Master Catalog

MC-DPTAC www.amana-ptac.com 7
Product SPecificationS: Ptc ModelS — cooling/electric Heat
230/208 Volts

,
,
PTC
073G***XXX
PTC
093G***XXX
PTC
123G***XXX
PTC
153G***XXX
Voltage ³
230 / 208 230 / 208 230 / 208 230 / 208
Capacity (BTU/h)
7,700 9,000 11,700 / 11,500 15,000 / 14,700
Amps
¹⁰
3.5 4.1 5.6 7.0
Was
¹⁰
670/660 805/785 1135/1105 1500/1470
EER
11.5 11.2/11.5 10.3/10.4 10.0/10.0

Min. Circuit Amps ²
,
,
¹⁰
4.2 4.9 6.8 8.5
CFM (Cool/Wet Coil)
High
290 290 290 340
Low
264 264 264 314
CFM (Dry Coil)
High
310 310 310 360
Low
282 282 282 332
Venlated Air, CFM (Fan Only)*
65* 65* 65* 65*
Dehumidicaon (Pints/Hr.)
1.7 2.2 3.6 4.4
Net Weight (lbs.)
98 102 102 113
Ship Weight (lbs.)
113 117 119 130
265/277 Volts


PTC
074G***XXX
PTC
094G***XXX
PTC
124G***XXX
PTC
154G***XXX
Voltage ¹
,
³
265 265 265 265
Capacity (BTU/h)
7,700 9,000 12,000 14,800
Amps
¹⁰
3.0 3.6 4.8 6.0
Was
¹⁰
670 795 1,165 1,480
EER
11.5 11.3 10.3 10.0

Min. Circuit Amps ²
,
,
¹⁰
3.6 4.4 5.9 7.4
CFM (Cool/Wet Coil)
High
290 290 290 340
Low
264 264 264 314
CFM (Dry Coil)
High
310 310 310 360
Low
282 282 282 332
Venlated Air, CFM (Fan Only)*
65* 65* 65* 65*
Dehumidicaon (Pints/Hr.)
1.7 2.2 3.6 4.4
Net Weight (lbs.)
98 102 102 113
Ship Weight (lbs.)
113 117 119 130
* Actual vent CFM performance will vary due to applicaon and installaon condions.

¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.
² Minimum Circuit Ampacity (MCA) rangs conform to the Naonal Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
Overcurrent protecon for all units without electric heaters is 15 amps. Overcurrent protecon on 265-volt models must be cartridge-style me-delay fuses (included and
factory-installed on all Amana® brand 265-volt chassis). See heater performance
Heang capacity and eciency based on unit operaon without condensate pump; unit automacally switches to electric heat at approximately 24°F outdoor ambient.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protecon. Amps and Was notaon refers to compressor only.