• SILENCE, RESET_RELAY, TEST or Data Base initialization pushbutton pressed.
Note: Audio beeps for SlLENCE, RESET_RELAY, TEST or Data Base initialization
pushbutton action are not disabled by this switch.
2. Delay Disable: When in the OFF position this switch will override and programmable
delays associated with sensor activation. Sensor activation delays can be configured from 0-
3600 seconds for Alarm1-3 and Fail sensor thresholds.
3. Zero Buffering Disable: When in the OFF position this switch will override the
programmable Zero Buffering value. Zero Buffering is used to inhibit display of gas
concentration below a specific threshold. When below this value the sensor will display 0
gas concentration. It can be configured from 0-5% of full scale gas concentration and
applies to the all sensors. Note: An analog output will still assert its assigned zone sensor(s)
gas concentration regardless of the zero buffer setting.
4. Minimum Run Timer Disable: When in the OFF position this switch will override any
relays currently executing their minimum run timer requirements, thus releasing them from
their energised or de-energised state. Minimum run timers can be configured for each relay
from 0 to 60minutes and will hold an active relay for the duration once a sensor/zone sensor
alarm has occurred. Note: Scheduled zone events don’t utilise Minimum Run Timers.
5. Calibration Mode: When in the OFF position this switch will ensure all sensor/zone sensor
alarms will be de-activated and ignored. This will include any current relay activations held
active by their associated minimum and post run timers. Fail devices status will still be
displayed, but external audio buzzer and annunciator will be de-activated. Calibration mode
should be used when making configuration changes through logged in menu navigation,
AMC Manager downloading or MODBUS writes to prevent unnecessary transitions on
building’s fan controller driven by relays. Note: An analog output will still assert its assigned
zone sensor(s) gas concentration regardless of calibration mode.
6. Post Run Timer Disable: When in the OFF position this switch will override any relays
currently executing their post run timer requirements, thus releasing them from their
energised or de-energised state. Post run timers can be configured for each relay from 0 to
60minutes and will hold an active relay for the duration once a sensor/zone sensor alarm
has cleared. Note: Scheduled zone events don’t utilise Post Run Timers.
4.1.2.2 RS-485
Five RS-485 interfaces are provided on terminal blocks, one for each of four MODBUS
interfaces to transmitters and a single RS-485 interface to a Building Automation System. To
facilitate field replacement, the RS-485 driver IC is mounted in a socket.
CAUTION
Power down the Digital Monitor before replacing any RS-485 driver ICs.
Ensure proper ESD precautions are taken before handling ICs.