Master Catalog

MC-DPTAC www.amana-ptac.com 9
Product SPecificationS: PtH ModelS — reverSe-cycle Heating PerforMance
Product SPecificationS: Ptc / PtH ModelS — electric Heat PerforMance
(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Conguration)



**AXXX

**AXXX

**AXXX

**AXXX

**AXXX

**AXXX

**AXXX

**AXXX
Voltage ¹, ³ 230 / 208 230 / 208 230 / 208 230 / 208 265 265 265 265
BTU/h ⁵ 6,800 8,300 / 8,100 11,500 / 11,300 13,800 / 13,600 6,800 8,300 11,400 13,700
Amps ¹⁰ 3.9 4.2 5.8 7.0 3.1 3.7 5.0 6.1
Was ¹⁰ 585 / 570 715 / 700 1085 /1035 1350 / 1330 570 715 1080 1340
COP ⁵ 3.4 / 3.5 3.4 3.1 / 3.2 3.0 3.5 3.4 3.1 3.0
CFM (Dry) 370 360 370 410 370 360 370 410
COP = Coeciency of Performance; per AHRI Test Procedures, units are rated for capacies and eciencies.

¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity rangs conform to the Naonal Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
⁴ Overcurrent protecon for all units without electric heaters is 15 amps. Overcurrent protecon on 265-volt models must be cartridge-style me-delay
fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heang capacity and eciency based on unit operaon without condensate pump; unit automacally switches to electric heat at approximately 24°F
outdoor ambient.
⁶ Specify two-digit heater kW size to complete model number.
⁷ R-410A refrigerant used in all systems.
⁸ All units meet or exceed ASHRAE 90.1 standards.
⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protecon. Amps and Was notaon refers to compressor only.

















  
230/208V 2.5 1 8,500 6,800 - - 2,570 / 2,115 11.2 / 10.1 14.1 15 6-15 P
230/208V 3.5 1 12,000 9,900 - - 3,570 / 2,935 15.5 / 14.1 19.5 20 6-20 P
230/208V 5 1 17,100 14,000 - - 5,070 / 4,160 22.1 / 20.0 27.6 30 6-30 P
265V 2.5 1 - - - - 8,500 2,570 9.7 12.2 15 7-20 P
265V 3.7 1 - - - - 12,600 3,770 14.2 17.9 20 7-20 P
265V 5 1 - - - - 17,100 5,070 19.2 23.9 25 7-30 P

¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity rangs conform to the Naonal Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
⁴ Overcurrent protecon for all units without electric heaters is 15 amps. Overcurrent protecon on 265-volt models must be cartridge-style me-delay
fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heang capacity and eciency based on unit operaon without condensate pump; unit automacally switches to electric heat at approximately 24°F
outdoor ambient.
⁶ Total was for 15,000 BTU/h models; subtract 20 was for PT07/09/12
⁷ Specify two-digit heater kW size to complete model number.
⁸ R-410A refrigerant used in all systems.
⁹ All units meet or exceed ASHRAE 90.1 standards.
¹⁰ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.