User manual

Digital Monitor AMC-1DBx Series User Manual
25
A shielded cable is employed to wire this signal to the target system. For each local
analog output, a three-position terminal block is provided.
Table 4-12 shows the pin-out and description for the integral analog outputs and terminal
blocks (39, J40).
Table 4-12: Integral Analog Output and Terminal Block Pin-out
Pin
1 2 3 4 5 6
Front Row
Ch1, 3
Ch 1
Signal
Signal
Ground
Chassis
Ground
Ch 3
Signal
Signal
Ground
Chassis
Ground
Back Row
Ch2, 4
Ch 2
Signal
Signal
Ground
Chassis
Ground
Ch 4
Signal
Signal
Ground
Chassis
Ground
Refer to
Figure 4-3: Digital Monitor Components for the location of the Analog Output Terminal
block.
Figure 4-12 Integral Analog Output Terminal Block
The analog output is configured for either voltage or current by the use of a dip switch.
Table 4-13: Analog Output and Voltage vs Current Switches
Channel Switch
Analog Output 1
SW12
Analog Output 2
SW14
Analog Output 3
SW11
Analog Output 4
SW13