User Manual

7) WIRING DIAGRAMS
B/O Option = “B” setting (default) means the shared
B/O terminal is energized while in Heat mode and o
in Cool. “O” setting means the shared B/O terminal is
energized while in Cool mode and o in Heat.
B (top two)
O (lower two)
Back of thermostat circuit board
For Heat Pump applications, the option below can be
le per the factory default.
B/O
R
Y
W2
W1
GH
GL
C
HP Reversing Valve
Heat Pump Compressor
Blower Fan (High Speed)
Blower Fan (Low Speed)
AMANA PHWT-A150H
THERMOSTAT
24V Power
*see note 3
24V Common
Auxiliary/Emerg Heat
*see note 2
*see note 1
NOT USED
B/O
R
Y
W2
W1
GH
GL
C
NOT USED
NOT USED
A/C Cooling
Blower Fan (High Speed)
Blower Fan (Low Speed)
AMANA PHWT-A150H
THERMOSTAT
24V Power
24V Common
**see note 3
Hea�ng Stage-1
**see note 2
**see note 1
UP TO 2H/1C HEAT PUMP APPLICATIONS:
(AMANA PTH & HEH PTAC MODELS):
UP TO 1H/1C CONVENTIONAL APPLICATIONS:
(AMANA PTC PTAC MODELS) **see note 1
* HEAT PUMP WIRING DIAGRAM NOTES:
Note 1: For Heat Pump applications the jumper wire
must be connected between W1 and Y.
Note 2: The “W2” terminal is used to call for Electric/
Auxiliary heat. If your Heat Pump PTAC does not have
Electric heat, then the “W2” terminal should not
be used and Installer Settings menu 10 (Aux. Stage
Oset) should be set to “OFF”.
Note 3: For PTAC units with only one fan speed
(single “G” fan wire), add a jumper wire (installer
provided) to bridge together “GH” and “GL. Connect
your fan wire to either terminal aer jumper wire has
been added.
** CONVENTIONAL WIRING DIAGRAM NOTES:
Note 1: For Conventional (cooling) PTAC units, the
jumper wire between Y & W1 should be removed and
Installer Settings menu 06 (System Type) must be set
to “Con”.
Note 2: If connecting to a Conventional PTAC unit
without electric heat, the W1 and W2 wire terminals
will not be used and Installer Settings menu 03
(Available Modes) should be set to “04: Cool Only”
Note 3: For PTAC units with only one fan speed
(single “G” fan wire), add a jumper wire (installer
provided) to bridge together “GH” and “GL. Connect
your fan wire to either terminal aer jumper wire has
been added.