Technical information

FEEDER AND BRANCH CIRCUITS
23
The suitable IEC/UL/CSA component is a 194R-NN060P3 (CCN,WJAZ,
conforming to UL 489) while in a NEMA start a 1494F-N60 (CCN,WHTY,
conforming to UL 98) is used, both with power rating equal to 15 hp (230V).
2.2 Sizing according to the CEC for the Canadian market
The sizing regulations are simplified because no distinction is made between
circuit breaker and switches and only the following rules are applied:
•size in current of the device should not be less than 115% of the current of the
largest motor plus the sum of all the FLAs of the other motors and all the rated
currents of the various loads from the motors.
•The power size of the device, if indicated should not be less than the power of
the largest motor.
2.3 Sizing in accordance with the NEC
The sizing of the switching device in the NEC requires the verification of two
different conditions, depending on the use of a power characterized component
(switch: hp rating) or characterized in current (circuit breaker: rating in A):
however some exceptions are applied. No other distinction is made between
circuit breaker and switches.
•Sizing in current: the size in current of the device should not be lower than
115% of the total current, obtained as the sum of the FLA of all the other loads.
•Sizing in power: two values are calculated, one relative to the sum of the FLAs
(current at full load, tab 430.250 of NEC or tab. 50.1 of UL 508A) and one to the
sum of the LRA (current with the rotor blocked table 430.251(B) of NEC) of all
the motors.The nominal currents of all the other loads (not motor) should be
Sect. (1.15x22) + 8 + 4 >=37.3A
Cond. 1.25 x 22 + 1.25 x 8 + 4 > = 41.5 A
AWG 8 (50A)