PTAC Brochure/Spec Sheet
14
www.amana-ptac.com
Product Specifications: HEH Models — Reverse-Cycle Heating Performance
HEH073H
**AXXX
HEH074H
**AXXX
HEH093H
**AXXX
HEH094H
**AXXX
HEH123H
**AXXX
HEH124H
**AXXX
HEH153H
***XXX
HEH154H
***XXX
Voltage ¹
,
³ 230 / 208
265
230 / 208
265
230 / 208
265 230 / 208 265
BTU/h ⁵ 6,500 / 6,400 6,800 8,200 / 8,000 8,300 10,600 / 10,500 11,400 13,900 / 13,700 13,700
Amps ¹⁰ 4.1 / 4.1 3.6 4.7 / 4.7 4.2 6.2 / 6.2 5.4 7.4 / 7.4 6.4
Was ¹⁰ 600 / 600 600 735 / 715 735 1,085 / 1,065 1,075 1,440 / 1,440 1,430
COP ⁵ 3.8 / 3.7 3.6 3.6 / 3.6 3.5 3.3 / 3.3 3.2 3.1 / 3.1 3.1
CFM (Dry) 360 360 370 370 370 370 410 410
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;
maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models
must be cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
Heating capacity and eiciency based on unit operation without condensate pump.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Refer to electric heat performance data for total MCA and recommended overcurrent protection.
Amps and Watts notation refers to compressor only.
PTH073G
**AXXX
PTH074G
**AXXX
PTH093G
**AXXX
PTH094G
**AXXX
PTH123G
**AXXX
PTH124G
**AXXX
PTH153G
**AXXX
PTH154G
**AXXX
Voltage ¹
,
³
230 / 208
265
230 / 208
265
230 / 208
265
230 / 208
265
BTU/h ⁵ 6,500 / 6,400 6,800 8,200 / 8,000 8,300 10,600 / 10,500 11,300 13,900 / 13,700 13,700
Amps ¹⁰ 3.9 / 3.9 3.1 4.2 / 4.2 3.7 5.8 / 5.8 5 7.0/7.0 6.1
Was ¹⁰ 585 / 585 585 715 / 700 715 1,085 / 1,035 1,080 1,350 / 1,330 1,340
COP ⁵ 3.5 / 3.4 3.4 3.4 / 3.4 3.4 3.2 / 3.2 3.1 3.0/3.0 3
CFM (Dry) 370 370 360 360 370 370 410 410
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models
must be cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
Heating capacity and eiciency based on unit operation without condensate pump.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Refer to electric heat performance data for total MCA and recommended overcurrent protection.
Amps and Watts notation refers to compressor only.
Product Specifications: PTH Models — Reverse-Cycle Heating Performance