Technical data

1. Correct positioning
It is possible to place the unit against the wall. The
base of the unit at the air inlet must be clear of any
obstruction by at least 400 mm. The top of the unit must
be clear of any obstruction by at least 400 mm.
2. Electrical connections
The Amcor D-1000 must be connected to the power
supply with appropriate leads.
The cord should pass through the hole with the rubber
grommet on the top left side of the unit. Properly fused
disconnect switches must be installed between the unit
and the power source.
3. Condensate drainline
The end of the condensate drain pipe protrudes from
the base of the dehumidifier on the back extending the
pipe long enough to reach the nearest drain outlet and
insert its end.
Check that the condensate water tube does not at any
point slope upwards, which would cause a blockage.
A U trap, located in a place where the water will not
freeze, will prevent unpleasant odours from being drawn
into the conditioned space. Where it is necessary for
condensate pipework or an electrical cable to pass
through a wall, a lined or sleeved hole should be made.
Ensure that pipework and cables do not touch each other.
The hole should be sealed when installation is completed.
INSTALL AND OPERATE YOUR AMCOR D-1000
4. Humidity control
The unit is controlled by a manually adjustable,
automatic humidistat, that switches the dehumidifier On
and Off, to maintain the desired humidity level.
The humidistat should be 24V wall mounted type.
It should be well ventilated and positioned at a height of
about 1.50 m above the floor. The two leads of the
humidistat should be connected to the appropriately
marked terminals on the terminal strip in the electrical
control panel. Those two leads should then be fed to the
vertical, white plastic conduit attached to the internal
dividing panel. Set the humidistat to the level of relative
humidity required in the controlled space. For example,
for normal comfort conditions the setting should be about
50% R.H.
5. Filter
The filter should be regularly checked and if necessary,
removed for cleaning or replacement. Slide the framed
filter forwards and lift it out. Hold it under streaming
water and flush it clean. Let the trapped water drip off the
filter fabric and replace the dried filter in reverse order.
6. De-icer control
Your Amcor D-1000 is equipped with an automatic
de-icer control that guards against ice forming on
refrigeration coils, in low temperature operation, by
shutting off the compressor.
Note: The fan will keep running until all the ice has
defrosted and then, the unit will start up again.
4
AMCOR MODEL D-1000
The Amcor D-1000 is a large capacity unit designed to
run highly efficiently in a domestic, commercial or
industrial environment.
The D-1000 keeps air dry and comfortable, prevents
condensation, and creates a better climate to prevent
damages caused by exessive humidity, such as: rusting of
equipment, dry rot of walls, mould growth in store
romms, etc.
It is ideal for places such as: restaurants, bars, printing
presses, indoor swimming pools, jacuzzis, garages,
animal enclosures, cellars, stores, boat sheds, weekend
cottages, archives, etc.
It can be positioned against the wall on legs.
Model D-1000