Installation Instructions

DESCRIPTION
The PTAC Hydronic Kit is an enclosure kit that provides
complete coverage of all PTAC plumbing and coils while still
allowing access to controls. The kit can only be installed
where there is a central boiler for heating the water. It does
not affect unit heating and cooling operations. The hydronic
kit chassis slides out for service without removing any
hydronic plumbing. The electrical connections are plug-in
type to assist in kit installation.
NOTE: Heat pump models will operate on heat pump
function down to the switchover temperature before operat-
ing on hydronic heat.
Freeze Protection
For PTAC Hydronic Coil freeze protection on hot water
systems, the hydronic system should use an antifreeze
PTAC HYDRONIC HEAT KIT
HVK03E
AND
HWK03E
I
NSTALLATION
I
NSTRUCTIONS
IO-386B
February 2011
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This
includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention
to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is
more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to
instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific
good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices.
However, if there is a direct conflict between existing practices and the content of this manual, the
precautions listed here take precedence.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
solution. However, the addition of antifreeze will reduce the
capacity of the hydronic coil and affect system sizing. The
higher the antifreeze concentration, the greater the capacity
reduction. Therefore, for optimum unit performance, only use
an antifreeze concentration that will protect to the lowest
ambient temperature expected. A 20% solution will protect
to approximately 15°F. A 50% solution protect to -35°F.
Use an antifreeze that is formulated for hydronic use. DO
NOT USE AUTOMOTIVE OR PETROLEUM BASED PROD-
UCTS.
Tools Required
1/4 Inch Electric Drill
1/8 Inch Diameter Drill Bit
Center Punch and Hammer
6 Foot Rule
Combination Square
1/4 Inch Nut Driver or Socket
5/16 Inch Nut Driver or Socket
Torch, Solder, Flux, etc.
Goodman Company, L.P.
5151 San Felipe, Suite 500 • Houston, TX 77056
www.amana-ptac.com
© 2010 - 2011 Goodman Company, L.P.

Summary of content (12 pages)