PTAC Brochure/Spec Sheet

13
Specifications and Accessories Catalog
Product Specifications: All Models — Electric Heat Performance
(Primary Heating for PTC, HEC, PMC Models; Auxiliary Heating for PTH, HEH, PMH Models; See below for Power Cord Configuration)
V
E
H
S (W)
N. 
S
N H (BTU/)
T
W
T
A
M. C
A
MOP
()
P
C
@ V @ V @ V
230/208V 1.5 / 1.2 1 5,100 4,200 - - 1,570 / 1,295 6.8 / 6.2 8.5 15 6-15 P
230/208V 2.5 / 2.1 1 8,500 6,800 - - 2,570 / 2,115 11.2 / 10.1 14.1 15 6-15 P
230/208V 3.5 / 2.9 1 12,000 9,900 - - 3,570 / 2,935 15.5 / 14.1 19.5 20 6-20 P
230/208V 5.0 / 4.1 1 17,100 14,000 - - 5,070 / 4,160 22.1 / 20.0 27.6 30 6-30 P
265V 1.5 1 - - - - 5,100 1,570 5.9 7.4 15 7-20P
265V 2.5 1 - - - - 8,500 2,570 9.7 12.2 15 7-20 P
265V 3.7 1 - - - - 12,600 3,770 14.2 17.9 20 7-20 P
265V 5 1 - - - - 17,100 5,070 19.2 23.9 25 7-30 P
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style
time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
Heating capacity and eiciency based on unit operation without condensate pump.
Total watts for 15,000 BTU/h models; subtract 20 watts for PT07/09/12
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
 All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.