User manual

Digital Monitor AMC-1DBx Series User Manual
82
Analog Output
Instance
Shows the setting of the analog output
instance. Instances can be local (L) or
remote (R).
Aout RInstanceO#001
2
Analog Output
Range
Shows the setting of the analog output
range. (0-20mA, 4-20mA)
Aout Range O#001
4-20mA
Analog Output Scale Shows the setting of the analog output
scale. (0.1 to 20.0) Scale will multiply the
outputs level by the scale value. Using a
scale greater then one (1) can saturate
the output.
Aout Scale O#001
20.0
Analog Output Type Shows the setting of the analog output
type. (Average, peak) The Average and
Peak selection refers to how zone data is
assigned to this output. Peak will select
to highest level from the list of zone
sensors while average will calculate a
mean level from the list of zone sensors.
When an Analog Output is assigned to
more than one zone, the higher
numbered zone’s data will prevail.
Aout Type O#001
Peak
Analog Output
Sampling Period
Shows the setting of the analog output
sampling period (0 to 60 seconds).
The sampling period provides a running
averaging of up to 60 samples over a
period of 60 seconds. This allows output
smoothing over the sampling period.
System performance and periodic device
updates prevent ideal smoothing.
Aout Sample O#001
60 seconds