User manual

Digital Monitor AMC-1DBx Series User Manual
28
5 INSTALLATION
Follow the guidelines in this section for proper locations and installation of the Digital
Monitor AMC-1DBx. In addition to these instructions, ensure installation is compliant with
local building and electrical codes. This section covers topics related to installation
location, mounting, cable selection, wiring instructions and monitor function
programming for the following products:
AMC Digital Monitor 1DBx
AMC-1DPS
AMC-1DA-RPT4 (RS-485 4-Port Repeater)
AMC-1DA-RPT (RS-485 Single Port Repeater)
AMC-1D-8R (RS-485 8-Relays, 2-Analog Outputs)
5.1 MOUNTING INSTRUCTIONS
Follow the guidelines in this section for proper locations and installation of the Digital
Monitor AMC-1DBx series monitor. In addition to these instructions, ensure installation is
compliant with local building and electrical codes. This section covers topics related to
installation location, mounting, cable selection, wiring instructions and monitor function
programming for the Digital Monitor AMC-1DBx series monitor.
5.1.1
AMC-1DBx Digital Monitor Mounting
Securely fasten the AMC-1DBx gas monitor on a solid, non-vibrating surface or
structure. Install the unit where it is not exposed to rain or water spray. Install in an area
where the local concentration of gas is unaffected by the presence of ventilation systems
and away from sources of interference gases. Mount the monitor where the unit can be
observed periodically.
For most applications the monitor should be mounted at eye level (1.2 -1.8 m (4-6 ft)
from the floor) using the mount provided on the enclosure.
See
Figure 5-1for mounting-hole locations.
WARNING
ALL CABLE ENTRY MUST BE MADE THROUGH THE BOTTOM OF THE
MONITOR ENCLOSURE ONLY. OTHER ENTRY LOCATIONS COULD
ALLOW FOREIGN MATERIAL TO ENTER THE ENCLOSURE, CAUSING
POSSIBLE DAMAGE TO THE INTERNAL COMPONENTS.