and Sub-base Accessory Top View 42" 40" 6 - 1 / 8" 24 - 5 / 16" 1" 9 - 9 / 16" Location of external drain holes on bottom flange of Wall Sleeve Air Flow Air Flow Air Flow Control Door Air Discharge Grille 3 1" 3" Clearance to side walls " Front View 58” LCDI CORD SET — 230V/208V UNIT* 42" LEFT R I GHT 16-1/16" 2-5/8" Right View AIR DISCHARGE GRILLE IS REVERSIBLE TO PROVIDE EITHER 15° OR 40° DISCHARGE ANGLE 7/8" STAMPED GRILLE 21-1/2" 14-1/8" WALL SLEEVE
Framing for Accessory Wall Sleeve (WS9XX) Alternative Fastening Method (Field Supplied) Wood Screw Toggle Bolt Expansion Anchor Bolt Mounting Holes (Drilled by Installer) Plastic Anchor Screws Wall Sleeve must extend a minimum of ¼” beyond outside wall to allow for proper caulking.
Packaged Terminal Air Conditioners and Heat Pumps with Control Board 7-Button Control Pad • One-Touch Activation • Total Fan Control • Easy-to-Read Display First-Year Warranty: Parts & Labor on entire unit Second through Fifth Year: Parts & Labor on certain sealed system components Second through Fifth Year: on certain functional parts only * Complete warranty details available at www.amana-ptac.com.