Operating instructions
PORT USE Types
TERMINAL - Used to upload and download setup information for the AD2150 from a PC. Select this use type when using the
AD2150SW12B software package. To obtain consistent performance from a PC, a 4800 baud rate is recommended.
KEYBOARD - Enables keyboard (or computer) control inputs to the port. For this use set Data Bits to 8, Parity to NONE, and
Stop Bits to 1. When a Port Expander is used, the port baud rate must be set to 4800, and the keyboards set to 1200.
ALARM - Used for an Alarm Interface Unit connection for input of alarm codes to the AD2150. Each alarm event message
sent to this port generates an output message to a serial printer via the PRINTER port (see below).
PRINTER - Outputs messages for all alarm and video loss events, both occurrence and removal, to a serial printer.
The ALARM message format is as follows:
05-MAR-1993 13:23:26 CONTACT 0001 CAMERA 0001 MONITOR 0001 CONTACT OPENED
Date of Event Contact Number Monitor Number Alarm Status
that caused Alarm armed for that contact
Time of Event Camera Number associated with that contact
Alarm Status: CONTACT OPENED - indicates that the alarm has been cleared/reset (Instant Clear)
TIMED OUT - indicates that the alarm was removed by timeout (Auto Clear)
ACKNOWLEDGED - indicates that the alarm was cleared by manual acknowledge
When the alarm first occurs, the Alarm Status part of the message is blank.
4-16
MENU PROGRAMMING - PORT MENU