Technical information

FEEDER AND BRANCH CIRCUITS
21
2. Disconnecting means
194R 1494V
The main disconnecting means is a necessary part of all electrical equipment but
can be provided by the final user (unlike the provisions of European standards).
In this case it is necessary to clearly specify the characteristics of the device in the
attached documentation.
In this section,
the devices suitab le f or s witching and their sizing independently of
their nature will be analyzed (switch or circuit breaker ).
It is possible to use the devices suitable for disconnecting to the function of
overload protection of electrical equipment.
2.1 Sizing the switch in accordance to UL 508
First of all it is necessary to distinguish between switch and circuit breaker.
Inverse-time or instantaneous-trip circuit breaker UL489 “Molded-Case Circuit
Breakers, Molded-Case Switches and Circuit Breaker Enclosures)
The total current (obtained by adding the FLA and the rated currents of all the
branch circuits) should not be more than 80% the size of the switch. It may be
more useful to express the same rule backwards: the size of the switch should not
be less than 125% of the total current.
EXAMPLE
Motor 7.5HP,230V,3ph
Table 50.1 > FLA = 22A
The circuit breaker shall have a size of
at least 1.25 x (22 + 8+ 4) > = 42.5A
For example a 140U-H2C3-C50 can be used