Product Specifications: PMH Models — Reverse-Cycle Heating Performance (cont.)
1,2,6,7,8,9
PMH073G
**EXXX
PMH074G
**EXXX
PMH093G
**EXXX
PMH094G
**EXXX
PMH123G
**EXXX
PMH124G
**EXXX
Voltage
3,4
230/208
265
230/208
265
230/208
265
BTU/h ⁵ 6,200 / 6,100 6,700 7,800 / 7,600 8,000 10,600 / 10,400 11,300
Amps ¹⁰ 3.6 / 3.4 3.2 4.3/4.3 4.2 5.9/5.9 5.1
Was ¹⁰ 600/600 595 735/715 710 1,085/1,065 1,065
COP ⁵ 3.3/3.3 3.3 3.4 / 3.4 3.3 3.1/3.1 3.1
CFM (Dry) 360 360 360 360 360 360
COP = Coeiciency of Performance; per ARI Test Procedures, units are rated for capacities and eiciencies.
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must
be cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
Heating capacity and eiciency based on unit operation without condensate pump;
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Refer to electric heat performance data for total MCA and recommended overcurrent protection.
Amps and Watts notation refers to compressor only