User manual
Digital Monitor AMC-1DBx Series User Manual
61
Units units.(PPM, PPB, %LEL,)
PPM
Set Full Scale Shows the setting of full scale.
Full Scale √S#001
100.0 PPM
Set Zero Scale
Shows the setting of zero scale. (Only
available on certain gas types. See
Appendix of gas types)
Zero Scale √S#001
0.0 DegC
Set Alarm
Conditions
Shows the setting of alarm conditions.
(Incr. Decr. Disabled, Window)
Alm Condition √S#001
Incr Alarm
Number of Alarms Shows the setting for the number of
alarms. (1-3. See Appendix of gas types)
No of Alarms √S#001
2
Select Alarm Relays Shows the setting of alarm relays.
(1= relay; A1=Alarm Point 1; S=sensor)
Alarm Relay A1√S#001
1
Set Activation Delay Shows the setting of the activation delay.
(in seconds) – Activation delay is the
amount of time a sensor must meet the
alarm threshold to trigger the sensor
alarm.
Act. Delay A1 √S#001
14 sec
Set Alarm
Thresholds
Shows the setting of the alarm
thresholds.
Alarm Set A1 √S#001
25 %FS 25.0 PPM
Set Fail Alarm Relay Shows the setting of the fail alarm relay.
(select 1-256); (relay=10)
F-Alarm Relay √S#001
10
Set Fail Activation
Delay
Shows the setting of the fail activation
delay. (select 0-3600 seconds)
Act. Delay A4 √S#001
315 sec
Set Fail Threshold Shows the setting of the fail threshold.
Fail Thresh √S#001
2.0 mA
Note:
The digital monitor uses an internal representation of a 4 – 20 mA interface when
dealing with sensors. Operational sensors have gas concentrations represented
by mA concentrations between 4 and 20 mA. When a digital sensor is in failure
mode, the representation of it’s gas concentration will be set to 0 mA.