Master Switch User Guide AP9210

27
MasterSwitch 100V – User Guide
27
Chapter 7:
Using
SNMP
This chapter briefly describes the APC MasterSwitch-MIB (provided on the diskette that came with the
MasterSwitch as PDU.
MIB) and how to use that MIB to configure and control output power from the
MasterSwitch, as a unit, or from each outlet, individually. This chapter also briefly describes the MasterSwitch-
MIB and MIB-II traps the MasterSwitch can send.
Note: This chapter assumes you are familiar with how to load and compile a MIB at the
NMS you will be using for SNMP control, and are proficient at using its SNMP
browser. See your NMS documentation for more information on loading, compiling
and using a
MIB. For more information on the MasterSwitch-MIB, see the
descriptions provided in the
SNMP browser for each OID, or use a text editor to
read a copy of the PDU.MIB.
Functions
You can use SNMP to:
n Define NMSs that can receive SNMP traps (using apcmgmt OIDs).
n Restart the MasterSwitch SNMP agent (using apcmgmt OIDs).
n Control master power by turning on, turning off or rebooting all MasterSwitch outlets (using
sPDUMasterControl OIDs).
n Define a master power on delay time value for providing master power to the outlets (using an
sPDUMasterConfig OID).
n Define a power on value for each outlet so that you can sequence the power output from the
MasterSwitch outlets (using
sPDUOutletConfig OIDs).
n Turn off, on or reboot any outlet, individually (using sPDUOutletControl OIDs).
n Define a name for the MasterSwitch
(using an sPDUMasterConfig OID).
n Define a device name for each outlet (using sPDUOutletControl OIDs).
n Define how long power remains off during reboot cycles (using an sPDUMasterConfig OID).
n Access information about factory preset values (using sPDUIdent OIDs).
You cannot use
SNMP to:
n Define the network configuration values needed by the MasterSwitch.
Note: When a BOOTP server (Chapter 2) is not being used, the console program must be
used to initially define these values. Once these values are defined, and
BOOTP is
disabled, you can use the console program or the embedded Web control to modify
the values.