SET BACnet CONFIGURATION
The AMC-1DBx digital monitor supports BACnet or EthernetIP and RS-485.
In order to support BACnet, the following site-specific attributes require configuration:
Set Device Name
Set Device ID
Set Network Number
Set Transport
The Set BACnet Configuration submenu is displayed in Figure 6-7.
Figure 6-7: Set BACnet Configuration Submenu
To access the Set BACnet Configuration submenu
1. Log into the gas monitor.
2. At the Log In screen, press ENTER.
3. Enter the valid 4-character password.
4. Press ENTER.
The Select Sensor menu item is displayed.
5. Press the DOWN pushbutton until the Set Interface submenu is displayed.
6. Configure the Set Interface submenu items as necessary.
Once the configuration of the Set Interface submenu items has been completed,
the IP Configuration submenu is displayed.
Once the configuration of the IP Configuration submenu is completed, the Set
BACnet Configuration submenu is displayed.
Table 6-7 describes the items found in the Set BACnet Configuration