PTAC Brochure/Spec Sheet
12
www.amana-ptac.com
Product Specifications: PMH Models — Cooling/Heat Pump/Electric Heat
230/208 Volts
Model
,
,
PMH
073G***XXX
PMH
093G***XXX
PMH
123G***XXX
Voltage 230 / 208 230 / 208 230 / 208
Capacity (BTU/h) 6,900 / 6,700 8,700 / 8,700 11,400 / 11,200
Amps
3.7 / 3.7 4.1 / 4.1 5.7 / 5.7
Watts
640 / 640 795 / 795 1,150 / 1,150
EER 11.9 / 12.0 11.7 / 11.8 10.8 / 11.0
Unit without Electric Heater
Min. Circuit Amps
,
,
5.4 6.0 8.0
CFM (Cool/Wet Coil)
High 340 330 340
Low 245 245 245
CFM (Dry Coil)
High 370 360 370
Low 270 270 270
Ventilated Air, CFM (Fan Only)* 65* 65* 65*
Dehumidification (Pints/Hr.) 1.7 2.2 3.6
Net Weight (lbs.) 128 132 135
Ship Weight (lbs.) 143 147 150
265 Volts
Model
,
,
PMH
074G***XXX
PMH
094G***XXX
PMH
124G***XXX
Voltage
,
265 265 265
Capacity (BTU/h) 7,700 9,000 12,000
Amps
3.2 4.2 5.1
Watts
655 775 1150
EER 11.7 11.6 10.4
Unit without Electric Heater
Min. Circuit Amps
,
,
4.9 6.0 7.2
CFM (Cool/Wet Coil)
High 340 330 340
Low 245 245 245
CFM (Dry Coil)
High 370 360 370
Low 270 270 270
Ventilated Air, CFM (Fan Only)* 65 65 65
Dehumidification (Pints/Hr.) 1.7 2.2 3.6
Net Weight (lbs.) 128 132 135
Ship Weight (lbs.) 143 147 150
* Actual vent CFM performance will vary due to application and installation conditions.
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and
disconnect switch PSHW04A.
Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;
maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be
cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance
Heating capacity and eiciency based on unit operation without condensate pump.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation
refers to compressor only.