User manual

Digital Monitor AMC-1DBx Series User Manual
63
To access the Select Relay menu
1. Log into the gas monitor.
2. At the Log In screen, press ENTER.
3. Enter the valid 4-character password.
4. Press ENTER.
The Select Sensor menu item is displayed.
5. Press the DOWN pushbutton.
The Select Relay menu item is displayed.
Table 6-2 describes the submenu items found in the Select Relay menu.
Table 6-2: Select Relay Menu
SUBMENU DESCRIPTION
DISPLAY
Select Relay Allows the selection of the relay of
interest for displaying the relay
configuration. (1-256)
Select Relay
1
Set Relay Admin
State
Shows the selection of the relay admin
state. (Enable/Disable)
Select Admin R#001
Enable
Set Interface Shows the selection of the relay
interface. (Local, Modbus1-4)
Rly Interface R#001
Local
Set Relay Address
Shows the selection of the relay address.
(1-256)
Rly L AddressR#001
1
Set Relay Instance Shows the selection of the relay
instance. (1-32) (L=local)
Rly L InstanceR#001
1
Set Alarm Count Shows the selection for the number of
alarms. (1-99)
Alarm count R#001
22
Set Minimum Run
Timer
Shows the minimum run time. (0-60,
ensures minimum relay active state
regardless of alarm/fail event)
Min Run Time R#001
5 min
Set Post Run Timer Shows the selection of the post run
timer. (0-60, holds the relay in active
state after alarm/fail event has cleared)
Post Run Time R#001
10 min
Set Normal State Shows the setting for the normal state
of the relay. (De-energized/Energized)
Relay Normal R#001
De-energized
Set Relay Type Shows the setting for the type of relay.
Relay Type R#001
Non-latching