PTAC Brochure/Spec Sheet

8
www.amana-ptac.com
Product Specifications: HEC Models — Cooling/Electric Heat
230/208 Volts
Model
,
,
HEC
073H***XXX
HEC
093H***XXX
HEC
123H***XXX
HEC
153H***XXX
HEC
094H***XXX
HEC
124H***XXX
Voltage  230 / 208 230 / 208 230 / 208 230 / 208 265 265
Capacity (BTU/h) 7,000 / 7,000 9,200 / 9,000 11,900 / 11,700 14,800 / 14,500 9,100 12,200
Amps
 3.6 / 3.6 4.6 / 4.6 5.5 / 5.5 7.3 / 7.3 4.1 5.3
Watts
 535 / 555 750 / 770 990 / 1025 1,470 / 1,440 765 1,120
EER 12.6 / 13.0 11.8 / 11.9 11.2 / 11.3 10.2 / 10.2 11.7 10.7
Unit without Electric Heater
Min. Circuit Amps
,
,
 4.2 5.5 6.6 7.3 4.8 6.3
CFM (Cool/Wet Coil)
High 340 330 340 340 290 390
Low 245 245 245 245 264 264
CFM (Dry Coil)
High 370 360 370 370 310 310
Low 270 270 270 270 282 282
Ventilated Air, CFM (Fan Only)* 65* 65* 65* 65* 65* 65*
Dehumidification (Pints/Hr.) 1.7 2.2 3.6 4.1 2.2 3.6
Net Weight (lbs.) 97 101 102 113 102 102
Ship Weight (lbs.) 112 116 118 130 117 119
* Actual vent CFM performance will vary due to application and installation conditions.
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.
Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay
fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance
Heating capacity and eiciency based on unit operation without condensate pump.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
 Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.