PTAC Brochure/Spec Sheet

10
www.amana-ptac.com
Product Specifications: HEH Models (High-Eiciency Heat Pumps) —
Cooling/Heat Pump/Electric Heat


,
,
HEH073H
**AXXX
HEH093H
**AXXX
HEH123H
**AXXX
HEH153H
***XXX
HEH074H
**AXXX
HEH094H
**AXXX
HEH124H
**AXXX
HEH154H
***XXX
Voltage ¹
,
³ 230 / 208 230 / 208 230 / 208 230 / 208 265 265 265 265
Capacity (BTU/h) 7,100 / 7,000 9,000 / 9,000 11,600 / 11,400 14,200 / 14,000 7,700 9,100 12,000 14,400
Amps¹⁰ 4.1 / 4.1 4.7 / 4.7 6.2 / 6.2 7.4 / 7.4 3.6 4.2 5.4 6.4
Was¹⁰ 595 / 595 720 / 720 1,040 / 1,040 1,440 / 1,440 595 730 1,040 1,430
EER 13.0 / 13.3 12.7 / 12.7 11.5 / 11.5 10.2 / 10.2 12.4 12.4 11.5 10.0



,
5.4 5.4 5.4 8.9 3.6 3.6 3.6 7.8
CFM (Cool/Wet Coil)
High
340 330 340 390 340 330 340 390
Low
245 245 245 340 245 245 245 340
CFM (Dry Coil)
High
370 360 370 410 370 360 370 410
Low
270 270 270 370 270 270 270 370
Venlated Air, CFM (Fan Only)*
65* 65* 65* 65* 65* 65* 65* 65*
Dehumidicaon (Pints/Hr.) 1.7 2.2 3.6 4.1 1.7 2.2 3.6 4.1
Net Weight (lbs.)
107 111 114 125 107 111 114 125
Ship Weight (lbs.) 122 126 131 142 122 126 131 142
* Actual vent CFM performance will vary due to application and installation conditions.
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be car-
tridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
Heating capacity and eiciency based on unit operation without condensate pump.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
 Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to
compressor only.