User manual

Digital Monitor AMC-1DBx Series User Manual
81
To access the Analog Out submenu
1. Log into the gas monitor.
2. At the Log In screen, press ENTER.
3. Enter the valid 4-character password.
4. Press ENTER.
The Select Sensor menu item is displayed.
5. Press the DOWN pushbutton until the Set Interface submenu is displayed.
6. Configure the Set Interface submenu items as necessary.
Once the configuration of the Set Interface submenu items has been completed, the IP
Configuration submenu is displayed.
Once the configuration of the IP Configuration submenu is completed, the BACnet
Configuration submenu is displayed.
Once the configuration of the BACnet submenu is completed, the MODBUS BAS
submenu is displayed.
Once the configuration of the MODBUS BAS submenu is completed, the Analog Out
submenu is displayed.
Table 6-9 describes the items found in the Analog Out submenu.
Table 6-9: Analog Out Submenu
SUBMENU DESCRIPTION
DISPLAY
Analog Out Allows the setting of the analog out
menu items which configure the system
analog outputs.
Analog Out
Analog Out
Select Analog Out #
Shows the setting of the analog out item.
(Analog Out Admin, AnaOut Interface,
AnaOut Range, AnaOut Scale, AnaOut
Type, AnaOut Sample)
Analog Out
AnaOut Interface
Analog Output
Number
Shows which analog interface is to be
configured. (1 to 128)
Select Analog Out #
1
Analog Output
Admin State
Shows the setting of the analog output
admin state. (Out of Service,
Disable/Enable) Out of Service mode
enables the analog output at a fixed
0.0mA level when proper communication
to the device is achieved.
Aout Admin O#001
Enable
Analog Output
Interface
Shows the setting of the analog output
interface. (local, Modbus1, Modbus2,
Modbus3, Modbus4)
Aout InterfaceO#001
Modbus1
Analog Output
Address
Shows the setting of the analog output
address. (1-247)
Aout Address O#001
101