Digital Monitor AMC-1DBx Series User Manual
77
submenu.
Table 6-7: Set BACnet Configuration Submenu
SUBMENU DESCRIPTION
DISPLAY
BACnet BAS
SetDevice Name
Allows the setting of the device name.
(Set Device Name, Set Transport, Set
Network Number, Set Device ID)
BACnet BAS
Set Device Name
BACnet Name Shows the selection of the BACnet
name. (maximum of 20 characters)
BACnet Name
AMC-1DBx BACnet Name
BACnet ID Shows the selection of the BACnet ID.
(any number between 0 and 4,194,303)
BACnet ID
1000003
BACnet Network
Number
Shows the selection of the BACnet
network number. (0-65534)
BACnet Network Number
00000
Configure BACnet
Transport
Shows the selection of the BACnet
transport types. (BACnet IP, BACnet
MSTP).
(If transport set to BACNET IP, go to
Set BAC IP UDP Port)
Set BACnet Transport
BACNET MSTP
Set BAC MSTP
Address
Shows the selection of the BAC MSTP
address. (Min value=1, max value=127,
default value=127)
Set BAC MSTP Address
127
Set BAC MSTP Max
Master
Shows the selection of the BAC MSTP
max master number. (Min value=1, max
value=127, default value=127)
BAC MSTP Max Masters
127
Set BAC MSTP
Timeout
Shows the selection of the BAC MSTP
timeout. (20-100ms, default value=20ms)
BAC MSTP Timeout
72 ms
Set BAC IP UDP
Port
Shows the selection of the BAC IP UDP
protocol. (UDP port is a 16-bit value
between 47808 and 47823. BACnet
typically uses port 47808)
Set BAC IP UDP Port
47820
Set BAC IP BBMD
Address
Shows the selection of the BAC IP
BBMD address. (0-255 for each network
segment) A non-zero value will require
registration with a BACnet Broadcast
Master Device.
BAC IP BBMD Address
000.000.000.000
Set BAC IP
TimetoLive
Shows the selection of the BAC IP Time
to Live setting (0-65535 seconds).
BAC IP TimetoLive
00060 seconds