User manual
Digital Monitor AMC-1DBx Series User Manual
100
Zone <Zone #> Relay <Relay #> <Schedule> <Phase> <Day, Same Day, Next Day> <Day #>
APPENDIX A.3 ALARM.LOG Items
The alarm log file messages can appear in the USB Storage device when the menu item Log File>Alarm is
enabled.
The Buzzer messages will appear when it is activated or cleared for various reasons. The Buzzer message
contains the following format:
Buzzer <Activated or Cleared> <reason>.
These reasons can also be blank or:
checking the Data Base,
System Failure,
Alarm, Device Failure,
SILENCE Pushbutton,
RESET_RELAY Pushbutton,
TEST Pushbutton,
Sensor Alarm.
In some cases the buzzer cleared reason is log on a separate line as follows:
System Failure Cleared
Sensor Alarm Cleared
Device Failure Cleared
Test Pushbutton Cleared
Data Base Failure Cleared
Cleared Data Base Good.
The Alarm LED message will appear when front panel LEDs are cleared or activated. The ALARM LED
message contains the following formats:
<Fault Alarm> LED <Cleared or Activated>
Alarm<number> LED <Cleared or Activated>
The Start Alarm Sensor message will appear when sensor delay timer is started. The level can be 1 to3
and sensor number can be 1-988. The Start Alarm Sensor message contains the following format:
Start Alarm <Level> Sensor:<Sensor #> Delay
The Increasing, Decreasing, Window Alarm message will appear when sensor alarm state becomes
active. The Level can be 1 to 3 and sensor number can be 1-988. The Increasing, Decreasing and Window
Alarm message contains the following formats:
Increasing Alarm <Alarm Level> Sensor:<Sensor #> Active
Decreasing Alarm <Alarm Level> Sensor:<Sensor #> Active
Window Alarm <Alarm Level> Sensor:<Sensor #> Active
The Alarm Relay message will appear when Relay alarm state changes. The following alarm states and
timer types are possible; Pending or Activated with Delay Timer or MRT (Minimum Run Time) and PRT
(Post Run Time) values with and without LATCHING. The Alarm Relay message contains the following
format:
Alarm Relay:<Alarm Level> <Pending or Activated> with <timer type> <and Latching>