RS-232 PROTOCOL
UP to four RS-232 controllers can be connected to the MPLT (requires AD2081 Rs-232
port expander). Controllers can be ADDTE, AD2088, ADC200/300, or ADCC1100
keyboards.
• A maximum of 1000 feet @ 1200 baud
• Repeat Mode must be set to OFF
• Use recommended BELDEN cable 88102 (plenum)
• Use recommended BELDEN cable 9729 (non-plenum)
Note: RS232 range is specified with the recommended cable types and at 1200 baud
only.
RS-485 Protocol Guideline
• Up to eight RS-485 controllers can be connected to the MPLT. Only ADCC200 or
ADCC300 keyboard supports RS-485 protocol.
• A maximum of 3300 feet @ 1200 baud.
• One shielded twisted pair, 22 AWG, BELDEN cable 8761 (plenum)
• One shielded twisted pair, 22 AWG, BELDEN cable 8760 (non-plenum)
• Requires biasing/termination on RS-485 network such as matrix, keyboard or dome.
• Bi-directional data flow
• Up to three matrixes can be daisy chained
SENSORNET Protocol Guideline
• Up to 32 Sensornet devices per Sensornet link can be connected to the MPLT.
Sensornet devices include other MPLT's or domes.
• Maximum of four repeaters in a Sensornet network.
• Use recommended BELDEN cable 88442 (plenum)
• Use recommended BELDEN cable 9407 (non-plenum)
• Follow Sensornet termination rules (8000-0970-01)
AD UTC Protocol Guideline
• Supports ULTRA 7 vers.1.05 or higher dome control via coax cable
• Bi-directional communication capability
• Data rate of 38400 BPS or greater
• Maximum of 2300 feet (700 metres)