Please refer to the supplementary manual 3370405A, AMC Manager User Manual.doc
for details.
The database can be saved or restored from or to the monitor through the serial
communication link or through ADF file placed on a USB storage device.
Using the serial communication link requires some initial menu configuration as
described in the menu navigation section Set Options, Serial Mode.
Using USB storage device to restore database will requires a system restart. Please
refer to the section DATABASE ON USB STORAGE DEVICE.
6.9 BACNET-IP INTERFACE
BACnet is a communications protocol for building automation and control networks. It is
an ASHRAE, ANSI, and ISO standard protocol. The BACnet-IP offers plug and play of
objects used for monitoring the state of the system over Ethernet.
Please refer to the supplementary manual 3369405A, AMC-1DBx BAS Interface
Manual.doc for details.
6.10 BAS MODBUS-RTU INTERFACE
The BAS MODBUS-RTU is a RS-485 physical link using the MODBUS-RTU digital
communication protocol that facilitates the monitoring of the system operation.
Additionally, the BAS MODBUS-RTU can configure the database associated with this
product and can be used as alternative to using the menu buttons or AMC Manager PC
Tool.
Please refer to the supplementary manual 3369405A, AMC-1DBx BAS Interface
Manual.doc for details.
6.11 DATABASE ON USB DEVICE
Once the monitor’s database is configured and stored in Non Volatile RAM a USB
storage device can be used to save it. This database can be loaded in AMC Manager or
used to restore the monitor’s database at a later time.
This section contains a procedure for saving database on to USB storage device and a
procedure for restoring the database from the USB port.
In order to save the Database using USB storage device:
1. Install a USB storage device into the USB port on the monitor.
2. Log in to the system through the menu described in the section menu system
Logging In.
3. Log out of the menu system.