To access the Set Options submenu
1. Log into the gas monitor.
2. At the Log In screen, press ENTER.
3. Enter the valid 4-character password.
4. Press ENTER.
The Select Sensor menu item is displayed.
5. Press the DOWN pushbutton.
The Select Relay menu item is displayed.
6. Press the DOWN pushbutton again.
The Select Zone menu item is displayed.
7. Continue pressing the DOWN pushbutton until the Set Options submenu is
displayed.
Table 6-4 describes the submenu items found in the Set Options menu.
Table 6-4: Set Options Submenu
SUBMENU DESCRIPTION
DISPLAY
Display Mode Allows the selection of the display mode.
(Disp All Data; Disp All Relay; Disp New
Alarms only; Disp Alarms only; Disp Raw
input)
Display Mode
Disp All Data
Show Location
Labels
Allows the selection of showing the
location labels. (Yes/No)
Show Location Labels
Yes
Default Fail
Threshold
Shows the selection of the default fail
threshold. (0.1-4.0mA)
Def Fail Threshold
1.9 mA
Power Up Alarm
Delay
Shows the selection of the power up
alarm delay setting. (1-999 seconds)
Power Up Alarm Delay
60 sec
Acknowledge Timer Shows the selection of the acknowledge
timer setting. (Blank; 0-60 minutes
infinite)
Ackn Timer
0 min
Audible Alarms Shows the selection of the audible alarm.
(All Alarms; all Alarms & Fail;
H-Alarms On)
Audible Alarms
All Alarms & Fail
Audio Cadence Shows the selection of the audible
cadence. (Continuous; Pulse)
Audio Cadence
Continuous
Zero Buffering Shows the selection of zero buffering.
(0.0 %FS to 5.0 % FS)
Zero Buffering
2.0 %FS