User manual
Digital Monitor AMC-1DBx Series User Manual
15
4.1.2.1 System Configuration DIP Switch
The functionality for the supplied dipswitch is identified in Table 4-1.
Table 4-1: System Configuration DIP Switch Functionality
Switch
Function
Normal Position
Description
1
Audio Disable
ON OFF to disable audio alarm
2
Delay Disable
ON OFF to disable all sensor activation delays
3
Zero Buff Disable
ON OFF to disable zero buffering
4
Min Run Disable
ON OFF to disable all relay minimum run times
5
CAL Mode
OFF ON to activate CAL mode
6
Post Run Timer
ON OFF to disable the POST run timer
7, 8 Language Select
See Description
7 OFF, 8 OFF = ENGLISH
7 ON, 8 OFF = FRENCH
7 OFF, 8 ON = SPANISH (future)
7 ON, 8 OFF = GERMAN (future)
Refer to
Figure 4-3: Digital Monitor Components for the location of the System Configuration DIP switch.
Figure 4-4 System Configuration DIP Switch
1. Audio Disable: When in the OFF position this switch will prevent the external buzzer and
annunciator from activating on sensor alarm or device failure. Please refer to 4.1.2.10 for
connection detail of the buzzer and annunciator. The buzzer can be activated for the
following reasons:
• System or Device (Sensor/Relay/Analog Output) Failure,
• Sensor or Zone Sensor Alarm,
• Power-up Data Base Checking,