FEEDER AND BRANCH CIRCUITS
22
Disconnect switch (or switch with fuses)
(UL 489 or UL 98, “Enclosed and Dead-
Front Switches”
Sizing follows different rules according to the type of load.
a) one or more loads, no motor: the size in current of the switch should not be
less than 115% of the total current (sum of the rated currents of all the
branch circuits).
b) a single motor: the power size (hp) of the switch should be shown in current
(using table 50.1 of UL 508A): this value obtained shall not be less than 115%
of the FLA (also obtained from tab. 50.1)
c) one or more motors and other loads: the power size (hp) of the switch shall
be shown in current (using tab.50.1 of UL 508A): this value shall not be less
than 115% of the FLAs of all the motors plus the rated currents of all the
other loads.
EXAMPLE
230V Three-phase system
The current for the sizing of the switch is: (1.15x22) A + 4 A + 8 A = 37.3 A
Now it is necessary to choose a switch with a size in power such that the current
received as in table 50.1 is above 37.3A: at 230V a switch of 15 hp (corresponding
with 42A) is required.
Sect. 1.25 x (22 + 8 + 4) >= 42.5A
Cond. 1.25 x 22 + 1.25 x 8 + 4 > = 41.5 A
AWG 10 (40A)