PTAC Brochure/Spec Sheet

12
www.amana-ptac.com
Product Specifications: PMH Models — Cooling/Heat Pump/Electric Heat
230/208 Volts
Model
,
,
PMH
073G***XXX
PMH
093G***XXX
PMH
123G***XXX
Voltage  230 / 208 230 / 208 230 / 208
Capacity (BTU/h) 6,900 / 6,700 8,700 / 8,700 11,400 / 11,200
Amps
 3.7 / 3.7 4.1 / 4.1 5.7 / 5.7
Watts
 640 / 640 795 / 795 1,150 / 1,150
EER 11.9 / 12.0 11.7 / 11.8 10.8 / 11.0
Unit without Electric Heater
Min. Circuit Amps
,
,
 5.4 6.0 8.0
CFM (Cool/Wet Coil)
High 340 330 340
Low 245 245 245
CFM (Dry Coil)
High 370 360 370
Low 270 270 270
Ventilated Air, CFM (Fan Only)* 65* 65* 65*
Dehumidification (Pints/Hr.) 1.7 2.2 3.6
Net Weight (lbs.) 128 132 135
Ship Weight (lbs.) 143 147 150
265 Volts
Model
,
,
PMH
074G***XXX
PMH
094G***XXX
PMH
124G***XXX
Voltage 
,
265 265 265
Capacity (BTU/h) 7,700 9,000 12,000
Amps
 3.2 4.2 5.1
Watts
 655 775 1150
EER 11.7 11.6 10.4
Unit without Electric Heater
Min. Circuit Amps
,
,
 4.9 6.0 7.2
CFM (Cool/Wet Coil)
High 340 330 340
Low 245 245 245
CFM (Dry Coil)
High 370 360 370
Low 270 270 270
Ventilated Air, CFM (Fan Only)* 65 65 65
Dehumidification (Pints/Hr.) 1.7 2.2 3.6
Net Weight (lbs.) 128 132 135
Ship Weight (lbs.) 143 147 150
* Actual vent CFM performance will vary due to application and installation conditions.
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and
disconnect switch PSHW04A.
Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;
maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be
cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance
Heating capacity and eiciency based on unit operation without condensate pump.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
 Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation
refers to compressor only.